    SINGLE-PACKAGE GAS HEATING/ELECTRIC COOLING UNITS Model 582A Sizes 018-060 1-1/2 to 5 Nominal Tons Low NOx Models Available Form No. PDS 582A.18.2 Single-Package Rooftop Units with. • Direct Spark Ignition • Low Sound Levels • AFUE ratings up to 81.1% • 10 SEER AVAILABLE OPTIONS One-piece heating and cooling units with low sound levels, eas ...

  • Bryant BRYANT 582A - page 2

    2 Low Sound Ratings ensure a quiet indoor and outdoor environ- ment with sound ratings as low as 7.5 bels. (See ARI capacity charts for individual values.) Easy-to-Service Cabinets provide easy single-panel acces- sibility to serviceable components during maintenance and installation. The basepan with integrated drain pan provides easy ground level ...

  • Bryant BRYANT 582A - page 3

    ARI* CAP ACITIES COOLING CAP ACITIES AND EFFICIENCIES UNIT 582A NOMINAL T ONS ST ANDARD CFM NET COOLING CAP ACITIES (Btuh) SEER† SOUND RA TINGS** (Bels) 018040 1 1 / 2 600 18,000 10.0 7.5 024040 024060 2 800 24,600 10.0 7.5 030040 030060 2 1 / 2 1000 28,800 10.0 7.5 036060 036090 3 1200 34,400 10.0 8.0 042060 042090 3 1 / 2 1400 42,000 10.0 8.0 0 ...

  • Bryant BRYANT 582A - page 4

    PHYSICAL DA T A UNIT SIZE 582A 018040 024040 024060 030040 030060 036060 036090 042060 042090 NOMINAL CAP ACITY (ton) 1 1 / 2 22 2 1 / 2 2 1 / 2 33 3 1 / 2 3 1 / 2 OPERA TING WEIGHT (lb) 249 280 280 280 280 314 314 355 355 COMPRESSOR(S) – QUANTITY Reciprocating-1 REFRIGERANT (R-22) Quantity (lb) 2.6 3.5 3.5 3.65 3.65 3.75 3.75 5.7 5.7 REFRIGERANT ...

  • Bryant BRYANT 582A - page 5

    OPTIONS AND ACCESSORIES F ACTORY -INST ALLED OPTIONS Louvered Grille provides hail guard and vandalism protection. A wire grille is standard on all models. See model number no- menclature for louvered grille options. Coil Options include copper/copper and vinyl-coated construc- tion for refrigerant coils. Units are shipped standard with copper tube ...

  • Bryant BRYANT 582A - page 6

    OPTIONS AND ACCESSORIES (cont) Economizer DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT P ANEL Filter Rack Manual Outdoor Air Damper 6 ...

  • Bryant BRYANT 582A - page 7

    BASE UNIT DIMENSIONS – 582A018-042 REQ'D CLEARANCES FOR OPERA TION AND SER VICING. in. (mm) Evaporator coil access side .................. 3 6 (914) Power entry side (except for NEC requirements) ......... 3 6 (914) Unit top ........................... 3 6 (914) Side opposite ducts ..................... 3 6 (914) Duct panel ................. ...

  • Bryant BRYANT 582A - page 8

    BASE UNIT DIMENSIONS – 582A048-060 FLUE HOOD REQ'D CLEARANCES FOR OPERA TION AND SER VICING. in. (mm) Evaporator coil access side .................. 3 6 (914) Power entry side (except for NEC requirements) ......... 3 6 (914) Unit top ........................... 3 6 (914) Side opposite ducts ..................... 3 6 (914) Duct panel ....... ...

  • Bryant BRYANT 582A - page 9

    ACCESSOR Y DIMENSIONS UNIT SIZE 582A ODS ORDER NUMBER A in. [mm] B in. [mm] C in. [mm] D in. [mm] FLA T CURB 018-042 CPRFCURB006A00 8 [203] 1 1 27 / 32 [301] 30 5 / 8 [778] 28 3 / 4 [730] CPRFCURB007A00 14 [356] 1 1 27 / 32 [301] 30 5 / 8 [778] 28 3 / 4 [730] 048,060 CPRFCURB008A00 8 [203] 15 27 / 32 [402] 42 1 / 8 [1070] 40 1 / 4 [1022] CPRFCURB00 ...

  • Bryant BRYANT 582A - page 10

    SELECTION PROCEDURE (with example) I DETERMINE COOLING AND HEA TING REQUIRE- MENTS A T DESIGN CONDITIONS: Given: Required Cooling Capacity (TC) .......... 34,000 Btuh Btuh Sensible Heat Capacity (SHC) ....... 25,000 Btuh Btuh Required Heating Capacity ......... 60,000 Btuh Condenser Entering Air T emperature ............9 5 F Indoor-Air T emperatur ...

  • Bryant BRYANT 582A - page 11

    PERFORMANCE DA T A NET COOLING CAP ACITIES 582A018 TEMP (F) OUTDOOR-AIR ENTERING CONDENSER EV APORA T OR AIR—CFM/BF 525/0.118 Evaporator Air—Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 15.7 18.5 20.9 16.5 19.2 21.5 17.2 19.8 21.9 SHC 13.5 1 1.6 9.5 14.9 12.7 10.2 16.2 13.6 10.7 kW 1.75 1.80 1.83 1.77 1.81 1.84 1.78 1.82 1.85 95 TC 14.5 17.3 19.9 1 ...

  • Bryant BRYANT 582A - page 12

    PERFORMANCE DA T A (cont) NET COOLING CAP ACITIES (cont) 582A036 TEMP (F) OUTDOOR-AIR ENTERING CONDENSER EV APORA T OR AIR—CFM/BF 1050/0.095 Evaporator Air—Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 31.8 35.3 38.7 32.7 36.1 39.5 33.4 36.8 40.1 SHC 29.1 24.2 19.0 31.4 26.0 20.0 33.4 27.6 21.0 kW 3.48 3.57 3.66 3.50 3.59 3.68 3.52 3.61 3.70 95 TC 3 ...

  • Bryant BRYANT 582A - page 13

    PERFORMANCE DA T A (cont) NET COOLING CAP ACITIES (cont) 582A060 TEMP (F) OUTDOOR-AIR ENTERING CONDENSER EV APORA T OR AIR – CFM/BF 1750/0.039 Evaporator Air – Ewb (F) 62 67 72 62 67 72 62 67 72 85 TC 53.9 61.5 69.3 56.1 63.6 71.1 58.0 65.2 72.4 SHC 48.8 41.4 33.4 53.7 45.2 35.7 58.0 48.8 37.9 kW 6.12 6.33 6.52 6.21 6.38 6.57 6.25 6.42 6.62 95 ...

  • Bryant BRYANT 582A - page 14

    PERFORMANCE DA T A (cont) DR Y COIL AIR DELIVER Y*—HORIZONT AL AND DOWNFLOW DISCHARGE (Deduct 10% for 208 v) 230 AND 460 VOL T Unit 582A Motor Speed External Static Pressure (in. wg) 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 018 Low W atts 227 212 196 177 165 153 CFM 1082 1016 929 796 668 428 ————— ————— Med W atts ——— ...

  • Bryant BRYANT 582A - page 15

    PERFORMANCE DA T A (cont) ECONOMIZER/1-IN. FIL TER PRESSURE DROP UNIT 582A PRESSURE DROP (in. wg) 018-042 0.12 048, 060 0.24 WET COIL PRESSURE DROP UNIT 582A AIRFLOW (CFM) PRESSURE DROP (in. wg) 018 500 0.049 600 0.070 700 0.095 024 700 0.077 800 0.100 900 0.127 030 900 0.065 1000 0.080 1 100 0.097 036 1 100 0.084 1200 0.100 1300 0.177 042 1300 0.1 ...

  • Bryant BRYANT 582A - page 16

    TYPICAL PIPING AND WIRING V ertical Discharge *NEC – National Electrical Code Horizontal Discharge 16 INDOOR THERMOST A T DISCONNECT PER NEC* FROM POWER SOURCE RETURN AIR T OP CO VER FROM GAS LINE *NEC - NA TIONAL ELECTRICAL CODE Horizontal Discharge ...

  • Bryant BRYANT 582A - page 17

    17 APPLICATION DATA 1. CONDENSATE TRAP —A 2-in. condensate trap must be field supplied. 2. DUCTWORK —Secure downflo w discharge ductwork to roof curb . For horizontal discharge applications , attach ductwork to unit with flanges. 3. T O CONVERT A UNIT TO DOWNFLO W DISCHARGE — Units are equipped with f actor y-installed inser ts in the down ...

  • Bryant BRYANT 582A - page 18

    TYPICAL WIRING SCHEMA TIC, 582A018-060; 208/230-1-60 LEGEND BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay EQUIP — Equipment FS — Flame Sensor FU — Fuse GND — Ground GVR — Gas V alve Relay HS — Hall Effect Sensor HV — High Voltage T ransformer TRAN I— Ignitor IDM — Induced-Dr ...

  • Bryant BRYANT 582A - page 19

    TYPICAL WIRING SCHEMA TIC, 582A030-060; 208/230-3-60 LEGEND AHA — Adjustable Heat Anticipator BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay CS — Centrifugal Switch EQUIP — Equipment FS — Fusible Link FU — Fuse GND — Ground GV — Gas V alve GVR — Gas V alve Relay HS — Hall Eff ...

  • Bryant BRYANT 582A - page 20

    TYPICAL WIRING SCHEMA TIC, 582A036-060; 460-3-60 LEGEND AHA — Adjustable Heat Anticipator BR — Blower Relay C— Contactor CAP — Capacitor COMP — Compressor Motor CR — Combustion Relay CS — Centrifugal Switch EQUIP — Equipment FS — Fusible Link FU — Fuse GND — Ground GV — Gas V alve GVR — Gas V alve Relay HS — Hall Effect ...

  • Bryant BRYANT 582A - page 21

    ELECTRICAL DA T A UNIT SIZE 582A V -PH-Hz VOL T AGE RANGE COMPRESSOR COND F AN MOTOR INDOOR F AN MOTOR POWER SUPPL Y Min Max RLA LRA FLA FLA MCA MOCP* 018 208/230-1-60 187 253 9.0 45.0 0.8 1.8 13.9 20 024 208/230-1-60 187 253 12.8 61.0 0.8 2.0 18.8 30 030 208/230-1-60 187 253 14.4 73.0 0.8 2.0 20.8 30 036 042 208/230-1-60 187 253 18.6 105.0 1.6 3.8 ...

  • Bryant BRYANT 582A - page 22

    CONTROLS OPERA TING SEQUENCE Heating — When the thermostat calls for heating, terminal “W” is energized, starting the induced-draft motor . When the hall- effect sensor on the induced-draft motor senses that it has reached the required speed, the burner ignition sequence be- gins. The indoor (evaporator) fan motor (IFM) is energized 45 second ...

  • Bryant BRYANT 582A - page 23

    GUIDE SPECIFICA TIONS P ACKAGED HEA TING/COOLING UNITS CONST ANT VOLUME APPLICA TION HV AC GUIDE SPECIFICA TIONS SIZE RANGE: 1 1 / 2 TO 5 TONS, NOMINAL COOLING 40,000 T O 130,000 BTUH, NOMINAL HEA TING INPUT BRY ANT MODEL NUMBER: 582A P ART 1 — GENERAL SYSTEM DESCRIPTION Outdoor rooftop mounted or ground level installed, gas heating/electric cool ...

  • Bryant BRYANT 582A - page 24

    GUIDE SPECIFICA TIONS (cont) K. Electrical Requirements: All unit power wiring shall enter the unit cabinet at a single location. L. Motors: 1. Compressor motors shall be of the refrigerant-cooled type with line-break thermal and current overload protection. 2. All fan motors shall have permanently lubricated bear- ings, and inherent, automatic res ...

Производитель Bryant Категория Heating System

Документы, которые мы получаем от производителя устройства Bryant BRYANT 582A мы можем разделить на несколько групп. Это в частности:
- технические чертежи Bryant
- инструкции обслуживания BRYANT 582A
- паспорта изделия Bryant
- информационные брошюры
- энергетические этикетки Bryant BRYANT 582A
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Bryant BRYANT 582A.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Bryant BRYANT 582A, инструкции обслуживания, короткие инструкции или инструкции пользователя Bryant BRYANT 582A. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Bryant BRYANT 582A.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Bryant BRYANT 582A, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Bryant BRYANT 582A пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Bryant BRYANT 582A.

Полная инструкция обслуживания Bryant, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Bryant BRYANT 582A - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Bryant BRYANT 582A, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Bryant BRYANT 582A, которое найдем в данном документе
3. Советы по использованию основных функций устройства Bryant BRYANT 582A - которые должны облегчить нам первые шаги во время использования Bryant BRYANT 582A
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Bryant BRYANT 582A
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Bryant BRYANT 582A в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Bryant BRYANT 582A?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Bryant BRYANT 582A, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Bryant BRYANT 582A со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)