    ZONEKIT4ZCAR Comfort Zone Installation and Start-Up Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE Safety Consideration ......................................................................1 Installation Considerations..........................................................1-2 Intro ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 2

    2. Use vibration isolators (flex connectors) on zone dampers and duct work to minimize noise. 3. Place dampers away from areas that may be noise sensitive. 4. TXV is required in air conditioning and heat pump applica- tions. 5. Use separate isolated transformer to supply power to Comfort Zone System (50 va minimum, class 2, field supplied). 6. Load ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 3

    Table 1—Wiring Requirements FROM COMFORT ZONE CENTER TO NO. OF WIRES GAGE MAX. LENGTH (FT) Four Zone Controller 3‡ 18/22 200/100 5‡ 18/22 200/100 Remote Room Sen- sors 2‡ 18/22 200/100 Remote Duct Sensors 2‡ 18/22 200/100 Dx Coil Sensor 2‡ 18/22 200/100 Home Access Module 3‡ 18/22 1000/100 ISOSAT* 3‡ 18/22 1000/100 Transformer† 21 ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 4

    Before insulating the duct work, check for proper damper opera- tion. Apply the 24vac between COM and OPN to open the damper and COM and CLS to close the damper. (See Fig. 7.) The damper will modulate counter-clockwise to open and clockwise to close. If in an emergency it becomes necessary to force a damper open, manually press in the red quick bla ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 5

    2. Secure flexible duct to zone damper using SMACNA or other approved method. 3. Properly seal joint using duct tape, mastic, or other approved method. Do not allow mastic to come in contact with actuator. 4. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check your local codes.) NOTE: All zone dampers and duct work must be properly supporte ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 6

    5. Insert 2-conductor wiring through 1 of pre-drilled holes in side of back plate. 6. Connect sensor to 2-wire conductor using provided wire nuts. (See Fig. 16 for connection to Comfort Zone Center.) Step 7—Install Dx Coil Sensor The Dx coil temperature sensor is recommended for use in heat pump with fan coil applications only. The sensor should ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 7

    Fig. 16—Comfort Zone System Wiring Diagram A94311  Zone Dampers Dx Coil Sensor (optional) Outside Air Sensor (optional) Duct Sensor Zone 2* Zone 3* Zone 4* Zone 1 4-Zone Controller Remote Room Sensors 72 68 2:45 24 VAC Transformer (Field Supplied) 50 VAC req. for basic 4 damper system. Please see Page 1, Electrica ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 8

    Changing the base temperatures will change the Comfort Temperature Setpoints used in the system schedules. Always set the Base Temperatures prior to programming the system schedules. Comfort Zone also uses a minimum temperature and a maximum temperature for comfort setpoints. The minimum and maximum temperatures are the same for all 4 zones. The Ma ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 9

    If Fan Switch on 4 zone controller is set to ON instead of Auto, then system fan will run continuously. Any time Comfort Zone is operating fan, it will be in active control of system. NOTE: If Auto Fan Off For Heating option (rotary switch position T-9) is ON, and Fan Switch on the 4 zone controller is ON, Comfort Zone will operate fan full time. O ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 10

    heater. The electric strip heat is much more expensive to operate when comparing cost per unit of heat. Because auxiliary stages of heating tend to be more expensive to operate, Comfort Zone attempts to keep number of stages at a minimum. CONFIGURATION OPTIONS FOR EQUIPMENT OPERATION Comfort Zone has several configurable options which allow it to c ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 11

    NOTE: Comfort Zone uses a 3-minute timer to delay start of second-stage (heating or cooling). This timer is started whenever first-stage heating or cooling is energized. This delay cannot be overridden or disabled. STAGE CONTROL DURING EQUIPMENT OPERATION As shown earlier, Comfort Zone has 6 configurable options which help govern equipment operatio ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 12

    then temperature at which first stage will be shut down will be offset 5°F above limit value (110°F to 114°F). If limit temperature is between 110°F and 155°F, then temperature at which first stage will shut down will be offset 20°F above limit value (130°F to 175°F). For Cooling modes the temperature is fixed at 50°F (10°C) for starting ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 13

    If a value of 105 to 110 is selected (second-stage heating is turned off at this value) then the first-stage high temperature trip limit is the programmed value plus 5°F (first-stage is turned off). If a value of 111 to 155 is selected (second-stage heating is turned off) then the first-stage high temperature trip limit is the programmed value plu ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 14

    7. Write down on a piece of paper AND GIVE TO THE OWNER a list showing what rooms are controlled by what dampers, and their corresponding zone numbers. Keep list for your future use. 8. Instruct owner to turn cool switch OFF in the fall, and turn it ON in the spring. 9. Make sure emergency heat switch is in the OFF position. If a gas furnace is use ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 15

    Cool Switch OFF —Cooling will not come on. AUTO —Cooling will come on when any zone is more than 1.5°F above desired cool setpoint. Fan Switch ON —Fan will stay on continuously (recommended). AUTO —Fan will come on only when heating or cooling is required. Emergency Heat Switch (Heat Pump Systems only) OFF —Electric strip heat will not c ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 16

    Press ADVANCE TIME/DAY button until desired start time is displayed. 6. Adjust setpoints. Adjust setpoints using up and down buttons until desired temperatures for the selected time period appear in display. These setpoints will be used during the time period currently displayed in clock window. 7. Complete time period programming. Repeat 4 through ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 17

    OUTSIDE AIR TEMPERATURE SENSOR The Outside Air Temperature Sensor must be used whenever an Outside Air Damper is installed. An Outside Air Temperature Sensor must also be used for dual fuel applications. Step 16—Troubleshooting This section contains information to assist you in troubleshooting problems and errors associated with the Comfort Zone ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 18

    Table 11—Toggle Summary TOGGLE SETTING ON OFF DEFAULT (T1)-Timeguard Override Timeguard delay is 30 sec, overrides 5-minute delay be- tween de-energizing and re-energizing HVAC stages. This option automatically returns to OFF after 30 sec timeout. If equipment has been shut down due to a leaving air tem- perature trip, the timeguard override has ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 19

    Table 12—Operating Problems SYMPTOM POSSIBLE CAUSE No Display Thermostat is not receiving power. 1. Verify that comfort zone center is receiving 24 vac. (50 va minimum required with 4 motorized dampers, 5 va for each additional motorized damper.) 2. Check that the thermostat is receiving a steady 10 VDC across the red and white wires at the syste ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 20

    Table 13—Storage Failure Errors Error Display (Dial Position T4) must be turned on. SF ERROR CODE DESCRIPTION SOLUTION 01 Temperature Programming Error Reprogram the scheduled temperatures. 02 Time Period Programming Error Reprogram the scheduled time periods. 03 Zone 1 Temperature Calibration Out of Range 1. Turn selection dial to position 2. 2. ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 21

    Table 14—Hardware Failure Errors Error Display (Dial Position T4) must be turned on. HF ERROR CODE DESCRIPTION SOLUTION 40 Zone 1 Temperature Sensor Bad sensor, shorted or open. 1. Check wiring and sensor. 2. Replace failed sensor, if necessary. Valid temperature range = 30°—180°F. 41 Zone 2 Temperature Sensor Bad sensor, shorted or open. 1. ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 22

    UNIT 24 VAC (R) C Y STANDARD SINGLE SPEED AIR CONDITIONER Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR FAN COIL COMFORT ZONE SYSTEM Y W2 W3 R C G O L E A A93227 UNIT 24 VAC (R) STANDARD SINGLE SPEED AIR CONDITIONER Yellow Red Blue White Brown Green Oran ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 23

    Fig. 19—Typical Wiring Diagrams (Fan Coil with Air Conditioner) Continued A94034 E UNIT 24 VAC (R) 2-SPEED AIR CONDITIONER (38TD) Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR FAN COIL COMFORT ZONE CENTER C R Y2 L Y1 Y1 R C G L E W3 Y/ Y2 W2 23 ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 24

    UNIT 24 VAC (R) C Y STANDARD SINGLE SPEED AIR CONDITIONER Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR VARIABLE SPEED FURNACE COMFORT ZONE CENTER Y W G R C RELAY COIL Green (P5) CONNECTION AT CONTROL BOARD Black 13 NOTE: Put set-up Switch No. 2 ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 25

    UNIT 24 VAC (R) Y2 R C 2-SPEED AIR CONDITIONER (38TD) Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR VARIABLE SPEED FURNACE COMFORT ZONE CENTER W G C R Y Y1 L RELAY COIL Green (P5) CONNECTION AT CONTROL BOARD Black 13 E (KGATT0101VSP) NOTE: Put set- ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 26

    Fig. 20—Typical Wiring Diagrams (Furnace with Air Conditioner) Continued Locking furnace into "low fire" may help prevent over conditioning in the heating mode. This will allow the furnace to stage between low and high fire. Before using this feature read furnace Installation Instructions for two- stage operation. Connect "W2" ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 27

    Fig. 21—Typical Wiring Diagrams (Fan Coil with Heat Pump) UNIT 24 VAC (R) STANDARD SINGLE SPEED HEAT PUMP Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR FAN COIL COMFORT ZONE CENTER G C R Y W2 O R C L A E Y W2 O W3 A93242 UNIT 24 VAC (R) STANDARD SINGLE SP ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 28

    Fig. 21—Typical Wiring Diagrams (Fan Coil with Heat Pump) Continued UNIT 24 VAC (R) 2-SPEED HEAT PUMP (38YD) Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR FAN COIL COMFORT ZONE SYSTEM G C R Y1 W2 O W2 R C E E O Y2 L W3 Y/ Y2 L W3 Y1 A94044 28 ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 29

    Fig. 22—Typical Wiring Diagram (Furnace with Heat Pump) UNIT 24 VAC (R) Y W2 STANDARD SINGLE SPEED HEAT PUMP Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR VARIABLE SPEED FURNACE COMFORT ZONE CENTER G A R C O R R1 R1 = Relay DPST, Pilot Duty, 24-v coil ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 30

    Fig. 22—Typical Wiring Diagrams (Furnace with Heat Pump) Continued UNIT 24 VAC (R) C R Y2 L 2-SPEED HEAT PUMP (38YD) Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR VARIABLE SPEED FURNACE COMFORT ZONE CENTER G Y1 R1 R R1 = Relay DPST, Pilot Duty, 24-v co ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 31

    Fig. 22—Typical Wiring Diagrams (Furnace with Heat Pump) Continued UNIT 24 VAC (R) C R Y1 O 2-SPEED HEAT PUMP (38YD) Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR FURNACE COMFORT ZONE CENTER G Y2 H R1 R R1 = Relay DPST, Pilot Duty, 24-v coil (HN61KK324) o ...

  • Carrier COMFORT ZONE ZONEKIT4ZCAR - page 32

    Comfort Zone Configuration Table TOGGLE DESCRIPTION FACTORY DEFAULT RECORD JOB SETTING T1 Timeguard Override OFF T2 Celsius Temperature Display OFF T3 2400 Baud Rate ON T4 Error Code Display ON T5 Enable Broadcast ON T6 Heat Pump Operation OFF T7 Outside Air Temp Sensor Attached OFF T8 Comfort Trend Setting ON T9 Auto Fan Off For Heat OFF T10 High/ ...

Производитель Carrier Категория Air Conditioner

Документы, которые мы получаем от производителя устройства Carrier COMFORT ZONE ZONEKIT4ZCAR мы можем разделить на несколько групп. Это в частности:
- технические чертежи Carrier
- инструкции обслуживания COMFORT ZONE ZONEKIT4ZCAR
- паспорта изделия Carrier
- информационные брошюры
- энергетические этикетки Carrier COMFORT ZONE ZONEKIT4ZCAR
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Carrier COMFORT ZONE ZONEKIT4ZCAR.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Carrier COMFORT ZONE ZONEKIT4ZCAR, инструкции обслуживания, короткие инструкции или инструкции пользователя Carrier COMFORT ZONE ZONEKIT4ZCAR. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Carrier COMFORT ZONE ZONEKIT4ZCAR.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Carrier COMFORT ZONE ZONEKIT4ZCAR, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Carrier COMFORT ZONE ZONEKIT4ZCAR пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Carrier COMFORT ZONE ZONEKIT4ZCAR.

Полная инструкция обслуживания Carrier, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Carrier COMFORT ZONE ZONEKIT4ZCAR - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Carrier COMFORT ZONE ZONEKIT4ZCAR, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Carrier COMFORT ZONE ZONEKIT4ZCAR, которое найдем в данном документе
3. Советы по использованию основных функций устройства Carrier COMFORT ZONE ZONEKIT4ZCAR - которые должны облегчить нам первые шаги во время использования Carrier COMFORT ZONE ZONEKIT4ZCAR
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Carrier COMFORT ZONE ZONEKIT4ZCAR
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Carrier COMFORT ZONE ZONEKIT4ZCAR в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Carrier COMFORT ZONE ZONEKIT4ZCAR?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Carrier COMFORT ZONE ZONEKIT4ZCAR, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Carrier COMFORT ZONE ZONEKIT4ZCAR со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)