    Manufacturer reserves the right to disco ntinue, or change at any time, specifications or de signs without notice and without inc urring obligations. Catalog No . 04-53 500052-01 Printed in U .S .A. Form 50PEC-2SI Pg 1 7-09 Replaces: 50PEC-1SI Installation, Star t-Up and Ser vice Instructions CONTENTS Page SAFETY CONSIDERA TIONS . . . . . . . . . . ...

  • Carrier 50PEC09-18 - page 2

    2 signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices, which would re- sult in minor personal inj ury or product and property damage. GENERAL The 50PEC water source heat pump console unit is a decen- tralized room terminal designed for field connection to a closed-circuit piping loop. Units ...

  • Carrier 50PEC09-18 - page 3

    3 LEGEND *Dimension reduced by fitting if selected. NO TE: Dimensions shown are in inches. Dim ensions in parentheses are in millimeters. EPT — External Pip e Thread IPT — Internal Pipe Thread Fig. 1 — 50PEC09-15 Piping Dimensions WATER IN WATER OUT COMPRE SS OR ACCE SS PANEL CONTROL BOX 1. 8 4 (77) CONDEN S ATE 5/ 8 " (15.9) ID VINYL HO ...

  • Carrier 50PEC09-18 - page 4

    4 LEGEND *Dimension reduced by fitting if selected. NO TE: Dimensions shown are in inches. Dim ensions in parentheses are in millimeters. EPT — External Pip e Thread IPT — Internal Pipe T hread Fig. 2 — 50PEC18 Piping Dimensions Right Hand Configuration OPT MO T WA T OP T AU T VA L V W ATE R . 8 75 ( OD C 3 /4" IP 3 /4" E WATER IN W ...

  • Carrier 50PEC09-18 - page 5

    5 NO TES: 1. Dimensions are shown in inches. Dimensions in paren theses are in millimeters. 2. Access is reduced if opti onal disconnect box is selected. 3. Optional autoflow valv e, motorized w ater valv e and disconnect bo x are shown. Fig. 3 — 50PEC09-15 Bo tt om Return Ca binet Dimensions — Right Hand Piping 3 0 1 1.5 (292) 4.9 (125) 3 .5 ( ...

  • Carrier 50PEC09-18 - page 6

    6 Fig. 4 — 50PEC18 Bo tt om Return Cabi net Dimensions — Right Hand Piping NO TES: 1. Dimensions are shown in inches. Dimens ions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow v alve , motorized water v alv e and disconnect box are sho wn. a50-8340 3 0˚ 11.50 (292) 4.90 (12 ...

  • Carrier 50PEC09-18 - page 7

    7 a50-8341 Fig. 5 — 50PEC09- 15 Bo tt om Return Ca binet Dimensions — Left Hand Piping NO TES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow valv e, motorized w ater valv e and disconnect bo x are shown. 3 0° 11 . 5 (292) 4.9 (1 ...

  • Carrier 50PEC09-18 - page 8

    8 Fig. 6 — 50PEC18 Bo tt om Return Ca bi net Dimensions — Left Hand Piping NO TES: 1. Dimensions are shown in inches. Dimens ions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow v alve , motorized water v alv e and disconnect box are shown. 3 0˚ 11.50 (292) 4.90 (125) 3 .50 ( ...

  • Carrier 50PEC09-18 - page 9

    9 a50-8343 Fig. 7 — 50PEC09-15 Fr ont Return Ca binet Dimensions — Right Hand Pip ing NO TES: 1. Dimensions are shown in inches. Dimens ions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow v alv e, motorized water v alv e and disconnect box are sho wn. 4 8 .0 3 0 3 .5 ( 8 9) 2 ...

  • Carrier 50PEC09-18 - page 10

    10 a50-8344 Fig. 8 — 50PEC18 Fr ont Re turn Cabine t Dimensio ns — Right Hand Piping NO TES: 1. Dimensions are shown in inches. Dimens ions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow v alv e, motorized water v alv e and disconnect box are sho wn. 54.00 3 0˚ 3 .50 ( 8 9) ...

  • Carrier 50PEC09-18 - page 11

    11 ° ( 8 9) L.H. (NOTE 2) .50 (1 3 ) 11.50 (292) .75 (19) 4.12 (105) (Note 2) a50-8345 Fig. 9 — 50PEC09-15 Fr ont Return Ca binet Dimensions — Left Hand Pip ing NO TES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters. 2. Access is reduced if opti onal disconnect box is selected. 3. Optional autoflow valv e, moto ...

  • Carrier 50PEC09-18 - page 12

    12 a50-8346 Fig. 10 — 50PEC18 Fr ont Return Cabi net Dimensions — Left Hand Piping NO TES: 1. Dimensions are shown in inches. Dimens ions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow valv e , motorized water valv e and disconnect bo x are shown. 54.00 3 0˚ 3 .50 ( 8 9) 21. ...

  • Carrier 50PEC09-18 - page 13

    13 Power S upply Blower Deck Blower Acce ss P a nel Compre ss or Acce ss P a nel Control Box 40.98 (1041) 4.46 (113) 0.75 (19) 0.75 (19) * 20.50 (521) 11. 5 4 (293) *16.66 (423) 30° 0.87 (22) Hard Wire Power S upply Blower Deck Blower Acce ss P a nel Compre ss or Acce ss P a nel Control Box 7.50 (191) 0.87 (22) 11.54 (293) 3.42 (87) *16.66 (423) 3 ...

  • Carrier 50PEC09-18 - page 14

    14 NO TES: 1. Dimensions shown are in inches. Dimens ions in parentheses are in millimeters. 2. Optional autoflow valv e, motorized w ater v alv e and disconnect box are shown. 3. Chassis can mount directly on floor. Fig. 12 — 50PEC09-15 Chas sis Dimensions — Fr ont Return Power S upply Blower Deck Compre ss or Acce ss P a nel Control Box 40.98 ...

  • Carrier 50PEC09-18 - page 15

    15 Fig. 13 — 50PEC18 Chassis Dimensions — Bottom Return *If optional subbase is selected, add 4.9 in. to dimension. NO TES: 1. Dimensions shown are in inches. Dimens ions in parentheses are in millimeters. 2. Optional autoflow valv e, motorized w ater valv e and disconnect bo x are shown. Blower Deck Blower Acce ss P a nel Compre ss or Acce ss ...

  • Carrier 50PEC09-18 - page 16

    16 Fig. 14 — 50PEC18 Chassis Dimensions — Fron t Return NO TES: 1. Dimensions shown are in inches. Dimens ions in parentheses are in millimeters. 2. Optional autoflow valve , motorized water v alv e and disconnect bo x are shown. 3. Chassis can mount directly on floor . Blower Deck Compre ss or Acce ss P a nel Control Box 46.98 (1193) 4.49 (114 ...

  • Carrier 50PEC09-18 - page 17

    17 Step 2 — Chec k Unit — Upon receipt of shipment at the jobsite, carefully check the shipment against the bill of lad- ing. Make sure all units have been received. Inspe ct the carton or crating of each unit, and inspect each unit for damage. En- sure the shipping company makes proper notation of any short- ages or damage on all copies of the ...

  • Carrier 50PEC09-18 - page 18

    18 Fig. 17 — 50PEC Unit Manual or A uto Changeover with Complete C Controller Wiring LEGEND NO TES: 1. Compressor and b low er motor thermally pro- tected internally . 2. All wiring to the unit must comply with local codes. 3. T ransf ormer is wired to 115-V (WHT) lead f or 115/1/60 units; 265-V (BRN) lead f or 265/1 /60 units; or 208-V (RED) lea ...

  • Carrier 50PEC09-18 - page 19

    19 LEGEND NO TES: 1. Compressor and b lower motor t hermally pro- tected internally . 2. All wiring to the unit m ust comply with local codes. 3. T ransf o rmer is wired to 115-V (WHT) lead f or 115/1/60 uni ts, 265 -V (BRN) lead f or 265/ 1/60 units, 240 -V (ORG) lead f or 240/1/50 units , or 208-V (RED) lead f or 208/1/60 units . Rewire tr ansfor ...

  • Carrier 50PEC09-18 - page 20

    20 *Optional wiring. AL — Alar m Relay Cont acts BM — Blo wer Motor CAP — Capacitor CB — Circuit Breaker CO — Sensor , Condensate Overflo w CR — Compressor Relay DM — Damper Moto r FP1 — Sensor, W ater Coil Freez e Protection FP2 — Sensor, Air Coil F r eeze Prot ection FSS — F an Speed Switch HP — High-Pressure Switch JW1 — ...

  • Carrier 50PEC09-18 - page 21

    21 *Optional wiring. AL — Alarm Relay Contacts BM — Blower Motor BR — Blower Rela y CAP — Capacitor CB — Circuit Breaker CO — Sensor , Condensate Ov erflo w CR — Compressor Relay DM — Damper Motor FP1 — Sensor , W ater Coil F reeze Protection FP2 — Sensor , Ai r Coil F reez e Protection HP — High-Pressure Switch JW1 — Jumper ...

  • Carrier 50PEC09-18 - page 22

    22 COMPLETE C CONTROL BR CR CAP PB GROUND TRANSFORMER BRN Y EL Y W O G R C AL1 AL2 A P1 ALARM RELA Y SEE NOTE 6 JW1 WV COMPRESSOR COOLING FA N 24 V AC COMMON ALARM CLASS 1 WIRING REQUIRED INSIDE CONTROL BOX Y O G R C L CLASS 1 OR 2 WIRING ACCEPT ABLE OUTSIDE CONTROL BOX TYPICAL HEA T PUMP T -ST A T SEE NOTE 5 BRN YEL BLU R Y JW3 FP1 JW2 FP2 SEE NOT ...

  • Carrier 50PEC09-18 - page 23

    23 AL — Alar m Relay Contacts BM — Blo wer Motor BR — Blower Rela y CAP — Capacitor CB — Circuit Breaker CO — Sensor , Condensate Overflo w CR — Compres sor Relay DM — Damper Motor FP1 — Sensor , W ater Coil F reez e Protection FP2 — Sensor , Air Coil F reez e Protection FSS — F an Speed Swit ch HP — High-Pressure Switch JW1 ...

  • Carrier 50PEC09-18 - page 24

    24 Y W O G R C AL1 AL2 A CR CMP1 FA N PWR HS1/EXH/RVS PREMIER LINK CR COMPLETE C CONTROL J4 J6 J5 J8 J1 PWR S P S A L W CMPSAFE T T T Y1 G R C AL1 CMP1 FA N PWR PREMIER LINK DELUXE D CONTROL J4 J8 J1 PWR CMPSAFE HS2 HS1 CMP2 Y2 W1 O/W2 J6 J5 S P T S A T L W T LEGEND NO TE: Rev ersing v alv e is on in Cooling mode. CR — Control Relay LW T — Lea ...

  • Carrier 50PEC09-18 - page 25

    25 Fig. 25 — Units wi th Complete C and WSHP Open Multiple Protocol Controls WH S P-OPEN A50-8355 LEGEND BM — Blo wer Motor BR — Blow er Rela y CO — Condensate Overflo w LW T — Lea ving W ater T emperature N.C. — Normally Clo sed OA D — Outside Air Damper OCC — Occupancy Input Contact RH — Relative Humidity SA T — Supply Air T e ...

  • Carrier 50PEC09-18 - page 26

    26 W S HP-OPEN Fig. 26 — Units with Deluxe D and WSHP Open Mul tiple Protocol Controls A50-8354 LEGEND BM — Blo wer Motor CO — Condensate Overflo w LW T — Leaving W ater T emperature N.C. — Normally Clo sed OA D — Outside Air Damper OCC — Occupancy Input Contact RH — Relative Humidity SA T — Supply Air T emperature SPT — Space T ...

  • Carrier 50PEC09-18 - page 27

    27 W S HP-OPEN Fig. 27 — Units wi th Complete C, ECM a nd WSHP Open Mu ltiple Protocol Controls A50-8356 LEGEND CO — Condensate Overflo w LW T — Leaving W ater T emperature N.C. — Normally Clo sed OA D — Outside Air Damper OCC — Occupancy Input Contact RH — Relative Humidity SA T — Supply Air T emperature SPT — Space T emperature ...

  • Carrier 50PEC09-18 - page 28

    28 W S HP-OPEN Fig. 28 — Units with Deluxe D, ECM and W SHP Open Multiple Protoc ol Controls A50-8353 LEGEND CO — Condensate Overflo w LW T — Leaving W ater T emperature N.C. — Normally Clo sed OA D — Outside Air Damper OCC — Occupancy Input Contact RH — Relative Humidity SA T — Supply Air T emperature SPT — Space T emperature ...

  • Carrier 50PEC09-18 - page 29

    29 012207-1BT4 8 5BT LED1 DB In s t a ll BT4 8 5 where device i s loc a ted a t the end of network s egment only. + 24v a c (If not in s t a lled, it m us t b e connected to DO-5) DEHUMIDIFY OUTPUT CONTACT (DO-6) (FACTORY OPTION) FAN S PEED (DO-7) (MED OR LOW) OA DAMPER (AO-2) FAN S PEED (DO- 8 ) (HIGH OR FAN ON ) LWT (Inp u t 6) S AT (LAT) (Inp u ...

  • Carrier 50PEC09-18 - page 30

    30 Table 2 — Electrical Data — 50PEC Uni ts LEGEND Step 5 — Wire Low V oltage Connections W A TER FREEZE PROTECTION — T h e Aq ua z o n e ™ co n - trol allows the field selection of source fluid freeze protection points through jumpers. The fact ory setting of jumper JW3 (FP1) is set for water at 30 F . In earth loop applications, jumper ...

  • Carrier 50PEC09-18 - page 31

    31 OP TIONAL W ALL-MOUNTED THERMOST A T — T h e 50PEC water source heat pump units are built with standard in- ternal thermostats in either manual changeover (MCO) or auto- matic changeover (ACO) configur ation. Refer to Fig. 17-20. When desired, the unit can be furnished with a 24-v control circuit which is field wired to a Carrier -supplied acc ...

  • Carrier 50PEC09-18 - page 32

    32 Table 6 — Rnet Wiri ng Specificatio ns LEGEND T o wire the SP T sensor to the controller : 1. Partially cut , then bend and pull of f the outer jacket of the Rnet cable(s), being careful not to nick the inner insulation. 2. Strip ab out 1 / 4 in. of the inner insulation from each wire. See Fig. 34. 3. W ire each terminal on the sensor to the s ...

  • Carrier 50PEC09-18 - page 33

    33 2. Install shut-off/bal ancing valves and unions at each unit to allow unit removal for servicing. NOTE: If flex hoses are used, unions are not necessary . 3. Install strainers at the inlet of each system circulating pump. 4. Before making the final water connections, flush the sys- tem as described in the Pre-Start-Up section of this manual. Af ...

  • Carrier 50PEC09-18 - page 34

    34 8. Refill the system with clea n, chemically treated water . Since water varies for each lo cality , contact a local water treatment company for the correct treatment chemicals to use in the area. Set the boiler to raise the loop temperature to approximately 85 F . . Circulate the solution for a minimum of 8 to 24 hours. At the end of this perio ...

  • Carrier 50PEC09-18 - page 35

    35 Table 9 — Water Quality Guideline s LEGEND *Heat exchanger mate rials considered ar e copper, cupronickel, 304 SS (stainless ste el), 316 SS , titanium. †Closed reci rculating sy stem is iden tified by a closed p ressur ized piping system. **Recircul ating open wells shoul d obser ve the open recirculat ing design consideratio ns. ††If t ...

  • Carrier 50PEC09-18 - page 36

    36 FIELD SELECT ABLE INPUTS Jumpers and DIP (dual in-line package) switches on the control board are used to customize unit operation and can be configured in the field. Complete C Control J umper Settings (See Fig. 17, 18, and 21) W A TER COIL FREEZE PROTECTION (FP1) LIMI T SETTING — Se l e c t j u mp e r 3 , ( JW 3 - F P 1 Lo w T em p ) t o cho ...

  • Carrier 50PEC09-18 - page 37

    37 Table 11 — DIP Switch Bloc k S2 — Accessory 2 Re lay Options LEGEND NO TE: All other switch combinations are in v alid. Auto Dehumidification Mode or High Fan Mode — Switch 7 provides selection of auto dehumidification fan m ode or high fan mode. In auto dehumidification fan mode, the fan speed relay will remain off during Cooling S tage 2 ...

  • Carrier 50PEC09-18 - page 38

    38 5. Slowly turn thermostat toward cooler position. Both fan and compressor should shut off when thermostat set point equals room temperature. Room temperature must be above 65 F for unit to shut off. Unit Start-Up with WSHP Open Controls — The WSHP Open is a multi-protocol (default BACnet*) con- troller with extensive features, flexible options ...

  • Carrier 50PEC09-18 - page 39

    39 b. Select W eekly , then pres s enter (7 schedules available). c. Select day and press enter . d. Press enter again and select ADD or DEL (DECR or INCR) set schedule. e. Enter ON/OFF time, then press continue. f. Press OK to appl y and save to a particular day of the week. g. Continue to add the same or dif ferent sched ule spe- cific days of th ...

  • Carrier 50PEC09-18 - page 40

    40 Table 13 — Approximate Fluid Volume (gal) per 100 f t of Pipe LEGEND NO TE: V olume of heat ex changer is appro ximately 1.0 gallon. Table 14 — Antifr eeze Percentages by Volume Cooling T ower/Boi ler Systems — Th ese systems typically use a common loop maintained at 60 to 90 F . Carrier recommends using a closed circuit evaporative coolin ...

  • Carrier 50PEC09-18 - page 41

    41 application, all compressor relays and related functions will track with their associated DIP switch 2 on S1. NIGHT LOW LIMIT (NLL) ST AGED HEA TING — In NLL staged Heating mode, the override (OVR) input becomes active and is recognized as a call for heating and the control will immediately go into a Heating Stage 1 mode. With an additional 30 ...

  • Carrier 50PEC09-18 - page 42

    42 maximum speed. If the SA T continues to fall 5 F below the minimum SA T limit, all cooling stages will be disabled. During Cooling mode, the reversing valve output will be held in the cooling position (either B or O type as configured) even after the compressor is stopped. The valve will not switch position until the Heating mode is required. Th ...

  • Carrier 50PEC09-18 - page 43

    43 ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers) specifications by providing a base ventilation rate and then increasing the rate as the CO 2 level in- creases. The control will begin to proportionally increase venti- lation when the CO 2 level rises above the start ventilation set point and will reach the full ...

  • Carrier 50PEC09-18 - page 44

    44 label. For example, flashing c ode 1 will have an alarm relay cycling code 1. Code 1 indica tes the control has not faulted since the last power-off to power -on sequence. WSHP Open T est Mode — T o enter WSHP Open test mode, navigate from the BAC view 6 home screen to the config- uration screen. Choose the servic e screen and enable unit test ...

  • Carrier 50PEC09-18 - page 45

    45 Table 17 — Aquazone™ Deluxe D Control Current LED Status an d Alarm Relay Operations LEGEND NO TES: 1. If there is no f ault in memory , the F ault LED will flash code 1. 2. Codes will be displa yed with a 10- second F ault LED pause. 3. Slow flash is 1 flash e v ery 2 seconds. 4. F ast flash is 2 flashes e v ery 1 second. 5. EXAMPLE: “Fla ...

  • Carrier 50PEC09-18 - page 46

    46 produce water (or debris) velocitie s that can erode the heat ex- changer wall and ultimately produce leaks. Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment anal- ysis is recommended. Refer to the Carrier System Design Man- ual, Part 5, for general water conditioning information. ...

  • Carrier 50PEC09-18 - page 47

    47 Checkin g System Char ge — Units are shipped with full operating charge. If rechar ging is necessary: 1. Insert thermometer bulb in insulating rubber sleeve on liquid line near filter drier . Use a digital thermometer for all temperature measurements. DO NOT use a mercury or dial-type thermometer . 2. Connect pressure gage to di schar ge line ...

  • Carrier 50PEC09-18 - page 48

    48 Table 18 — Troubleshooting LEGEND F AUL T HEA TING COOLING POSSIBLE CAUSE SOLUTION Main Power Problems X X Gree n Status LED Off Check line voltage circuit breaker and disconnect . Check for line v oltage bet ween L1 and L2 on the co ntactor. Check f or 24-vac between R and C on con troller . Check primar y/ secondar y voltage on t ransformer ...

  • Carrier 50PEC09-18 - page 49

    49 Table 18 — Troubleshooting ( cont) LEGEND F AUL T HEA TING COOLING POSSIBLE CAUSE SOLUTION Only Compressor Runs X X Ther mostat wir ing Check G wiring at heat pump. Jumper G and R for fan operation. Check Y and W wiring at hea t pump . Jumper Y and R for compressor operatio n in T es t mode. X X Fan motor relay Jumper G and R for f an operatio ...

  • Carrier 50PEC09-18 - page 50

    50 APPENDIX A — WSHP OPEN SCREEN CONFIGURA TION LEGEND SCREEN NAME POINT NAME PAS SWO RD LEVEL EDITABLE RANGE DEFAULT NOTES Equipment Status Operati ng Mode No P assword Re q uired Off, F an Only , Economize , Cooling, Heating, Cont F an, T est, Start Dela y , Dehumidify Display s unit operat ing mode SPT F Displa ys SPT SA T F Displa ys SA T Con ...

  • Carrier 50PEC09-18 - page 51

    51 APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PA SS WO RD LEVEL EDITABLE RANGE DEFAULT NOTES Unit Maintenance Operating Mode No P assw ord re q uired Off, F an Only ,Econom ize, Cooling, Heating, Cont F an, T est, Start Delay , Dehumidify Display s unit operating mode F an Oper ating Mode Auto /Continuou s/Al ...

  • Carrier 50PEC09-18 - page 52

    52 APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont) LEGEND SCREEN NAME P OINT NAME PA S SWO RD LEVEL EDITABLE RANG E DEFAULT NOTES Configuration Set Points Occupied Heating User/Admin P assw ord le vel access X 40 - 90 F 72 F Defi nes the Occupied Heating Set P oint Occupied Cooling X 55 - 99 F 76 F Def ines the Occupied Cooling Set P oint Unoc ...

  • Carrier 50PEC09-18 - page 53

    53 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PAS SW OR D LEVE L EDITABLE RANGE DEFAULT NOTES Configuration Unit Configuration F an Mode Admin P ass word lev el access only X Aut o/Continuous/ Always On Continuous Aut o= Intermittant operation during both occupied and unoccupied periods/ Continuou s = Intermi ...

  • Carrier 50PEC09-18 - page 54

    54 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PAS SW OR D LEVEL EDITABLE RANGE DEFAULT NOTES Configuration Service Configuration # of F an Speeds Admin P ass word lev el access only X 1,2 ,3 3 Used to set n umber of fan mot or speeds G Output T ype X F an On/F an Low Fan On When set to F an On, G out put is e ...

  • Carrier 50PEC09-18 - page 55

    55 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME P OINT NAME PA S SWO RD LEVEL EDITABLE RANGE DEFAUL T NOTES Configuration Alarm Configuration SPT Occupied Alarm Hysteresis Admin P assw ord lev el access only X2 - 2 0 F 5 F Defines the h ysteresis applied abo ve the cooling and belo w the heating set points bef ore an alar ...

  • Carrier 50PEC09-18 - page 56

    56 ...

  • Carrier 50PEC09-18 - page 57

    57 ...

  • Carrier 50PEC09-18 - page 58

    Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 04-53 500052-01 Printed in U .S .A. Form 50PEC-2SI Pg 58 7-09 Replaces: 50PEC-1SI Copy right 2009 Carrier Cor poration ...

  • Carrier 50PEC09-18 - page 59

    CL-1 50PEC UNIT ST ART -UP CHECKLIST CUSTOMER: ___________________________ JOB NAME: _ _____________________________________ _ MODEL NO.:___________________________ S ERIAL NO.: ____________________ DA TE: _________ I. PRE-ST ART -UP DOES THE UNIT VOL T AGE CORRESPOND WI TH THE SUPPL Y VOL T AGE A V AILABLE ? (Y/N) HA VE THE POWER AND CONTROL WIRIN ...

  • Carrier 50PEC09-18 - page 60

    Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 04-53 500052-01 Printed in U .S. A. Form 50PEC-2SI CL-2 7-09 Replaces: 50PE C-1SI Copy right 2009 Carrier Cor poration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ...

Produzent Carrier Kategorie Heat Pump

Dokumente, die wir vom Produzenten des Geräts Carrier 50PEC09-18 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Carrier
- Bedienungsanleitungen 50PEC09-18
- Produktkarten Carrier
- Informationsbroschüren
- oder Energieetiketten Carrier 50PEC09-18
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Carrier 50PEC09-18.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Carrier 50PEC09-18, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Carrier 50PEC09-18. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Carrier 50PEC09-18 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Carrier 50PEC09-18, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Carrier 50PEC09-18 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Carrier 50PEC09-18 verständlich ist.

Eine gänzliche Bedienungsanleitung von Carrier sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Carrier 50PEC09-18 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Carrier 50PEC09-18 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Carrier 50PEC09-18, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Carrier 50PEC09-18 - die uns die ersten Schritte während der Nutzung von Carrier 50PEC09-18 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Carrier 50PEC09-18 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Carrier 50PEC09-18 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Carrier 50PEC09-18?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Carrier 50PEC09-18 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Carrier 50PEC09-18 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)