Manuel d’utilisation Carrier 50PEC09-18

60 pages 4.36 mb
Télécharger

Aller à la page of 60

Summary
  • Carrier 50PEC09-18 - page 1

    Manufacturer reserves the right to disco ntinue, or change at any time, specifications or de signs without notice and without inc urring obligations. Catalog No . 04-53 500052-01 Printed in U .S .A. Form 50PEC-2SI Pg 1 7-09 Replaces: 50PEC-1SI Installation, Star t-Up and Ser vice Instructions CONTENTS Page SAFETY CONSIDERA TIONS . . . . . . . . . . ...

  • Carrier 50PEC09-18 - page 2

    2 signifies hazards that could result in personal injury or death. CAUTION is used to identify unsafe practices, which would re- sult in minor personal inj ury or product and property damage. GENERAL The 50PEC water source heat pump console unit is a decen- tralized room terminal designed for field connection to a closed-circuit piping loop. Units ...

  • Carrier 50PEC09-18 - page 3

    3 LEGEND *Dimension reduced by fitting if selected. NO TE: Dimensions shown are in inches. Dim ensions in parentheses are in millimeters. EPT — External Pip e Thread IPT — Internal Pipe Thread Fig. 1 — 50PEC09-15 Piping Dimensions WATER IN WATER OUT COMPRE SS OR ACCE SS PANEL CONTROL BOX 1. 8 4 (77) CONDEN S ATE 5/ 8 " (15.9) ID VINYL HO ...

  • Carrier 50PEC09-18 - page 4

    4 LEGEND *Dimension reduced by fitting if selected. NO TE: Dimensions shown are in inches. Dim ensions in parentheses are in millimeters. EPT — External Pip e Thread IPT — Internal Pipe T hread Fig. 2 — 50PEC18 Piping Dimensions Right Hand Configuration OPT MO T WA T OP T AU T VA L V W ATE R . 8 75 ( OD C 3 /4" IP 3 /4" E WATER IN W ...

  • Carrier 50PEC09-18 - page 5

    5 NO TES: 1. Dimensions are shown in inches. Dimensions in paren theses are in millimeters. 2. Access is reduced if opti onal disconnect box is selected. 3. Optional autoflow valv e, motorized w ater valv e and disconnect bo x are shown. Fig. 3 — 50PEC09-15 Bo tt om Return Ca binet Dimensions — Right Hand Piping 3 0 1 1.5 (292) 4.9 (125) 3 .5 ( ...

  • Carrier 50PEC09-18 - page 6

    6 Fig. 4 — 50PEC18 Bo tt om Return Cabi net Dimensions — Right Hand Piping NO TES: 1. Dimensions are shown in inches. Dimens ions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow v alve , motorized water v alv e and disconnect box are sho wn. a50-8340 3 0˚ 11.50 (292) 4.90 (12 ...

  • Carrier 50PEC09-18 - page 7

    7 a50-8341 Fig. 5 — 50PEC09- 15 Bo tt om Return Ca binet Dimensions — Left Hand Piping NO TES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow valv e, motorized w ater valv e and disconnect bo x are shown. 3 0° 11 . 5 (292) 4.9 (1 ...

  • Carrier 50PEC09-18 - page 8

    8 Fig. 6 — 50PEC18 Bo tt om Return Ca bi net Dimensions — Left Hand Piping NO TES: 1. Dimensions are shown in inches. Dimens ions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow v alve , motorized water v alv e and disconnect box are shown. 3 0˚ 11.50 (292) 4.90 (125) 3 .50 ( ...

  • Carrier 50PEC09-18 - page 9

    9 a50-8343 Fig. 7 — 50PEC09-15 Fr ont Return Ca binet Dimensions — Right Hand Pip ing NO TES: 1. Dimensions are shown in inches. Dimens ions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow v alv e, motorized water v alv e and disconnect box are sho wn. 4 8 .0 3 0 3 .5 ( 8 9) 2 ...

  • Carrier 50PEC09-18 - page 10

    10 a50-8344 Fig. 8 — 50PEC18 Fr ont Re turn Cabine t Dimensio ns — Right Hand Piping NO TES: 1. Dimensions are shown in inches. Dimens ions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow v alv e, motorized water v alv e and disconnect box are sho wn. 54.00 3 0˚ 3 .50 ( 8 9) ...

  • Carrier 50PEC09-18 - page 11

    11 ° ( 8 9) L.H. (NOTE 2) .50 (1 3 ) 11.50 (292) .75 (19) 4.12 (105) (Note 2) a50-8345 Fig. 9 — 50PEC09-15 Fr ont Return Ca binet Dimensions — Left Hand Pip ing NO TES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters. 2. Access is reduced if opti onal disconnect box is selected. 3. Optional autoflow valv e, moto ...

  • Carrier 50PEC09-18 - page 12

    12 a50-8346 Fig. 10 — 50PEC18 Fr ont Return Cabi net Dimensions — Left Hand Piping NO TES: 1. Dimensions are shown in inches. Dimens ions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow valv e , motorized water valv e and disconnect bo x are shown. 54.00 3 0˚ 3 .50 ( 8 9) 21. ...

  • Carrier 50PEC09-18 - page 13

    13 Power S upply Blower Deck Blower Acce ss P a nel Compre ss or Acce ss P a nel Control Box 40.98 (1041) 4.46 (113) 0.75 (19) 0.75 (19) * 20.50 (521) 11. 5 4 (293) *16.66 (423) 30° 0.87 (22) Hard Wire Power S upply Blower Deck Blower Acce ss P a nel Compre ss or Acce ss P a nel Control Box 7.50 (191) 0.87 (22) 11.54 (293) 3.42 (87) *16.66 (423) 3 ...

  • Carrier 50PEC09-18 - page 14

    14 NO TES: 1. Dimensions shown are in inches. Dimens ions in parentheses are in millimeters. 2. Optional autoflow valv e, motorized w ater v alv e and disconnect box are shown. 3. Chassis can mount directly on floor. Fig. 12 — 50PEC09-15 Chas sis Dimensions — Fr ont Return Power S upply Blower Deck Compre ss or Acce ss P a nel Control Box 40.98 ...

  • Carrier 50PEC09-18 - page 15

    15 Fig. 13 — 50PEC18 Chassis Dimensions — Bottom Return *If optional subbase is selected, add 4.9 in. to dimension. NO TES: 1. Dimensions shown are in inches. Dimens ions in parentheses are in millimeters. 2. Optional autoflow valv e, motorized w ater valv e and disconnect bo x are shown. Blower Deck Blower Acce ss P a nel Compre ss or Acce ss ...

  • Carrier 50PEC09-18 - page 16

    16 Fig. 14 — 50PEC18 Chassis Dimensions — Fron t Return NO TES: 1. Dimensions shown are in inches. Dimens ions in parentheses are in millimeters. 2. Optional autoflow valve , motorized water v alv e and disconnect bo x are shown. 3. Chassis can mount directly on floor . Blower Deck Compre ss or Acce ss P a nel Control Box 46.98 (1193) 4.49 (114 ...

  • Carrier 50PEC09-18 - page 17

    17 Step 2 — Chec k Unit — Upon receipt of shipment at the jobsite, carefully check the shipment against the bill of lad- ing. Make sure all units have been received. Inspe ct the carton or crating of each unit, and inspect each unit for damage. En- sure the shipping company makes proper notation of any short- ages or damage on all copies of the ...

  • Carrier 50PEC09-18 - page 18

    18 Fig. 17 — 50PEC Unit Manual or A uto Changeover with Complete C Controller Wiring LEGEND NO TES: 1. Compressor and b low er motor thermally pro- tected internally . 2. All wiring to the unit must comply with local codes. 3. T ransf ormer is wired to 115-V (WHT) lead f or 115/1/60 units; 265-V (BRN) lead f or 265/1 /60 units; or 208-V (RED) lea ...

  • Carrier 50PEC09-18 - page 19

    19 LEGEND NO TES: 1. Compressor and b lower motor t hermally pro- tected internally . 2. All wiring to the unit m ust comply with local codes. 3. T ransf o rmer is wired to 115-V (WHT) lead f or 115/1/60 uni ts, 265 -V (BRN) lead f or 265/ 1/60 units, 240 -V (ORG) lead f or 240/1/50 units , or 208-V (RED) lead f or 208/1/60 units . Rewire tr ansfor ...

  • Carrier 50PEC09-18 - page 20

    20 *Optional wiring. AL — Alar m Relay Cont acts BM — Blo wer Motor CAP — Capacitor CB — Circuit Breaker CO — Sensor , Condensate Overflo w CR — Compressor Relay DM — Damper Moto r FP1 — Sensor, W ater Coil Freez e Protection FP2 — Sensor, Air Coil F r eeze Prot ection FSS — F an Speed Switch HP — High-Pressure Switch JW1 — ...

  • Carrier 50PEC09-18 - page 21

    21 *Optional wiring. AL — Alarm Relay Contacts BM — Blower Motor BR — Blower Rela y CAP — Capacitor CB — Circuit Breaker CO — Sensor , Condensate Ov erflo w CR — Compressor Relay DM — Damper Motor FP1 — Sensor , W ater Coil F reeze Protection FP2 — Sensor , Ai r Coil F reez e Protection HP — High-Pressure Switch JW1 — Jumper ...

  • Carrier 50PEC09-18 - page 22

    22 COMPLETE C CONTROL BR CR CAP PB GROUND TRANSFORMER BRN Y EL Y W O G R C AL1 AL2 A P1 ALARM RELA Y SEE NOTE 6 JW1 WV COMPRESSOR COOLING FA N 24 V AC COMMON ALARM CLASS 1 WIRING REQUIRED INSIDE CONTROL BOX Y O G R C L CLASS 1 OR 2 WIRING ACCEPT ABLE OUTSIDE CONTROL BOX TYPICAL HEA T PUMP T -ST A T SEE NOTE 5 BRN YEL BLU R Y JW3 FP1 JW2 FP2 SEE NOT ...

  • Carrier 50PEC09-18 - page 23

    23 AL — Alar m Relay Contacts BM — Blo wer Motor BR — Blower Rela y CAP — Capacitor CB — Circuit Breaker CO — Sensor , Condensate Overflo w CR — Compres sor Relay DM — Damper Motor FP1 — Sensor , W ater Coil F reez e Protection FP2 — Sensor , Air Coil F reez e Protection FSS — F an Speed Swit ch HP — High-Pressure Switch JW1 ...

  • Carrier 50PEC09-18 - page 24

    24 Y W O G R C AL1 AL2 A CR CMP1 FA N PWR HS1/EXH/RVS PREMIER LINK CR COMPLETE C CONTROL J4 J6 J5 J8 J1 PWR S P S A L W CMPSAFE T T T Y1 G R C AL1 CMP1 FA N PWR PREMIER LINK DELUXE D CONTROL J4 J8 J1 PWR CMPSAFE HS2 HS1 CMP2 Y2 W1 O/W2 J6 J5 S P T S A T L W T LEGEND NO TE: Rev ersing v alv e is on in Cooling mode. CR — Control Relay LW T — Lea ...

  • Carrier 50PEC09-18 - page 25

    25 Fig. 25 — Units wi th Complete C and WSHP Open Multiple Protocol Controls WH S P-OPEN A50-8355 LEGEND BM — Blo wer Motor BR — Blow er Rela y CO — Condensate Overflo w LW T — Lea ving W ater T emperature N.C. — Normally Clo sed OA D — Outside Air Damper OCC — Occupancy Input Contact RH — Relative Humidity SA T — Supply Air T e ...

  • Carrier 50PEC09-18 - page 26

    26 W S HP-OPEN Fig. 26 — Units with Deluxe D and WSHP Open Mul tiple Protocol Controls A50-8354 LEGEND BM — Blo wer Motor CO — Condensate Overflo w LW T — Leaving W ater T emperature N.C. — Normally Clo sed OA D — Outside Air Damper OCC — Occupancy Input Contact RH — Relative Humidity SA T — Supply Air T emperature SPT — Space T ...

  • Carrier 50PEC09-18 - page 27

    27 W S HP-OPEN Fig. 27 — Units wi th Complete C, ECM a nd WSHP Open Mu ltiple Protocol Controls A50-8356 LEGEND CO — Condensate Overflo w LW T — Leaving W ater T emperature N.C. — Normally Clo sed OA D — Outside Air Damper OCC — Occupancy Input Contact RH — Relative Humidity SA T — Supply Air T emperature SPT — Space T emperature ...

  • Carrier 50PEC09-18 - page 28

    28 W S HP-OPEN Fig. 28 — Units with Deluxe D, ECM and W SHP Open Multiple Protoc ol Controls A50-8353 LEGEND CO — Condensate Overflo w LW T — Leaving W ater T emperature N.C. — Normally Clo sed OA D — Outside Air Damper OCC — Occupancy Input Contact RH — Relative Humidity SA T — Supply Air T emperature SPT — Space T emperature ...

  • Carrier 50PEC09-18 - page 29

    29 012207-1BT4 8 5BT LED1 DB In s t a ll BT4 8 5 where device i s loc a ted a t the end of network s egment only. + 24v a c (If not in s t a lled, it m us t b e connected to DO-5) DEHUMIDIFY OUTPUT CONTACT (DO-6) (FACTORY OPTION) FAN S PEED (DO-7) (MED OR LOW) OA DAMPER (AO-2) FAN S PEED (DO- 8 ) (HIGH OR FAN ON ) LWT (Inp u t 6) S AT (LAT) (Inp u ...

  • Carrier 50PEC09-18 - page 30

    30 Table 2 — Electrical Data — 50PEC Uni ts LEGEND Step 5 — Wire Low V oltage Connections W A TER FREEZE PROTECTION — T h e Aq ua z o n e ™ co n - trol allows the field selection of source fluid freeze protection points through jumpers. The fact ory setting of jumper JW3 (FP1) is set for water at 30 F . In earth loop applications, jumper ...

  • Carrier 50PEC09-18 - page 31

    31 OP TIONAL W ALL-MOUNTED THERMOST A T — T h e 50PEC water source heat pump units are built with standard in- ternal thermostats in either manual changeover (MCO) or auto- matic changeover (ACO) configur ation. Refer to Fig. 17-20. When desired, the unit can be furnished with a 24-v control circuit which is field wired to a Carrier -supplied acc ...

  • Carrier 50PEC09-18 - page 32

    32 Table 6 — Rnet Wiri ng Specificatio ns LEGEND T o wire the SP T sensor to the controller : 1. Partially cut , then bend and pull of f the outer jacket of the Rnet cable(s), being careful not to nick the inner insulation. 2. Strip ab out 1 / 4 in. of the inner insulation from each wire. See Fig. 34. 3. W ire each terminal on the sensor to the s ...

  • Carrier 50PEC09-18 - page 33

    33 2. Install shut-off/bal ancing valves and unions at each unit to allow unit removal for servicing. NOTE: If flex hoses are used, unions are not necessary . 3. Install strainers at the inlet of each system circulating pump. 4. Before making the final water connections, flush the sys- tem as described in the Pre-Start-Up section of this manual. Af ...

  • Carrier 50PEC09-18 - page 34

    34 8. Refill the system with clea n, chemically treated water . Since water varies for each lo cality , contact a local water treatment company for the correct treatment chemicals to use in the area. Set the boiler to raise the loop temperature to approximately 85 F . . Circulate the solution for a minimum of 8 to 24 hours. At the end of this perio ...

  • Carrier 50PEC09-18 - page 35

    35 Table 9 — Water Quality Guideline s LEGEND *Heat exchanger mate rials considered ar e copper, cupronickel, 304 SS (stainless ste el), 316 SS , titanium. †Closed reci rculating sy stem is iden tified by a closed p ressur ized piping system. **Recircul ating open wells shoul d obser ve the open recirculat ing design consideratio ns. ††If t ...

  • Carrier 50PEC09-18 - page 36

    36 FIELD SELECT ABLE INPUTS Jumpers and DIP (dual in-line package) switches on the control board are used to customize unit operation and can be configured in the field. Complete C Control J umper Settings (See Fig. 17, 18, and 21) W A TER COIL FREEZE PROTECTION (FP1) LIMI T SETTING — Se l e c t j u mp e r 3 , ( JW 3 - F P 1 Lo w T em p ) t o cho ...

  • Carrier 50PEC09-18 - page 37

    37 Table 11 — DIP Switch Bloc k S2 — Accessory 2 Re lay Options LEGEND NO TE: All other switch combinations are in v alid. Auto Dehumidification Mode or High Fan Mode — Switch 7 provides selection of auto dehumidification fan m ode or high fan mode. In auto dehumidification fan mode, the fan speed relay will remain off during Cooling S tage 2 ...

  • Carrier 50PEC09-18 - page 38

    38 5. Slowly turn thermostat toward cooler position. Both fan and compressor should shut off when thermostat set point equals room temperature. Room temperature must be above 65 F for unit to shut off. Unit Start-Up with WSHP Open Controls — The WSHP Open is a multi-protocol (default BACnet*) con- troller with extensive features, flexible options ...

  • Carrier 50PEC09-18 - page 39

    39 b. Select W eekly , then pres s enter (7 schedules available). c. Select day and press enter . d. Press enter again and select ADD or DEL (DECR or INCR) set schedule. e. Enter ON/OFF time, then press continue. f. Press OK to appl y and save to a particular day of the week. g. Continue to add the same or dif ferent sched ule spe- cific days of th ...

  • Carrier 50PEC09-18 - page 40

    40 Table 13 — Approximate Fluid Volume (gal) per 100 f t of Pipe LEGEND NO TE: V olume of heat ex changer is appro ximately 1.0 gallon. Table 14 — Antifr eeze Percentages by Volume Cooling T ower/Boi ler Systems — Th ese systems typically use a common loop maintained at 60 to 90 F . Carrier recommends using a closed circuit evaporative coolin ...

  • Carrier 50PEC09-18 - page 41

    41 application, all compressor relays and related functions will track with their associated DIP switch 2 on S1. NIGHT LOW LIMIT (NLL) ST AGED HEA TING — In NLL staged Heating mode, the override (OVR) input becomes active and is recognized as a call for heating and the control will immediately go into a Heating Stage 1 mode. With an additional 30 ...

  • Carrier 50PEC09-18 - page 42

    42 maximum speed. If the SA T continues to fall 5 F below the minimum SA T limit, all cooling stages will be disabled. During Cooling mode, the reversing valve output will be held in the cooling position (either B or O type as configured) even after the compressor is stopped. The valve will not switch position until the Heating mode is required. Th ...

  • Carrier 50PEC09-18 - page 43

    43 ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers) specifications by providing a base ventilation rate and then increasing the rate as the CO 2 level in- creases. The control will begin to proportionally increase venti- lation when the CO 2 level rises above the start ventilation set point and will reach the full ...

  • Carrier 50PEC09-18 - page 44

    44 label. For example, flashing c ode 1 will have an alarm relay cycling code 1. Code 1 indica tes the control has not faulted since the last power-off to power -on sequence. WSHP Open T est Mode — T o enter WSHP Open test mode, navigate from the BAC view 6 home screen to the config- uration screen. Choose the servic e screen and enable unit test ...

  • Carrier 50PEC09-18 - page 45

    45 Table 17 — Aquazone™ Deluxe D Control Current LED Status an d Alarm Relay Operations LEGEND NO TES: 1. If there is no f ault in memory , the F ault LED will flash code 1. 2. Codes will be displa yed with a 10- second F ault LED pause. 3. Slow flash is 1 flash e v ery 2 seconds. 4. F ast flash is 2 flashes e v ery 1 second. 5. EXAMPLE: “Fla ...

  • Carrier 50PEC09-18 - page 46

    46 produce water (or debris) velocitie s that can erode the heat ex- changer wall and ultimately produce leaks. Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment anal- ysis is recommended. Refer to the Carrier System Design Man- ual, Part 5, for general water conditioning information. ...

  • Carrier 50PEC09-18 - page 47

    47 Checkin g System Char ge — Units are shipped with full operating charge. If rechar ging is necessary: 1. Insert thermometer bulb in insulating rubber sleeve on liquid line near filter drier . Use a digital thermometer for all temperature measurements. DO NOT use a mercury or dial-type thermometer . 2. Connect pressure gage to di schar ge line ...

  • Carrier 50PEC09-18 - page 48

    48 Table 18 — Troubleshooting LEGEND F AUL T HEA TING COOLING POSSIBLE CAUSE SOLUTION Main Power Problems X X Gree n Status LED Off Check line voltage circuit breaker and disconnect . Check for line v oltage bet ween L1 and L2 on the co ntactor. Check f or 24-vac between R and C on con troller . Check primar y/ secondar y voltage on t ransformer ...

  • Carrier 50PEC09-18 - page 49

    49 Table 18 — Troubleshooting ( cont) LEGEND F AUL T HEA TING COOLING POSSIBLE CAUSE SOLUTION Only Compressor Runs X X Ther mostat wir ing Check G wiring at heat pump. Jumper G and R for fan operation. Check Y and W wiring at hea t pump . Jumper Y and R for compressor operatio n in T es t mode. X X Fan motor relay Jumper G and R for f an operatio ...

  • Carrier 50PEC09-18 - page 50

    50 APPENDIX A — WSHP OPEN SCREEN CONFIGURA TION LEGEND SCREEN NAME POINT NAME PAS SWO RD LEVEL EDITABLE RANGE DEFAULT NOTES Equipment Status Operati ng Mode No P assword Re q uired Off, F an Only , Economize , Cooling, Heating, Cont F an, T est, Start Dela y , Dehumidify Display s unit operat ing mode SPT F Displa ys SPT SA T F Displa ys SA T Con ...

  • Carrier 50PEC09-18 - page 51

    51 APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PA SS WO RD LEVEL EDITABLE RANGE DEFAULT NOTES Unit Maintenance Operating Mode No P assw ord re q uired Off, F an Only ,Econom ize, Cooling, Heating, Cont F an, T est, Start Delay , Dehumidify Display s unit operating mode F an Oper ating Mode Auto /Continuou s/Al ...

  • Carrier 50PEC09-18 - page 52

    52 APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont) LEGEND SCREEN NAME P OINT NAME PA S SWO RD LEVEL EDITABLE RANG E DEFAULT NOTES Configuration Set Points Occupied Heating User/Admin P assw ord le vel access X 40 - 90 F 72 F Defi nes the Occupied Heating Set P oint Occupied Cooling X 55 - 99 F 76 F Def ines the Occupied Cooling Set P oint Unoc ...

  • Carrier 50PEC09-18 - page 53

    53 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PAS SW OR D LEVE L EDITABLE RANGE DEFAULT NOTES Configuration Unit Configuration F an Mode Admin P ass word lev el access only X Aut o/Continuous/ Always On Continuous Aut o= Intermittant operation during both occupied and unoccupied periods/ Continuou s = Intermi ...

  • Carrier 50PEC09-18 - page 54

    54 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME POINT NAME PAS SW OR D LEVEL EDITABLE RANGE DEFAULT NOTES Configuration Service Configuration # of F an Speeds Admin P ass word lev el access only X 1,2 ,3 3 Used to set n umber of fan mot or speeds G Output T ype X F an On/F an Low Fan On When set to F an On, G out put is e ...

  • Carrier 50PEC09-18 - page 55

    55 APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont) LEGEND SCREEN NAME P OINT NAME PA S SWO RD LEVEL EDITABLE RANGE DEFAUL T NOTES Configuration Alarm Configuration SPT Occupied Alarm Hysteresis Admin P assw ord lev el access only X2 - 2 0 F 5 F Defines the h ysteresis applied abo ve the cooling and belo w the heating set points bef ore an alar ...

  • Carrier 50PEC09-18 - page 56

    56 ...

  • Carrier 50PEC09-18 - page 57

    57 ...

  • Carrier 50PEC09-18 - page 58

    Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 04-53 500052-01 Printed in U .S .A. Form 50PEC-2SI Pg 58 7-09 Replaces: 50PEC-1SI Copy right 2009 Carrier Cor poration ...

  • Carrier 50PEC09-18 - page 59

    CL-1 50PEC UNIT ST ART -UP CHECKLIST CUSTOMER: ___________________________ JOB NAME: _ _____________________________________ _ MODEL NO.:___________________________ S ERIAL NO.: ____________________ DA TE: _________ I. PRE-ST ART -UP DOES THE UNIT VOL T AGE CORRESPOND WI TH THE SUPPL Y VOL T AGE A V AILABLE ? (Y/N) HA VE THE POWER AND CONTROL WIRIN ...

  • Carrier 50PEC09-18 - page 60

    Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 04-53 500052-01 Printed in U .S. A. Form 50PEC-2SI CL-2 7-09 Replaces: 50PE C-1SI Copy right 2009 Carrier Cor poration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ...

Fabricant Carrier Catégorie Heat Pump

Les documents que nous recevons du fabricant de l'appareilCarrier 50PEC09-18 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Carrier
- manuels d’utilisations 50PEC09-18
- fiches produit Carrier
- dépliants
- ou étiquettes-énergie Carrier 50PEC09-18
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Carrier 50PEC09-18.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Carrier 50PEC09-18, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Carrier 50PEC09-18. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Carrier 50PEC09-18.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Carrier 50PEC09-18, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Carrier 50PEC09-18 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Carrier 50PEC09-18.

Le manuel d’utilisation complet Carrier, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Carrier 50PEC09-18 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Carrier 50PEC09-18, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lCarrier 50PEC09-18 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Carrier 50PEC09-18 - qui devraient nous aider dans les premières étapes lors de l'utilisation Carrier 50PEC09-18
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Carrier 50PEC09-18
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Carrier 50PEC09-18 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Carrier 50PEC09-18?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Carrier 50PEC09-18, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Carrier 50PEC09-18 il est probable qu’il a envie de partager la façon de le résoudre.