Bedienungsanleitung Bard 1 W48A1

25 Seiten 0.48 mb
Download

Zur Seite of 25

Summary
  • Bard 1 W48A1 - page 1

    Manual 2100-508A Page 1 of 25 INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS W18A1 W18L1 W24A1 W24L1 W30A1 W30L1 W36A1 W36L1 W42A1 W42L1 W48A1 W48L1 W60A1 W60L1 W70A1 W70L1 Manual : 2100-508A Supersedes: 2100-508 File: V olume III T ab 16 Date: 02-10-09 Bard Manufacturing Company , Inc. Bryan, Ohio 43506 Since 1914...Mov ...

  • Bard 1 W48A1 - page 2

    Manual 2100-508A Page 2 of 25 Content s Figures Figure 1 Fresh Air Damper Assembly ................... 5 Figure 2 Unit Dimensions ...................................... 7 Figure 3A Mounting Instructions .............................. 8 Figure 3B Mounting Instructions - W18, 24, 30, 36 .... 9 Figure 3C Mounting Instructions - W42, 48, 60, 70 ... 10 ...

  • Bard 1 W48A1 - page 3

    Manual 2100-508A Page 3 of 25 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Ele ctrical Code ...................... ANSI ...

  • Bard 1 W48A1 - page 4

    Manual 2100-508A Page 4 of 25 W ALL MOUNT GENERAL INFORMA TION AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE W 42 A 1– A 10 X X X X X A NOTE: Vent options X, B and M are without exhaust capability. May require separate field supplied barometric relief in buildi ng. SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for extern ...

  • Bard 1 W48A1 - page 5

    Manual 2100-508A Page 5 of 25 DUCT WORK All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both cons ...

  • Bard 1 W48A1 - page 6

    Manual 2100-508A Page 6 of 25 s s e c c A e c i v r e S r o f d e r i u q e R s e c n a r a e l C w o l f r i A r e s n e d n o C e t a u q e d A d n a S L E D O M E D I S T F E L E D I S T H G I R A 6 3 W , A 0 3 W , A 4 2 W , A 8 1 W " 5 1 " 0 2 L 6 3 W , L 0 3 W , L 4 2 W , L 8 1 W " 0 2 " 5 1 A 0 7 W , A 0 6 W , A 8 4 W , A ...

  • Bard 1 W48A1 - page 7

    Manual 2100-508A Page 7 of 25 I A C K 2.13 H J 2.63 9.06 P M L O E .44 W 5.75 F G R S S S S S T D Return A ir Opening MIS-2488 B Drain Inle t Air Air Outlet Front View Side View Cond. 1 Back View Condenser Bracket Installation Bottom (Built In) Brackets Mounting Side Wall Location Shipping Flashing Entrances Electrical Optional Entrance Electrical ...

  • Bard 1 W48A1 - page 8

    Manual 2100-508A Page 8 of 25 FIGURE 3A W18A1, W18L1, W24A1, W24L1 MOUNTING INSTRUCTIONS 12" 12" 12" 12" 12" 20" 20" 1" 3" 4" Typ. 8" 20 1 2 " 12" 1" 3 1 8 " 4" Typ. 5" 7 8 " 3 13 16 " 2" 2" 7 1 16 " 7 1 16 " DUCT CONTROLS AND HEATER A ...

  • Bard 1 W48A1 - page 9

    Manual 2100-508A Page 9 of 25 FIGURE 3B W30A1, W30L1, W36A1, W36L1 MOUNTING INSTRUCTIONS " 12" 12" 12" 12" 12" Typ . 4 " 2 28" 1" 3" 4" Typ . 4 1 2 " 8 7 5" 1 14" 1" 3 1 8 " E B A D C 4" C MATERIALS AIR DUCT IS RE QUIRED CONTROLS AND HEATE R ACCES S IS ON OP POSI T ...

  • Bard 1 W48A1 - page 10

    Manual 2100-508A Page 10 of 25 FIGURE 3C W42A1, W42L1, W48A1, W48L1, W60A1, W60L1, W70A1, W70L1 MOUNTING INSTRUCTIONS D 16" 16" 16" 16" 16" 1 7 8 " 6 1 2 " 6 1 2 " 2 1 8 " 7 8 " 1" 3" 4" Typ. 4" Typ. 6 1 2 " 30" E 16" A C C 3 1 8 " B RAIN FLASH ING TOP RETURN ...

  • Bard 1 W48A1 - page 11

    Manual 2100-508A Page 11 of 25 FIGURE 4 ELECTRIC HEAT CLEARANCE W30A1, W30L1, W36A1, W36L1, W42A1, W42L1, W48A1, W48L1, W60A1, W60L1, W70A1, W70L1 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 ...

  • Bard 1 W48A1 - page 12

    Manual 2100-508A Page 12 of 25 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS DUCT OPENING RETURN AIR SUPPLY AIR WOOD FRAME WALL INSTALLATION OPENING WALL BE FO R E MOUNT ON UNIT OPENING BEFORE INSTALL ATION BOTTOM M OUNTING CONCRET E B L OCK WAL L I NS T A LL AT IO N BRACKET. MOUNT ON OPENING WOOD OR STEEL SIDING OPENING I ...

  • Bard 1 W48A1 - page 13

    Manual 2100-508A Page 13 of 25 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS LOWER ED RAISED FLOO R RAFTERS SUPPLY AIR CEILING SURFACE WAL L SL EEVE RETURN AIR CLOSET W ALL GRILL E FLASHING RETURN AIR FLASHING SUPPLY DUCT MAYBE L OCATED IN AN ATTIC OR BELO W CEIL ING RAFTERS AS SHOWN SUPPLY DUCT MAY BE L OCATED IN AN ATTIC SURFACE RAFTERS FINISHED CE ...

  • Bard 1 W48A1 - page 14

    Manual 2100-508A Page 14 of 25 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed K ...

  • Bard 1 W48A1 - page 15

    Manual 2100-508A Page 15 of 25 ST ART UP THESE UNITS REQUIRE R-410A REFRIGERANT AND POL YOL ESTER OIL. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant. 3. Use manifold gauges rated for R-410A (800 psi/250 psi low). 4. R-410A is a binary blend of ...

  • Bard 1 W48A1 - page 16

    Manual 2100-508A Page 16 of 25 ST ART UP (Continued) IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. HIGH PRESSURE SWITCH All W**A/W**L wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch. If tripped, this pressure switch may ...

  • Bard 1 W48A1 - page 17

    Manual 2100-508A Page 17 of 25 SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. On a ...

  • Bard 1 W48A1 - page 18

    Manual 2100-508A Page 18 of 25 TROUBLESHOOTING FIGURE 8 FAN BLADE SETTING MIS-1724 TABLE 1 FAN BLADE DIMENSION REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. 3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws. 4. Unwire con ...

  • Bard 1 W48A1 - page 19

    Manual 2100-508A Page 19 of 25 TABLE 3 COOLING PRESSURE TABLE Air Temperature Entering Outdoor Coil °F Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuate ...

  • Bard 1 W48A1 - page 20

    Manual 2100-508A Page 20 of 25 TABLE 4 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conducto ...

  • Bard 1 W48A1 - page 21

    Manual 2100-508A Page 21 of 25 TABLE 5 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conducto ...

  • Bard 1 W48A1 - page 22

    Manual 2100-508A Page 22 of 25 TABLE 6 RECOMMENDED AIRFLOW TABLE 7 INDOOR BLOWER PERFORMANCE TABLE 8 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY V alues shown are for units equipped with standard 1-inch throwaway filter or 1-inch washable filter . Derate ESP by .15 for 2-inch pleated filters. l e d o M d e t a R * M F C d e t a R * P S E d e d n e ...

  • Bard 1 W48A1 - page 23

    Manual 2100-508A Page 23 of 25 TABLE 9 ELECTRIC HEAT s l e d o M1 - V 0 4 21 - V 8 0 23 - V 0 4 23 - V 8 0 23 - V 0 6 4 W Ks p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T B 47 . 6 10 5 6 3 14 . 4 10 4 2 0 1 58 . 0 25 6 0 7 11 . 8 10 0 8 2 1 64 . 4 10 0 5 0 25 . 2 10 6 3 5 12 . 70 0 5 0 2 83 . 3 30 0 3 7 28 . 8 25 7 4 0 2 97 . 1 ...

  • Bard 1 W48A1 - page 24

    Manual 2100-508A Page 24 of 25 W18A1-A W24A1-A W24A1-B W24A1-C W30A1-A W30A1-B W30A1-C W36A1-A W36A1-B W36A1-C W42A1-A W42A1-B W42A1-C W48A1-A W48A1-B W48A1-C W60A1-A W60A1-B W60A1-C W70A1-A W70A1-B W70A1-C TABLE 10 OPTIONAL ACCESSORIES r e b m u N t r a P 5 0 A - 2 0 A W H EX X 8 0 A - A 2 0 W H EX X 0 1 A - A 2 0 A W H EX X 6 0 B - 4 2 A W H EX 6 ...

  • Bard 1 W48A1 - page 25

    Manual 2100-508A Page 25 of 25 TABLE 11 VENT & CONTROL OPTIONS W18, W24 W30, W36 W42, W48, W60, W70 r e b m u N t r a Pn o i t p i r c s e D 4 1 - C M CT D O XXX 5 1 - C M C) e s a h P - 1 V 0 3 2 ( t i K t r a t S XXX 3 2 - C M CC D DX X 4 2 - C M CC D DX 8 2 - C M CC A L XXX 2 - D A F Bd r a d n a t S - r e p m a D r i A h s e r F c i r t e m ...

Produzent Bard Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Bard 1 W48A1 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Bard
- Bedienungsanleitungen 1 W48A1
- Produktkarten Bard
- Informationsbroschüren
- oder Energieetiketten Bard 1 W48A1
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Bard 1 W48A1.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Bard 1 W48A1, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Bard 1 W48A1. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Bard 1 W48A1 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Bard 1 W48A1, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Bard 1 W48A1 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Bard 1 W48A1 verständlich ist.

Eine gänzliche Bedienungsanleitung von Bard sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Bard 1 W48A1 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Bard 1 W48A1 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Bard 1 W48A1, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Bard 1 W48A1 - die uns die ersten Schritte während der Nutzung von Bard 1 W48A1 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Bard 1 W48A1 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Bard 1 W48A1 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Bard 1 W48A1?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Bard 1 W48A1 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Bard 1 W48A1 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)