    Manual 2100-508A Page 1 of 25 INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS W18A1 W18L1 W24A1 W24L1 W30A1 W30L1 W36A1 W36L1 W42A1 W42L1 W48A1 W48L1 W60A1 W60L1 W70A1 W70L1 Manual : 2100-508A Supersedes: 2100-508 File: V olume III T ab 16 Date: 02-10-09 Bard Manufacturing Company , Inc. Bryan, Ohio 43506 Since 1914...Mov ...

  • Bard 1 W48A1 - page 2

    Manual 2100-508A Page 2 of 25 Content s Figures Figure 1 Fresh Air Damper Assembly ................... 5 Figure 2 Unit Dimensions ...................................... 7 Figure 3A Mounting Instructions .............................. 8 Figure 3B Mounting Instructions - W18, 24, 30, 36 .... 9 Figure 3C Mounting Instructions - W42, 48, 60, 70 ... 10 ...

  • Bard 1 W48A1 - page 3

    Manual 2100-508A Page 3 of 25 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Ele ctrical Code ...................... ANSI ...

  • Bard 1 W48A1 - page 4

    Manual 2100-508A Page 4 of 25 W ALL MOUNT GENERAL INFORMA TION AIR CONDITIONER WALL MOUNT MODEL NOMENCLATURE W 42 A 1– A 10 X X X X X A NOTE: Vent options X, B and M are without exhaust capability. May require separate field supplied barometric relief in buildi ng. SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for extern ...

  • Bard 1 W48A1 - page 5

    Manual 2100-508A Page 5 of 25 DUCT WORK All duct work, supply and return, must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both cons ...

  • Bard 1 W48A1 - page 6

    Manual 2100-508A Page 6 of 25 s s e c c A e c i v r e S r o f d e r i u q e R s e c n a r a e l C w o l f r i A r e s n e d n o C e t a u q e d A d n a S L E D O M E D I S T F E L E D I S T H G I R A 6 3 W , A 0 3 W , A 4 2 W , A 8 1 W " 5 1 " 0 2 L 6 3 W , L 0 3 W , L 4 2 W , L 8 1 W " 0 2 " 5 1 A 0 7 W , A 0 6 W , A 8 4 W , A ...

  • Bard 1 W48A1 - page 7

    Manual 2100-508A Page 7 of 25 I A C K 2.13 H J 2.63 9.06 P M L O E .44 W 5.75 F G R S S S S S T D Return A ir Opening MIS-2488 B Drain Inle t Air Air Outlet Front View Side View Cond. 1 Back View Condenser Bracket Installation Bottom (Built In) Brackets Mounting Side Wall Location Shipping Flashing Entrances Electrical Optional Entrance Electrical ...

  • Bard 1 W48A1 - page 8

    Manual 2100-508A Page 8 of 25 FIGURE 3A W18A1, W18L1, W24A1, W24L1 MOUNTING INSTRUCTIONS 12" 12" 12" 12" 12" 20" 20" 1" 3" 4" Typ. 8" 20 1 2 " 12" 1" 3 1 8 " 4" Typ. 5" 7 8 " 3 13 16 " 2" 2" 7 1 16 " 7 1 16 " DUCT CONTROLS AND HEATER A ...

  • Bard 1 W48A1 - page 9

    Manual 2100-508A Page 9 of 25 FIGURE 3B W30A1, W30L1, W36A1, W36L1 MOUNTING INSTRUCTIONS " 12" 12" 12" 12" 12" Typ . 4 " 2 28" 1" 3" 4" Typ . 4 1 2 " 8 7 5" 1 14" 1" 3 1 8 " E B A D C 4" C MATERIALS AIR DUCT IS RE QUIRED CONTROLS AND HEATE R ACCES S IS ON OP POSI T ...

  • Bard 1 W48A1 - page 10

    Manual 2100-508A Page 10 of 25 FIGURE 3C W42A1, W42L1, W48A1, W48L1, W60A1, W60L1, W70A1, W70L1 MOUNTING INSTRUCTIONS D 16" 16" 16" 16" 16" 1 7 8 " 6 1 2 " 6 1 2 " 2 1 8 " 7 8 " 1" 3" 4" Typ. 4" Typ. 6 1 2 " 30" E 16" A C C 3 1 8 " B RAIN FLASH ING TOP RETURN ...

  • Bard 1 W48A1 - page 11

    Manual 2100-508A Page 11 of 25 FIGURE 4 ELECTRIC HEAT CLEARANCE W30A1, W30L1, W36A1, W36L1, W42A1, W42L1, W48A1, W48L1, W60A1, W60L1, W70A1, W70L1 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is important to insure that the 1/4 ...

  • Bard 1 W48A1 - page 12

    Manual 2100-508A Page 12 of 25 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS DUCT OPENING RETURN AIR SUPPLY AIR WOOD FRAME WALL INSTALLATION OPENING WALL BE FO R E MOUNT ON UNIT OPENING BEFORE INSTALL ATION BOTTOM M OUNTING CONCRET E B L OCK WAL L I NS T A LL AT IO N BRACKET. MOUNT ON OPENING WOOD OR STEEL SIDING OPENING I ...

  • Bard 1 W48A1 - page 13

    Manual 2100-508A Page 13 of 25 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS LOWER ED RAISED FLOO R RAFTERS SUPPLY AIR CEILING SURFACE WAL L SL EEVE RETURN AIR CLOSET W ALL GRILL E FLASHING RETURN AIR FLASHING SUPPLY DUCT MAYBE L OCATED IN AN ATTIC OR BELO W CEIL ING RAFTERS AS SHOWN SUPPLY DUCT MAY BE L OCATED IN AN ATTIC SURFACE RAFTERS FINISHED CE ...

  • Bard 1 W48A1 - page 14

    Manual 2100-508A Page 14 of 25 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed K ...

  • Bard 1 W48A1 - page 15

    Manual 2100-508A Page 15 of 25 ST ART UP THESE UNITS REQUIRE R-410A REFRIGERANT AND POL YOL ESTER OIL. GENERAL: 1. Use separate service equipment to avoid cross contamination of oil and refrigerants. 2. Use recovery equipment rated for R-410A refrigerant. 3. Use manifold gauges rated for R-410A (800 psi/250 psi low). 4. R-410A is a binary blend of ...

  • Bard 1 W48A1 - page 16

    Manual 2100-508A Page 16 of 25 ST ART UP (Continued) IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. HIGH PRESSURE SWITCH All W**A/W**L wall mounted air conditioner series models are supplied with a remote reset for the high and low pressure switch. If tripped, this pressure switch may ...

  • Bard 1 W48A1 - page 17

    Manual 2100-508A Page 17 of 25 SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. On a ...

  • Bard 1 W48A1 - page 18

    Manual 2100-508A Page 18 of 25 TROUBLESHOOTING FIGURE 8 FAN BLADE SETTING MIS-1724 TABLE 1 FAN BLADE DIMENSION REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. 3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws. 4. Unwire con ...

  • Bard 1 W48A1 - page 19

    Manual 2100-508A Page 19 of 25 TABLE 3 COOLING PRESSURE TABLE Air Temperature Entering Outdoor Coil °F Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuate ...

  • Bard 1 W48A1 - page 20

    Manual 2100-508A Page 20 of 25 TABLE 4 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conducto ...

  • Bard 1 W48A1 - page 21

    Manual 2100-508A Page 21 of 25 TABLE 5 1 Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. 2 Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes. 3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conducto ...

  • Bard 1 W48A1 - page 22

    Manual 2100-508A Page 22 of 25 TABLE 6 RECOMMENDED AIRFLOW TABLE 7 INDOOR BLOWER PERFORMANCE TABLE 8 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY V alues shown are for units equipped with standard 1-inch throwaway filter or 1-inch washable filter . Derate ESP by .15 for 2-inch pleated filters. l e d o M d e t a R * M F C d e t a R * P S E d e d n e ...

  • Bard 1 W48A1 - page 23

    Manual 2100-508A Page 23 of 25 TABLE 9 ELECTRIC HEAT s l e d o M1 - V 0 4 21 - V 8 0 23 - V 0 4 23 - V 8 0 23 - V 0 6 4 W Ks p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T Bs p m AH U T B 47 . 6 10 5 6 3 14 . 4 10 4 2 0 1 58 . 0 25 6 0 7 11 . 8 10 0 8 2 1 64 . 4 10 0 5 0 25 . 2 10 6 3 5 12 . 70 0 5 0 2 83 . 3 30 0 3 7 28 . 8 25 7 4 0 2 97 . 1 ...

  • Bard 1 W48A1 - page 24

    Manual 2100-508A Page 24 of 25 W18A1-A W24A1-A W24A1-B W24A1-C W30A1-A W30A1-B W30A1-C W36A1-A W36A1-B W36A1-C W42A1-A W42A1-B W42A1-C W48A1-A W48A1-B W48A1-C W60A1-A W60A1-B W60A1-C W70A1-A W70A1-B W70A1-C TABLE 10 OPTIONAL ACCESSORIES r e b m u N t r a P 5 0 A - 2 0 A W H EX X 8 0 A - A 2 0 W H EX X 0 1 A - A 2 0 A W H EX X 6 0 B - 4 2 A W H EX 6 ...

  • Bard 1 W48A1 - page 25

    Manual 2100-508A Page 25 of 25 TABLE 11 VENT & CONTROL OPTIONS W18, W24 W30, W36 W42, W48, W60, W70 r e b m u N t r a Pn o i t p i r c s e D 4 1 - C M CT D O XXX 5 1 - C M C) e s a h P - 1 V 0 3 2 ( t i K t r a t S XXX 3 2 - C M CC D DX X 4 2 - C M CC D DX 8 2 - C M CC A L XXX 2 - D A F Bd r a d n a t S - r e p m a D r i A h s e r F c i r t e m ...

メーカー Bard カテゴリー Air Conditioner

Bard 1 W48A1のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 1 W48A1の取扱説明書
- Bardの製品カード
- パンフレット
- またはBard 1 W48A1の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Bard 1 W48A1の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Bard 1 W48A1の取り付け説明書、サービスマニュアル、簡易説明書、またはBard 1 W48A1のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Bard 1 W48A1の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Bard 1 W48A1デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBard 1 W48A1を使用するのを助ける技術的文書のことです。説明書は通常、全てのBard 1 W48A1ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Bardの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Bard 1 W48A1の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBard 1 W48A1の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Bard 1 W48A1に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Bard 1 W48A1デバイスの基本機能を使うにあたってのヒント。 Bard 1 W48A1のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Bard 1 W48A1に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるBard 1 W48A1のメーカー/サービスへの連絡先に関する情報。

Bard 1 W48A1についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもBard 1 W48A1の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがBard 1 W48A1で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)