    LT-0230 (2/97) Do Not Throw Away! This programming guide contains information you need to program and service the XR10 panel and should be kept along with your other DMP technical documentation. XR10 Command Processor Panel Programming Guide 10 Zone Burglary/Fire/Access Control Panel with Built-in Communicator 2841 E. Industrial Drive Springfield, ...

  • DMP Electronics Command Processor Panel - page 2

    MODEL XR10 PROGRAMMING GUIDE Copyright © 1995 - 1997 Digital Monitoring Products, Inc. Information furnished by DMP is believed to be accurate and reliable. This information is subject to change without notice. When using the Series XR10 control for any UL, NFPA, CSFM or other listing organization's approved methods, refer to this manual and ...

  • DMP Electronics Command Processor Panel - page 3

    TABLE OF CONTENTS Introduction .................................................................................................................................................................. 1 1.1 Before Y ou Begin .................................................................................................................................... ...

  • DMP Electronics Command Processor Panel - page 4

    TABLE OF CONTENTS Section Page 6.1 SYSTEM OPTIONS ................................................................................................................................................ 9 6.2 ALL/PERIMETER ....................................................................................................................................... ...

  • DMP Electronics Command Processor Panel - page 5

    1 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10 Programming Guide 1-INTRODUCTION Introduction 1.1 Before You Begin About this Guide This guide provides programming information for the DMP XR10 Command Processor Panel. After this Introduction, the remaining sections describe the functions of each programming menu item along w ...

  • DMP Electronics Command Processor Panel - page 6

    2 XR10 Programming Guide 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 1 - INTRODUCTION 1.4 Programmer Lockout Codes Although the XR10 panel allows you to enter the built-in Programmer without a lockout code, we recommend you install one to restrict programming access to only those persons your company authorizes. You can do this ...

  • DMP Electronics Command Processor Panel - page 7

    3 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10 Programming Guide 1 - INTRODUCTION If you are changing a phone number or account number, press the SELECT key followed by the appropriate digit keys. If entering a communication type or choosing a programming option, the keypad displays the available response options above the ...

  • DMP Electronics Command Processor Panel - page 8

    4 XR10 Programming Guide 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 2 - INITIALIZATION 2.1 INITIALIZATION This function allows you to set the panel's user codes and Programmer selections back to factory defaults before programming the panel for the first time or a new installation. After you select YES to clear a section ...

  • DMP Electronics Command Processor Panel - page 9

    5 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10 Programming Guide 3 - COMMUNICATION 3.6 TEST FREQUENCY Allows you to set how often the panel's test report is sent to the receiver. Enter from 1 to 60 days. Enter zero to disable the test report. How to set the Recall Test time Once you have finished programming the panel, ...

  • DMP Electronics Command Processor Panel - page 10

    6 XR10 Programming Guide 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 3.16 PAGER REPORTING YES allows the panel to send Alarm, Trouble, Opening, and Closing reports to a numeric pager. The panel uses DTMF tones to generate the account and report information sent over the pager terminal equipment. Selecting NO allows you to use t ...

  • DMP Electronics Command Processor Panel - page 11

    7 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10 Programming Guide 4 - REMOTE OPTIONS 4.1 REMOTE OPTIONS This section allows you to enter the information needed for Remote Command/Remote Programming operation. A description of the Remote Options follow: 4.2 REMOTE KEY This option allows you to enter a code of up to eight digi ...

  • DMP Electronics Command Processor Panel - page 12

    8 XR10 Programming Guide 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 5.1 SYSTEM REPORTS This section of the Programmer allows you to select the reports the XR10 sends to the receiver. 5.2 OPENING/CLOSING REPORTS YES allows the panel to send opening/closing reports by user to the receiver. 5.3 ABORT REPORT YES allows the panel t ...

  • DMP Electronics Command Processor Panel - page 13

    9 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10 Programming Guide 6.1 SYSTEM OPTIONS This section allows you to select system wide functions of the XR10 system. 6.2 ALL/PERIMETER YES configures the panel as a Perimeter (Area 1) and Interior (Area 2) system. NO configures the panel for Home/Sleep/Away operation. In addition t ...

  • DMP Electronics Command Processor Panel - page 14

    10 XR10 Programming Guide 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 7.1 OUTPUT OPTIONS This function allows you to program the panel's Bell Output functions and certain Output options. Switched Ground (open collector) outputs are available from the XR10 when using a 4-wire output harness (Model 300 Harness). Refer to the ...

  • DMP Electronics Command Processor Panel - page 15

    11 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10 Programming Guide 7.5 OUTPUT ACTION This option allows you to define the operation of the panel's four annunciator outputs. 7.5A CUTOFF OUTPUTS Any or all of the available outputs can be programmed here to turn off after the time specified in OUTPUT CUTOFF TIME . See sect ...

  • DMP Electronics Command Processor Panel - page 16

    12 XR10 Programming Guide 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 8.1 ZONE INFORMATION This allows you to define the operation of each protection zone used in the system. A description of each programming option follows: 8.2 ZONE NUMBER Enter the number of the zone you intend to program. Press COMMAND to enter a zone name. ...

  • DMP Electronics Command Processor Panel - page 17

    13 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10 Programming Guide 8.6 ARM AREAS This option specifies the areas to be armed by the Arming Type Zone. When disarmed, all areas in the system are disarmed. PERIMETER/ALL - Specify whether the arming zone arms just the Perimeter (PERIM) or the Perimeter and Interior areas (ALL) f ...

  • DMP Electronics Command Processor Panel - page 18

    14 XR10 Programming Guide 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 8.9A MESSAGE TO TRANSMIT You can send two report types to the receiver: Alarm and Trouble. These are represented by the characters A and T . Press any top row SELECT key to display the zone's report options. ALARM - Selecting A, allows an alarm report to ...

  • DMP Electronics Command Processor Panel - page 19

    15 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10 Programming Guide 8.11 ENTRY DELAY Select the entry delay timer for this zone. Entry delay timers 1 and 2 are programmed in section 6.4. 8.12 CROSS ZONE Select YES to enable cross zoning for this zone. Cross zoning requires this zone to trip twice, or this zone and another cro ...

  • DMP Electronics Command Processor Panel - page 20

    16 XR10 Programming Guide 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 9.1 STOP At the STOP prompt, pressing any SELECT key allows you to exit the XR10 Programmer. When selected, the panel performs an internal reset and exits the programmer. The Stop function causes the following to occur: • The system is DISARMED • The pane ...

  • DMP Electronics Command Processor Panel - page 21

    17 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10 Programming Guide 11.1 Status List The Status List is the current status of the system or records of recent system events that are displayed on the alphanumeric keypads. For example, in Home/Away systems, you might see the display SYSTEM READY . This would be the current statu ...

  • DMP Electronics Command Processor Panel - page 22

    18 XR10 Programming Guide 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 11.4 Zone Type Specifications This section describes applications for the default zone types in Zone Information programming. The XR10 panel contains 11 default zone types for use in configuring the system. These zone types provide the most commonly selected ...

  • DMP Electronics Command Processor Panel - page 23

    19 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10 Programming Guide 11.5 Zone Type Descriptions NT (Night Zone) - Controlled instant zone used for perimeter doors and windows and interior devices such as PIRs and Glassbreak detectors. DY (Day zone) - Used for emergency doors or fire doors to sound the keypad buzzer and displa ...

  • DMP Electronics Command Processor Panel - page 24

    20 XR10 Programming Guide 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 11.7 Default panel programming This program sheets shows the XR10 panel's default program settings. Figure A1: XR10 Factory Default Program 11 - APPENDIX Name Account Number Phone Date Address City State Zip SYSTEM OPTIONS All/Perimeter NO YES Closing Co ...

  • DMP Electronics Command Processor Panel - page 25

    21 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 XR10 Programming Guide 11.8 4-2 Communication Reports The table below contains a complete list of hexadecimal characters sent using the DMP 4-2 communication format. 11.9 How to Read this Table The first column on the left is the first digit of the 2-digit event code sent to the re ...

  • DMP Electronics Command Processor Panel - page 26

    22 XR10 Programming Guide 2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282 11.10 4-2 Examples The following examples are the actual event codes a central station would receive. The full report would also include the account number and checksum. When the central station receives this event code It means 1A A Fire alarm is being repor ...

Fabricante DMP Electronics Categoría Home Security System

Los documentos del dispositivo DMP Electronics Command Processor Panel que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos DMP Electronics
- manuales de instrucciones Command Processor Panel
- hojas de producto DMP Electronics
- folletos informativos
- o etiquetas energéticas DMP Electronics Command Processor Panel
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones DMP Electronics Command Processor Panel.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje DMP Electronics Command Processor Panel, instrucciones de servicio, instrucciones cortas o instrucciones de usuario DMP Electronics Command Processor Panel. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto DMP Electronics Command Processor Panel.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo DMP Electronics Command Processor Panel, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar DMP Electronics Command Processor Panel. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de DMP Electronics Command Processor Panel.

El manual de instrucciones completo de DMP Electronics debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual DMP Electronics Command Processor Panel - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice DMP Electronics Command Processor Panel, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de DMP Electronics Command Processor Panel que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo DMP Electronics Command Processor Panel - que deben facilitarnos los primeros pasos durante el uso de DMP Electronics Command Processor Panel
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con DMP Electronics Command Processor Panel
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de DMP Electronics Command Processor Panel en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de DMP Electronics Command Processor Panel?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con DMP Electronics Command Processor Panel, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con DMP Electronics Command Processor Panel probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)