    COMMERCIAL PRODUCT S Potential for Fire, Smoke and Asphyxiation Hazards T o the Homeowner or Equipment Owner: Please read and carefully follow all instructions provided in this manual regarding your responsibilities in caring for your heating equipment. Contact a professional, quali fi ed service agency for installation, start-up or service work. ...

  • Beckett CULUS CF1400 - page 2

    2 Special Requirements - The installation of a burner shall be in accordance with the regulations of authorities having Jurisdiction. For recommended installation practices in the U.S. refer to the latest edition of NFP A 31. (CSA-B139 and CSA-B140 in Canada. ○ Impaired Burner Performance & Fire Hazard Do NOT operate the burner beyond speci ? ...

  • Beckett CULUS CF1400 - page 3

    3 CF1400/CF2300 Burner Manual Owner ’ s Responsibility: Service Agency Responsibility: Follow these instructions exactly . Failure to follow these instructions, misuse, or incorrect adjustment of the burner could result in asphyxiation, explosion or fi re. Contact a professional, quali fi ed service agency for the installation, adjustment and s ...

  • Beckett CULUS CF1400 - page 4

    4 Pr e-Installa tion Checklist Combustion Air Supply The fuel supply piping and tank must provide #1 or #2 fuel oil at pressure or vacuum conditions suitable for the fuel unit (oil pump) on the burner . Refer to fuel unit literature in the literature envelope in the burner carton to verify allowable suction pressure. If fuel supply is level with or ...

  • Beckett CULUS CF1400 - page 5

    5 CF1400/CF2300 Burner Manual The fuel unit nozzle port pressure is factory set at 300 psig. Some original equipment manufacturer burner applications may call for a lower pressure to obtain a required fi ring rate. Do not change this pressure unless directed to do so by the appliance manufacturer . Electrical Supply V erify that the power connecti ...

  • Beckett CULUS CF1400 - page 6

    6 Model Firing Rate (gph) Minimum Dimensions Refractory Lined Wet-based Boilers HLHL CF1400 0 to 5 7.0” 25.0” 7.0” 25.0” 5 to 10 8.0” 35.0” 8.0” 40.0” CF2300 5 to 10 8.0” 35.0” 8.0” 40.0” 10 to 15 9.0” 40.0” 9.0” 50.0” 15 to 20 1 1.0” 55.0” 1 1.0” 60.0” Note: 10% turndown indicates suf fi cient reserve air t ...

  • Beckett CULUS CF1400 - page 7

    7 CF1400/CF2300 Burner Manual Stray Light The control must detect a dark, no- fl ame condition in order to start the burner or it will hold in the stray light lockout mode. Shield the burner view window from direct exposure to intense light. ○ ○ Mount the Bur ner Mount Flange(s) on Air T ube This section does not apply to burners with welded ? ...

  • Beckett CULUS CF1400 - page 8

    8 Figure 5 – Nozzle and Nozzle Line Assembly Figure 6 – Nozzle Line Assembly in Burner Mount Air T ube to Burner Remove the rear access door from the back of the burner for improved access to the interior . Attach the air tube to the burner with the bolts and acorn nuts provided. The acorn nuts must go on the outside of the burner , with the bo ...

  • Beckett CULUS CF1400 - page 9

    9 CF1400/CF2300 Burner Manual Set “Z” Dimension Replace the rear access door on the burner , making sure that the adjusting plate assembly is seated in the recessed area in the housing. Loosen acorn nut (item c ) and spline nut (item b ). Move nozzle line forward to the maximum head setting #9 and tighten acorn nut (item c ). Loosen acorn nut ( ...

  • Beckett CULUS CF1400 - page 10

    10 Special Note: The burner is shipped with a by- pass plug installed in the fuel unit. For low/high operation, the by-pass plug must be left in the fuel unit, regardless of the fuel system used (one-pipe with by-pass loop or two-pipe). Do not remove the by-pass plug. One-pipe Oil System By-pass Loop Refer to Figure 9 (item m ). Note the addition o ...

  • Beckett CULUS CF1400 - page 11

    11 CF1400/CF2300 Burner Manual Low- fi re/high- fi re operation – The fuel unit nozzle port pressure is factory set at 300 psig. At high fi re, full pressure (300 psig) is applied at the oil nozzle, causing full input. At low fi re, the by-passing is done inside the fuel unit when the by-pass valve operates. This by-passing of oil reduces the ...

  • Beckett CULUS CF1400 - page 12

    12 2 1 3 5 6 8 4 7 Standby Motor -off delay V alve-on delay T rial for ignition Ignition carryover Run Lockout Recycle 9 Pump prime Run : With a fl ame established and the control continuing to detect a fl ame, the burner will operate in the RUN Mode until the load demand is satis fi ed or a limit opens. If terminals RC1 and RC2 are jumpered, th ...

  • Beckett CULUS CF1400 - page 13

    13 CF1400/CF2300 Burner Manual Figure 13 – T ypical Wiring (7505P) Section: Wire the Burner ...

  • Beckett CULUS CF1400 - page 14

    14 Figure 14 – T ypical Wiring (R7184B) T ypical Burner Sequence of Operation - 7184B Control Refer to the appliance manufacturer ’s wiring diagram for actual speci fi cations. Standby — The burner is idle, waiting for a call for heat. When a call for heat is initiated, there is a 3- to 10-second delay while the control performs a safe start ...

  • Beckett CULUS CF1400 - page 15

    15 CF1400/CF2300 Burner Manual Pr epare the Bur ner f or Star t-up Start-up checklist V erify the following before attempting to start burner . Combustion air supply and venting have been inspected and veri fi ed to be free of obstructions and installed in accordance with all applicable codes. Fuel unit by-pass plug has not been installed for one- ...

  • Beckett CULUS CF1400 - page 16

    16 Figure 16 – Adjusting Plate Initial Setting, Typical T able 4A – CF1400 Initial Indicator Adjustment Plate Settings CF1400 T ube Head Position Damper Position Approximate Head Setting Firing Rate (gph) Approximate Air Damper Setting Firing Rate (gph) A 0 4.00 0 -- 1 4.50 10 -- 2 5.00 20 4.00 3 6.00 30 5.00 4 7.00 40 7.00 5 7.50 50 8.00 6 8.0 ...

  • Beckett CULUS CF1400 - page 17

    17 CF1400/CF2300 Burner Manual Initial Air Settings If your burner was built for a speci fi c OEM (Original Equipment Manufacturer) application, the “Mfr ’s Settings” label (see Figure 1 ) will indicate the application and the initial air settings made at Beckett. Please verify those settings using the following procedure. If your burner was ...

  • Beckett CULUS CF1400 - page 18

    18 Star t the Bur ner Start Burner and V ent Air From Oil Line Disable Function Any time the motor is running, press and hold the reset button to disable the burner . The burner will remain of f as long as the button is held and will return to standby when released. Cad Cell Resistance Measurement: If the Beckett 7505 control is equipped with the G ...

  • Beckett CULUS CF1400 - page 19

    19 CF1400/CF2300 Burner Manual Place the low- fi re hold switch in the high- fi re position . The damper motor will begin to rotate after four seconds. Use combustion test instruments to adjust the burner . Adjust the air by moving the red cam to a lower number until a trace of smoke is achieved with CO 2 level as high as possible (lowest possibl ...

  • Beckett CULUS CF1400 - page 20

    20 Annual Service Replace the oil supply line fi lter . The line fi lter cartridge must be replaced to avoid contamination of the fuel unit and nozzle. Inspect the oil supply system. All fi ttings should be leak-tight. The supply lines should be free of water , sludge and other restrictions. Remove and clean the pump strainer if applicable. Repl ...

  • Beckett CULUS CF1400 - page 21

    21 CF1400/CF2300 Burner Manual SK9930 3 2 4 5 6 1 SK9931 8 9 7 Section: Replacement Parts Figure 19a – Burner Replacement Parts ...

  • Beckett CULUS CF1400 - page 22

    22 Item Part Name Description CF1400 Part No. CF2300 Part No. 1 Oil V alve Mounted on Junction Box 21789U 21789U 2 Knurled Nut All models 3666 3666 3 Adjusting plate assembly w/ cast aluminum door w/ stamped sheet-metal door 51213U 5201701U 51213U 5201701U 4 Fuel pump B2T A-8245 21313U 21313U 5 Damper motor 2-stage 750601U 750601U 6 Fuel lines Spec ...

  • Beckett CULUS CF1400 - page 23

    23 CF1400/CF2300 Burner Manual Figure 19b – Burner Replacement Parts (Continued) SK9936 SK9932 SK9930 14 13 12 10 20 11 21 22 23 15 16 17 18 19 ...

  • Beckett CULUS CF1400 - page 24

    USA: P .O. Box 1289 ● Elyria, Ohio 44036 Canada: R.W . Beckett Canada, Ltd. ● Unit #3, 430 Laird Road ● Guelph, Ontario N1G 3X7 www .beckettcorp.com Part Number 6104 BCF23 R14, Printed in the U.S.A. 08/10 The R. W . BECKETT CORPORA TION (“Beckett”) warrants to persons who purchase its “Products” from Beckett for resale, or for incorpo ...

Fabricante Beckett Categoría Burner

Los documentos del dispositivo Beckett CULUS CF1400 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Beckett
- manuales de instrucciones CULUS CF1400
- hojas de producto Beckett
- folletos informativos
- o etiquetas energéticas Beckett CULUS CF1400
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Beckett CULUS CF1400.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Beckett CULUS CF1400, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Beckett CULUS CF1400. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Beckett CULUS CF1400.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Beckett CULUS CF1400, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Beckett CULUS CF1400. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Beckett CULUS CF1400.

El manual de instrucciones completo de Beckett debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Beckett CULUS CF1400 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Beckett CULUS CF1400, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Beckett CULUS CF1400 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Beckett CULUS CF1400 - que deben facilitarnos los primeros pasos durante el uso de Beckett CULUS CF1400
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Beckett CULUS CF1400
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Beckett CULUS CF1400 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Beckett CULUS CF1400?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Beckett CULUS CF1400, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Beckett CULUS CF1400 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)