    TECHNICAL GUIDE AFFINITY SPLIT -SYSTEM HEA T PUMPS 18 SEER – R-410A MODELS: YZH024 THRU 060 (2 THRU 5 NOMINAL TONS) Due to continuous pr oduct improvement, spec ifications are subject to change without notice. Visit us on the web at www .york.com Additional rati ng information can be foun d at www .ari.org/aridirectory LISTED ISO 9001 Certified Q ...

  • York YZH024 THRU 060 - page 2

    2 Unitary Products Group 345094-YTG-D-0108 All dimensions are in inches. They are subject to change without notice. Certified dimensions wil l be provided upon request. Physical and Electrical Dat a MODEL YZH0241 1 YZH0361 1 YZ H0481 1 YZH0601 1 Unit Supply V oltage 208-230V , 1 φ, 60Hz Normal V oltage Range 1 187 to 252 Minimum Circuit Ampacity 1 ...

  • York YZH024 THRU 060 - page 3

    Unitary Products Group 3 345094-YTG-D-0108 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refri gerant for the condenser , the smallest evaporator and 15 feet of intercon- necting line tubing. 2. V erify the TXV and additional charge requ ired for specific evaporator coil in th e system using the above table. 3. Additional ...

  • York YZH024 THRU 060 - page 4

    4 Unitary Products Group 345094-YTG-D-0108 COOLING CAP ACITY - With A ir Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL W ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 18 SEER HP WITH MV - V ARIABLE SPEED YZH0241 1 MV12B 17 FC/MC43B 1 645 18.2 13.5 16.40 14.00 2 835 23.6 18.8 13.60 MV12D 24 FC/MC48D 1 645 18.5 14.0 17.00 14.50 ...

  • York YZH024 THRU 060 - page 5

    Unitary Products Group 5 345094-YTG-D-0108 COOLING CAP ACITY - With V a riable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE YZH0241 1 P(C,V)9*B12 FC/MC/PC43B 17 1 560 18.0 12.9 16.6O 14.10 2 820 23.6 18.9 13.30 YZH0361 1 P(C,V)8*B16 FC/MC/PC43B 17 1 750 24.6 18.1 1 ...

  • York YZH024 THRU 060 - page 6

    6 Unitary Products Group 345094-YTG-D-0108 YZH0481 1 P(C,V)8*C16 FC/MC/PC48C 21 1 880 33.0 23.4 16.3O 13.30 2 1500 46.0 34.6 1 1.70 P(C,V)8*C20 FC/MC/PC48C 21 1 1030 33.0 25.0 16.4O 13.40 2 1610 46.5 35.4 1 1.80 P(C,V)9*C16 FC/MC/PC48C 21 1 1090 34.0 26.0 16.9O 13.86 2 1600 46.0 35.2 1 1.60 P(C,V)9*C20 FC/MC/PC48C 21 1 1010 33.0 24.6 16.2O 13.20 2 ...

  • York YZH024 THRU 060 - page 7

    Unitary Products Group 7 345094-YTG-D-0108 ** Refer to Quick Selection Chart for specific furnace match-up. HEA TING CAP ACITY - With Air Handler UNIT MODEL AIR HANDLER MODEL COIL 1 MODEL W HEA TING ST AGE RA TED CFM NET MBH HSPF COP @ 47 47 OD 17 O D 18 SEER HP WITH MV - V ARIABLE SPEED YZH0241 1 MV12B FC/MC43B 17 1 645 19.3 - - 4.0 2 835 24.0 17. ...

  • York YZH024 THRU 060 - page 8

    8 Unitary Products Group 345094-YTG-D-0108 HEA TING CAP ACITY - With V a riable Speed F urnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W HEA TING ST AGE RA TED CFM NET MBH HSPF COP @ 47 47 OD 17 OD YZH0241 1 P(C,V)9*B12 FC/MC/PC43B 17 1 560 19.1 - - 3. 80 2 820 24.2 17.1 9.6 3. 90 2 560 23.8 15.0 9.3 3. 20 YZH0361 1 P(C,V)8*B16 FC/ ...

  • York YZH024 THRU 060 - page 9

    Unitary Products Group 9 345094-YTG-D-0108 YZH0361 1 P(C,V)8*C20 FC/MC62D 24 1 780 26.4 - - 4.00 2 1200 36.0 26.2 9.55 4 .20 2 780 36.0 23.8 9.35 3.20 P(C,V)9*C20 FC/MC62D 24 1 790 26.4 - - 4.00 2 1 195 36.0 26.0 9.55 4.20 2 790 36.0 24.0 9.35 3.40 P(C,V)9*D20 FC/MC62D 24 1 775 26.4 - - 4.00 2 1220 36.0 26.0 10 4.40 2 775 36.0 23.8 9.8 3.20 P(C,V)8 ...

  • York YZH024 THRU 060 - page 10

    10 Unitary Products Group 345094-YTG-D-0108 YZH0481 1 P(C,V)9*D20 FC/MC/PC60D 24 1 985 36.0 - - 3.80 2 1560 48.0 32.6 9.8 4. 00 2 985 39.0 25.6 9.5 3. 20 P(C,V)8*C20 FC/MC62D 24 1 1030 36.0 - - 3.80 2 1610 48.0 32.8 9.8 4. 00 2 1030 38.5 25.2 9.5 3. 20 P(C,V)9*C20 FC/MC62D 24 1 1010 36.0 - - 3.80 2 1580 48.0 32.6 9.3 3. 80 2 1010 38.0 25.0 9 3.00 P ...

  • York YZH024 THRU 060 - page 11

    Unitary Products Group 11 345094-YTG-D-0108 ACCESSORIES* TXV Kits - 1 TVM9 series thermal expansion valves precisely meter refrigerant for optimu m performance. Bonnet Sensor (2SB1370012 4) - The bonnet sensor is used to sense plenum temperature, and is optional with a gas or oil back-up heat source. Compatible on ly with 13 SEER an d higher heat p ...

  • York YZH024 THRU 060 - page 12

    12 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York YZH024 THRU 060 - page 13

    Unitary Products Group 13 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per degree belo ...

  • York YZH024 THRU 060 - page 14

    14 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York YZH024 THRU 060 - page 15

    Unitary Products Group 15 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per degree belo ...

  • York YZH024 THRU 060 - page 16

    16 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York YZH024 THRU 060 - page 17

    Unitary Products Group 17 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per degree belo ...

  • York YZH024 THRU 060 - page 18

    18 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York YZH024 THRU 060 - page 19

    Unitary Products Group 19 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per degree belo ...

  • York YZH024 THRU 060 - page 20

    20 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining the perfo rman ce with other indoor section. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0241 1 INDOOR COIL MODEL NO . FC/MC/PC48D + MV12D AIR TEMP . ENTERING OUTDOOR UNIT AIR TE ...

  • York YZH024 THRU 060 - page 21

    Unitary Products Group 21 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor section. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0241 1 INDOOR COIL MODEL NO. FC/MC/PC48D + MV12D AIR TEMP . ENTERING OUTDOOR UNIT AI ...

  • York YZH024 THRU 060 - page 22

    22 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0361 1 INDOOR COIL MODEL NO. FC/MC62D + MV1 2D AIR TEMP . ENTERING OUTDOOR UNIT AIR TEM ...

  • York YZH024 THRU 060 - page 23

    Unitary Products Group 23 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0361 1 INDOOR COIL MODEL NO. FC/MC62D + MV12D AIR TEMP . ENTERING OUTDOOR UNIT AIR ...

  • York YZH024 THRU 060 - page 24

    24 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0481 1 INDOOR COIL MODEL NO. FC/MC62D + MV2 0D AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP ...

  • York YZH024 THRU 060 - page 25

    Unitary Products Group 25 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0481 1 INDOOR COIL MODEL NO. FC/MC62D + MV20D AIR TEMP . ENTERING OUTDOOR UNIT AIR ...

  • York YZH024 THRU 060 - page 26

    26 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0601 1 INDOOR COIL MODEL NO. FC/MC62D + MV2 0D AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP ...

  • York YZH024 THRU 060 - page 27

    Unitary Products Group 27 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0601 1 INDOOR COIL MODEL NO. FC/MC62D + MV20D AIR TEMP . ENTERING OUTDOOR UNIT AIR ...

  • York YZH024 THRU 060 - page 28

    Subject to change without notice. Printe d in U.S.A. 345094-YTG-D-0108 Copyright © by Unitary Products Gr oup 2008. All ri ghts reserved. Supersedes: 345094-YTG-C-1007 Unitary 5005 Norman Product s Y ork OK Group Drive 73069 NOTES ...

Fabricante York Categoría Air Conditioner

Los documentos del dispositivo York YZH024 THRU 060 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos York
- manuales de instrucciones YZH024 THRU 060
- hojas de producto York
- folletos informativos
- o etiquetas energéticas York YZH024 THRU 060
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones York YZH024 THRU 060.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje York YZH024 THRU 060, instrucciones de servicio, instrucciones cortas o instrucciones de usuario York YZH024 THRU 060. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto York YZH024 THRU 060.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo York YZH024 THRU 060, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar York YZH024 THRU 060. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de York YZH024 THRU 060.

El manual de instrucciones completo de York debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual York YZH024 THRU 060 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice York YZH024 THRU 060, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de York YZH024 THRU 060 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo York YZH024 THRU 060 - que deben facilitarnos los primeros pasos durante el uso de York YZH024 THRU 060
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con York YZH024 THRU 060
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de York YZH024 THRU 060 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de York YZH024 THRU 060?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con York YZH024 THRU 060, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con York YZH024 THRU 060 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)