    TECHNICAL GUIDE AFFINITY SPLIT -SYSTEM HEA T PUMPS 18 SEER – R-410A MODELS: YZH024 THRU 060 (2 THRU 5 NOMINAL TONS) Due to continuous pr oduct improvement, spec ifications are subject to change without notice. Visit us on the web at www .york.com Additional rati ng information can be foun d at www .ari.org/aridirectory LISTED ISO 9001 Certified Q ...

  • York YZH024 THRU 060 - page 2

    2 Unitary Products Group 345094-YTG-D-0108 All dimensions are in inches. They are subject to change without notice. Certified dimensions wil l be provided upon request. Physical and Electrical Dat a MODEL YZH0241 1 YZH0361 1 YZ H0481 1 YZH0601 1 Unit Supply V oltage 208-230V , 1 φ, 60Hz Normal V oltage Range 1 187 to 252 Minimum Circuit Ampacity 1 ...

  • York YZH024 THRU 060 - page 3

    Unitary Products Group 3 345094-YTG-D-0108 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refri gerant for the condenser , the smallest evaporator and 15 feet of intercon- necting line tubing. 2. V erify the TXV and additional charge requ ired for specific evaporator coil in th e system using the above table. 3. Additional ...

  • York YZH024 THRU 060 - page 4

    4 Unitary Products Group 345094-YTG-D-0108 COOLING CAP ACITY - With A ir Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL W ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 18 SEER HP WITH MV - V ARIABLE SPEED YZH0241 1 MV12B 17 FC/MC43B 1 645 18.2 13.5 16.40 14.00 2 835 23.6 18.8 13.60 MV12D 24 FC/MC48D 1 645 18.5 14.0 17.00 14.50 ...

  • York YZH024 THRU 060 - page 5

    Unitary Products Group 5 345094-YTG-D-0108 COOLING CAP ACITY - With V a riable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE YZH0241 1 P(C,V)9*B12 FC/MC/PC43B 17 1 560 18.0 12.9 16.6O 14.10 2 820 23.6 18.9 13.30 YZH0361 1 P(C,V)8*B16 FC/MC/PC43B 17 1 750 24.6 18.1 1 ...

  • York YZH024 THRU 060 - page 6

    6 Unitary Products Group 345094-YTG-D-0108 YZH0481 1 P(C,V)8*C16 FC/MC/PC48C 21 1 880 33.0 23.4 16.3O 13.30 2 1500 46.0 34.6 1 1.70 P(C,V)8*C20 FC/MC/PC48C 21 1 1030 33.0 25.0 16.4O 13.40 2 1610 46.5 35.4 1 1.80 P(C,V)9*C16 FC/MC/PC48C 21 1 1090 34.0 26.0 16.9O 13.86 2 1600 46.0 35.2 1 1.60 P(C,V)9*C20 FC/MC/PC48C 21 1 1010 33.0 24.6 16.2O 13.20 2 ...

  • York YZH024 THRU 060 - page 7

    Unitary Products Group 7 345094-YTG-D-0108 ** Refer to Quick Selection Chart for specific furnace match-up. HEA TING CAP ACITY - With Air Handler UNIT MODEL AIR HANDLER MODEL COIL 1 MODEL W HEA TING ST AGE RA TED CFM NET MBH HSPF COP @ 47 47 OD 17 O D 18 SEER HP WITH MV - V ARIABLE SPEED YZH0241 1 MV12B FC/MC43B 17 1 645 19.3 - - 4.0 2 835 24.0 17. ...

  • York YZH024 THRU 060 - page 8

    8 Unitary Products Group 345094-YTG-D-0108 HEA TING CAP ACITY - With V a riable Speed F urnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W HEA TING ST AGE RA TED CFM NET MBH HSPF COP @ 47 47 OD 17 OD YZH0241 1 P(C,V)9*B12 FC/MC/PC43B 17 1 560 19.1 - - 3. 80 2 820 24.2 17.1 9.6 3. 90 2 560 23.8 15.0 9.3 3. 20 YZH0361 1 P(C,V)8*B16 FC/ ...

  • York YZH024 THRU 060 - page 9

    Unitary Products Group 9 345094-YTG-D-0108 YZH0361 1 P(C,V)8*C20 FC/MC62D 24 1 780 26.4 - - 4.00 2 1200 36.0 26.2 9.55 4 .20 2 780 36.0 23.8 9.35 3.20 P(C,V)9*C20 FC/MC62D 24 1 790 26.4 - - 4.00 2 1 195 36.0 26.0 9.55 4.20 2 790 36.0 24.0 9.35 3.40 P(C,V)9*D20 FC/MC62D 24 1 775 26.4 - - 4.00 2 1220 36.0 26.0 10 4.40 2 775 36.0 23.8 9.8 3.20 P(C,V)8 ...

  • York YZH024 THRU 060 - page 10

    10 Unitary Products Group 345094-YTG-D-0108 YZH0481 1 P(C,V)9*D20 FC/MC/PC60D 24 1 985 36.0 - - 3.80 2 1560 48.0 32.6 9.8 4. 00 2 985 39.0 25.6 9.5 3. 20 P(C,V)8*C20 FC/MC62D 24 1 1030 36.0 - - 3.80 2 1610 48.0 32.8 9.8 4. 00 2 1030 38.5 25.2 9.5 3. 20 P(C,V)9*C20 FC/MC62D 24 1 1010 36.0 - - 3.80 2 1580 48.0 32.6 9.3 3. 80 2 1010 38.0 25.0 9 3.00 P ...

  • York YZH024 THRU 060 - page 11

    Unitary Products Group 11 345094-YTG-D-0108 ACCESSORIES* TXV Kits - 1 TVM9 series thermal expansion valves precisely meter refrigerant for optimu m performance. Bonnet Sensor (2SB1370012 4) - The bonnet sensor is used to sense plenum temperature, and is optional with a gas or oil back-up heat source. Compatible on ly with 13 SEER an d higher heat p ...

  • York YZH024 THRU 060 - page 12

    12 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York YZH024 THRU 060 - page 13

    Unitary Products Group 13 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per degree belo ...

  • York YZH024 THRU 060 - page 14

    14 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York YZH024 THRU 060 - page 15

    Unitary Products Group 15 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per degree belo ...

  • York YZH024 THRU 060 - page 16

    16 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York YZH024 THRU 060 - page 17

    Unitary Products Group 17 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per degree belo ...

  • York YZH024 THRU 060 - page 18

    18 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: For dry bulb temperatures dif f erent than those listed (bet ween 73-87 F), sensible capacity increa se s by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York YZH024 THRU 060 - page 19

    Unitary Products Group 19 345094-YTG-D-0108 Multipliers for determining the performance with ot her indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decre ases by 1060 BTUH per 10 00 CFM per degree belo ...

  • York YZH024 THRU 060 - page 20

    20 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining the perfo rman ce with other indoor section. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0241 1 INDOOR COIL MODEL NO . FC/MC/PC48D + MV12D AIR TEMP . ENTERING OUTDOOR UNIT AIR TE ...

  • York YZH024 THRU 060 - page 21

    Unitary Products Group 21 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor section. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0241 1 INDOOR COIL MODEL NO. FC/MC/PC48D + MV12D AIR TEMP . ENTERING OUTDOOR UNIT AI ...

  • York YZH024 THRU 060 - page 22

    22 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining th e performance with other indoor sec tions . NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0361 1 INDOOR COIL MODEL NO. FC/MC62D + MV1 2D AIR TEMP . ENTERING OUTDOOR UNIT AIR TEM ...

  • York YZH024 THRU 060 - page 23

    Unitary Products Group 23 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0361 1 INDOOR COIL MODEL NO. FC/MC62D + MV12D AIR TEMP . ENTERING OUTDOOR UNIT AIR ...

  • York YZH024 THRU 060 - page 24

    24 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0481 1 INDOOR COIL MODEL NO. FC/MC62D + MV2 0D AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP ...

  • York YZH024 THRU 060 - page 25

    Unitary Products Group 25 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0481 1 INDOOR COIL MODEL NO. FC/MC62D + MV20D AIR TEMP . ENTERING OUTDOOR UNIT AIR ...

  • York YZH024 THRU 060 - page 26

    26 Unitary Products Group 345094-YTG-D-0108 Multipliers for determining the perfo rman ce with other indoor sections. NOTE: KW RA TING IS FOR OUT DOOR AND INDOOR UNITS. LOW CFM HEA TING PERFORMA NCE DA T A - LOW CFM 1-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0601 1 INDOOR COIL MODEL NO. FC/MC62D + MV2 0D AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP ...

  • York YZH024 THRU 060 - page 27

    Unitary Products Group 27 345094-YTG-D-0108 Multipliers for de termining the performa nce with other i ndoor sections. NOTE: KW RA TING IS FOR OU TDOOR AND INDOOR UNITS. HIGH CFM HEA TIN G PERFOR MA NCE DA T A - HIGH CFM 2-ST AGE OPERA TION OUTDOOR UNIT MODEL NO. YZH0601 1 INDOOR COIL MODEL NO. FC/MC62D + MV20D AIR TEMP . ENTERING OUTDOOR UNIT AIR ...

  • York YZH024 THRU 060 - page 28

    Subject to change without notice. Printe d in U.S.A. 345094-YTG-D-0108 Copyright © by Unitary Products Gr oup 2008. All ri ghts reserved. Supersedes: 345094-YTG-C-1007 Unitary 5005 Norman Product s Y ork OK Group Drive 73069 NOTES ...

メーカー York カテゴリー Air Conditioner

York YZH024 THRU 060のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- YZH024 THRU 060の取扱説明書
- Yorkの製品カード
- パンフレット
- またはYork YZH024 THRU 060の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、York YZH024 THRU 060の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、York YZH024 THRU 060の取り付け説明書、サービスマニュアル、簡易説明書、またはYork YZH024 THRU 060のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、York YZH024 THRU 060の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

York YZH024 THRU 060デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがYork YZH024 THRU 060を使用するのを助ける技術的文書のことです。説明書は通常、全てのYork YZH024 THRU 060ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Yorkの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. York YZH024 THRU 060の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははYork YZH024 THRU 060の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。York YZH024 THRU 060に関してこのドキュメントで見つけることができる全てのヒントの目次
3. York YZH024 THRU 060デバイスの基本機能を使うにあたってのヒント。 York YZH024 THRU 060のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。York YZH024 THRU 060に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるYork YZH024 THRU 060のメーカー/サービスへの連絡先に関する情報。

York YZH024 THRU 060についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもYork YZH024 THRU 060の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがYork YZH024 THRU 060で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)