Manual de instrucciones Carrier 13 50XP

24 de páginas 1.35 mb
Descargar

Pasar a la página of 24

Summary
  • Carrier 13 50XP - page 1

    PERFORMANCE™ 13 50XP SINGLE-PACKAGED ELECTRIC COOLING UNITS WITH PURON® (R-410A) REFRIGERANT 2 to 5 Nominal Tons Product Data UNIT 50XP Single-Packaged Products with Energy-Sa ving Features and Puron® refrigerant. • Low Sound Le vels • 13 SEER • V ariable Speed Blo wer-Standard • Factory Installed TXV Features/Bene fi ts One-piece cool ...

  • Carrier 13 50XP - page 2

    2 50XP cooling unit that is pre-wired, pre- piped, and pre-charged for minimum installation expense. 50XP units are av ailable in a variety of standard cooling sizes with voltage options to meet residential and light commercial requirements. Units are light weight, and install easily on a rooftop or at ground-le vel. The hightech, composite base pa ...

  • Carrier 13 50XP - page 3

    3 50XP Model number nomenc lature ARI* capacities COOLING CAPACITIES AND EFFICIENCIES 50XP 024 3 UNIT 50XP NOMINAL T ONS ST ANDARD CFM NET COOLING CAP ACITIES (Btuh) EER@A** SEER† SOUND RA TINGS‡ (dB) 024 2 800 24,000 11.0 13.0 72 030 2-1/2 1000 28,800 11.0 13.0 72 036 3 1100 36,000 11.0 13.0 72 042 3-1/2 1400 41,000 11.0 13.0 72 048 4 1450 45, ...

  • Carrier 13 50XP - page 4

    4 50XP OUTDOOR SOUND: OCT A VE B AND D A T A—DECIBELS (Lw(A)) Ph ysical data * Required fi lter siz es shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling air fl ow or the heating air fl ow v elocity of 300 ft/min f or throwa way type or 450 ft/min f or high-capacity type. Air fi lter pressu ...

  • Carrier 13 50XP - page 5

    5 50XP F actory-installed options Coil options include T in-Plated* indoor hairpins, copper/ copper and vinyl-coated construction for refrigerant coils. Units are shipped standard with copper tube/aluminum fi n construction. See model number nomenclature for coil options. *T in-Plated indoor coils are built with special hairpins that are designed ...

  • Carrier 13 50XP - page 6

    6 50XP ECONOMIZER FIL TER RACK MANUAL OUTSIDE AIR DAMPER DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT P ANEL 7 50XP ...

  • Carrier 13 50XP - page 7

    7 50XP Base unit dimensions—50XP024-036 UNIT ELECTRICAL CHARA CTERISTICS UNIT WEIGHT UNIT HEIGHT in. [mm] “A” CENTER OF GRA VITY in. [mm] lb kg X Y Z 50XP024 208/230-1-60 343 156 39.02 [991.1] 20 [508] 19.3 [489] 17.6 [447] 50XP030 208/230-1-60 343 156 39.02 [991.1] 20 [508] 19.3 [489] 17.6 [447] 50XP036 208/230-1-60, 208/230-3-60 366 166 41. ...

  • Carrier 13 50XP - page 8

    8 50XP Base unit dimensions—50XP042-060 UNIT ELECTRICAL CHARA CTERISTICS UNIT WEIGHT UNIT HEIGHT in. [mm] “A” CENTER OF GRA VITY in. [mm] lb kg X Y Z 50XP042 208/230-1-60, 208/230-3-60 433 197 42.98 [1091.7] 21 [533.4] 20.5 [520.2] 16.6 [421.6] 50XP048 208/230-1-60, 208/230-3-60 456 207 44.98 [1142.5] 19.5 [495.3] 17.6 [447.6] 18.0 [457.2] 50 ...

  • Carrier 13 50XP - page 9

    9 50XP Accessory dimensions UNIT SIZE ODS CA T ALOG NUMBER A in. [mm] B in. [mm] C in. [mm] D in. [mm] 50XP024-036 CPRFCURB006A00 8 [203] 11 [279] 16-1/2 [419] 28-3/4 [730] CPRFCURB007A00 14 [356] 11 [279] 16-1/2 [419] 28-3/4 [730] 50XP042-060 CPRFCURB008A00 8 [203] 16-3/16 [411] 17-3/8 [441] 40-1/4 [1022] CPRFCURB009A00 14 [356] 16-3/16 [411] 17-3 ...

  • Carrier 13 50XP - page 10

    10 50XP I Determine cooling and heating requirements at design conditions: Given: Required Cooling Capacity (TC) . . . . . . . . . . 34,500 Btuh Sensible Heat Capacity (SHC) . . . . . . . . . . . . 26,000 Btuh Required Heating Capacity . . . . . . . . . . . . . . 15,000 Btuh Condenser Entering Air Temperature . . . . . . . . . . . . 95°F Indoor-Ai ...

  • Carrier 13 50XP - page 11

    11 50XP P erf ormance data- Standard ECM Indoor Motor COOLING CAP A CITIES See Legend and Notes on page 13. 50XP024 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air—CFM/BF 800/0.026 900/0.032 1000/0.04 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC SHC kW 24.0 24.5 26.5 29.1 24.6 25.1 27.1 ...

  • Carrier 13 50XP - page 12

    12 50XP P erf ormance data (cont)- Standar d ECM Indoor Motor COOLING CAP A CITIES See Legend and Notes on page 13. 50XP036 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air—CFM/BF 1100/0.06 1225/0.07 1400/0.08 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC 36.2 36.8 39.7 43.8 36.9 37.4 40.3 ...

  • Carrier 13 50XP - page 13

    13 50XP P erf ormance data (cont)- Standar d ECM Indoor Motor COOLING CAP A CITIES 50XP048 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air—CFM/BF 1260/0.06 1400/0.06 1600/0.08 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC 45.0 45.8 49.6 54.7 46.7 47.3 51.2 56.3 48.1 48.7 52.5 57.8 SHC 39. ...

  • Carrier 13 50XP - page 14

    14 50XP P erf ormance data (cont) ECONOMIZER 1-in. FIL TER PRESSURE DR OP (in. wg) MUL TIPLICA TION F A CTORS Example: 15.0 kW (at 240v) heater on 208 v = 15.0 (.75 mult f actor) = 11.25 capacity at 208 v UNIT50XP PRESSURE DROP 024-036 0.20 042-060 0.25 HEA TER kW RA TING VO LT AG E DISTRIBUTION MUL TIPLICA TION F ACT OR 240 200 208 230 240 .69 .75 ...

  • Carrier 13 50XP - page 15

    15 50XP 50XP ECM DR Y COIL AIRFLO W–SMALL CABINET 50XP ECM DR Y COIL AIRFLO W–LARGE CABINET 50XP ECM WET COIL PRESSURE DROP UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC PRESSURE RANGE 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0 024 COOLING 800 725 — 885 805 730 990 9 ...

  • Carrier 13 50XP - page 16

    16 50XP INDOOR THERMOST A T DISCONNECT PER NEC* FROM POWER SOURCE RETURN AIR T OP CO VER *NEC - NA TIONAL ELECTRICAL CODE Typical piping and wiring ROOF RETURN-AIR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BO X (FIELD-SUPPLIED) SUPPL Y -AIR FLEXIBLE DUCT ROOF-MOUNTING CURB C00023 C00063 50XP ...

  • Carrier 13 50XP - page 17

    17 50XP Condensate trap — A 2-in. condensate trap must be fi eld supplied. Ductwork — Secure do wn fl ow dischar ge ductwork to roof curb . For horizontal dischar ge applications, attach ductwork to unit with fl anges. T o con vert a unit to down fl o w discharge — Units are equipped with factory-installed inserts in the do wn fl ow open ...

  • Carrier 13 50XP - page 18

    18 50XP Electrical data UNIT SIZE 50XP V -PH-Hz V O LTAG E RANGE COMPRESSOR OUTDOOR F AN MOT OR INDOOR F AN MOT OR ELECTRIC HEA T PO WER SUPPL Y Min Max RLA LRA FLA FLA Nominal kW* FLA UNIT MCA MAX FUSE or CKT . BKR. MOCP 024 208/230-1-60 187 253 13.5 61.0 0.8 4.3 —/— 3.8/5 5.4/7.2 7.5/10 —/— 18.1/20.8 26/30 36.1/41.7 22.0/22.0 27.9/31.4 37 ...

  • Carrier 13 50XP - page 19

    19 50XP 4 5 2=5v 4 5 7=7v 4 5 5=2v LEGEND FLA — Full Load Amps LRA — Lock ed Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Ov ercurrent Protection RLA — Rated Load Amps NO TES: 1. In compliance with NEC (National Electr ical Code) requirements for multimotor and combination load equipment (refer to NEC Ar ticles 430 and 440), the o ...

  • Carrier 13 50XP - page 20

    20 50XP T ypical wiring schematic— 208/230-1-60 C01037 ...

  • Carrier 13 50XP - page 21

    21 50XP T ypical wiring schematic— 208/230-3-60 C03026 ...

  • Carrier 13 50XP - page 22

    22 50XP Operating sequence Cooling — When the system thermostat calls for cooling, 24 V is supplied to the “Y” and “G” terminals of the thermostat. This completes the circuit to the contactor coil (C) and indoor (e vaporator) fan time delay relay (TDR). The normally open contacts of C close and complete the circuit to compressor motor (CO ...

  • Carrier 13 50XP - page 23

    23 50XP Packaged Electric Cooling Units Constant Volume Application HVAC Guide Specifications Size Range: 2 to 5 Tons, Nominal Cooling Carrier Model Number: 50XP Part 1—General SYSTEM DESCRIPTION Outdoor rooftop or ground mounted, electric cooling unit utilizing a hermetic compressor for cooling duty and optional electric heating. Unit shall disc ...

  • Carrier 13 50XP - page 24

    Copyright 2005 Carrier Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 Printed in U.S.A. edition date: 10/05 Manufacturer reserves the right to change, at any time, specifications or designs without notice and obligations Catalog No: 50XP-4PD Replaces: 50XP-3PD L. Grille 1. Louvered Grille: Louvered grille shall be standard on all units. M. ...

Fabricante Carrier Categoría Fan

Los documentos del dispositivo Carrier 13 50XP que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Carrier
- manuales de instrucciones 13 50XP
- hojas de producto Carrier
- folletos informativos
- o etiquetas energéticas Carrier 13 50XP
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Carrier 13 50XP.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Carrier 13 50XP, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Carrier 13 50XP. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Carrier 13 50XP.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Carrier 13 50XP, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Carrier 13 50XP. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Carrier 13 50XP.

El manual de instrucciones completo de Carrier debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Carrier 13 50XP - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Carrier 13 50XP, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Carrier 13 50XP que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Carrier 13 50XP - que deben facilitarnos los primeros pasos durante el uso de Carrier 13 50XP
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Carrier 13 50XP
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Carrier 13 50XP en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Carrier 13 50XP?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Carrier 13 50XP, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Carrier 13 50XP probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)