    PERFORMANCE™ 13 50XP SINGLE-PACKAGED ELECTRIC COOLING UNITS WITH PURON® (R-410A) REFRIGERANT 2 to 5 Nominal Tons Product Data UNIT 50XP Single-Packaged Products with Energy-Sa ving Features and Puron® refrigerant. • Low Sound Le vels • 13 SEER • V ariable Speed Blo wer-Standard • Factory Installed TXV Features/Bene fi ts One-piece cool ...

  • Carrier 13 50XP - page 2

    2 50XP cooling unit that is pre-wired, pre- piped, and pre-charged for minimum installation expense. 50XP units are av ailable in a variety of standard cooling sizes with voltage options to meet residential and light commercial requirements. Units are light weight, and install easily on a rooftop or at ground-le vel. The hightech, composite base pa ...

  • Carrier 13 50XP - page 3

    3 50XP Model number nomenc lature ARI* capacities COOLING CAPACITIES AND EFFICIENCIES 50XP 024 3 UNIT 50XP NOMINAL T ONS ST ANDARD CFM NET COOLING CAP ACITIES (Btuh) EER@A** SEER† SOUND RA TINGS‡ (dB) 024 2 800 24,000 11.0 13.0 72 030 2-1/2 1000 28,800 11.0 13.0 72 036 3 1100 36,000 11.0 13.0 72 042 3-1/2 1400 41,000 11.0 13.0 72 048 4 1450 45, ...

  • Carrier 13 50XP - page 4

    4 50XP OUTDOOR SOUND: OCT A VE B AND D A T A—DECIBELS (Lw(A)) Ph ysical data * Required fi lter siz es shown are based on the larger of the ARI (Air Conditioning & Refrigeration Institute) rated cooling air fl ow or the heating air fl ow v elocity of 300 ft/min f or throwa way type or 450 ft/min f or high-capacity type. Air fi lter pressu ...

  • Carrier 13 50XP - page 5

    5 50XP F actory-installed options Coil options include T in-Plated* indoor hairpins, copper/ copper and vinyl-coated construction for refrigerant coils. Units are shipped standard with copper tube/aluminum fi n construction. See model number nomenclature for coil options. *T in-Plated indoor coils are built with special hairpins that are designed ...

  • Carrier 13 50XP - page 6

    6 50XP ECONOMIZER FIL TER RACK MANUAL OUTSIDE AIR DAMPER DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT P ANEL 7 50XP ...

  • Carrier 13 50XP - page 7

    7 50XP Base unit dimensions—50XP024-036 UNIT ELECTRICAL CHARA CTERISTICS UNIT WEIGHT UNIT HEIGHT in. [mm] “A” CENTER OF GRA VITY in. [mm] lb kg X Y Z 50XP024 208/230-1-60 343 156 39.02 [991.1] 20 [508] 19.3 [489] 17.6 [447] 50XP030 208/230-1-60 343 156 39.02 [991.1] 20 [508] 19.3 [489] 17.6 [447] 50XP036 208/230-1-60, 208/230-3-60 366 166 41. ...

  • Carrier 13 50XP - page 8

    8 50XP Base unit dimensions—50XP042-060 UNIT ELECTRICAL CHARA CTERISTICS UNIT WEIGHT UNIT HEIGHT in. [mm] “A” CENTER OF GRA VITY in. [mm] lb kg X Y Z 50XP042 208/230-1-60, 208/230-3-60 433 197 42.98 [1091.7] 21 [533.4] 20.5 [520.2] 16.6 [421.6] 50XP048 208/230-1-60, 208/230-3-60 456 207 44.98 [1142.5] 19.5 [495.3] 17.6 [447.6] 18.0 [457.2] 50 ...

  • Carrier 13 50XP - page 9

    9 50XP Accessory dimensions UNIT SIZE ODS CA T ALOG NUMBER A in. [mm] B in. [mm] C in. [mm] D in. [mm] 50XP024-036 CPRFCURB006A00 8 [203] 11 [279] 16-1/2 [419] 28-3/4 [730] CPRFCURB007A00 14 [356] 11 [279] 16-1/2 [419] 28-3/4 [730] 50XP042-060 CPRFCURB008A00 8 [203] 16-3/16 [411] 17-3/8 [441] 40-1/4 [1022] CPRFCURB009A00 14 [356] 16-3/16 [411] 17-3 ...

  • Carrier 13 50XP - page 10

    10 50XP I Determine cooling and heating requirements at design conditions: Given: Required Cooling Capacity (TC) . . . . . . . . . . 34,500 Btuh Sensible Heat Capacity (SHC) . . . . . . . . . . . . 26,000 Btuh Required Heating Capacity . . . . . . . . . . . . . . 15,000 Btuh Condenser Entering Air Temperature . . . . . . . . . . . . 95°F Indoor-Ai ...

  • Carrier 13 50XP - page 11

    11 50XP P erf ormance data- Standard ECM Indoor Motor COOLING CAP A CITIES See Legend and Notes on page 13. 50XP024 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air—CFM/BF 800/0.026 900/0.032 1000/0.04 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC SHC kW 24.0 24.5 26.5 29.1 24.6 25.1 27.1 ...

  • Carrier 13 50XP - page 12

    12 50XP P erf ormance data (cont)- Standar d ECM Indoor Motor COOLING CAP A CITIES See Legend and Notes on page 13. 50XP036 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air—CFM/BF 1100/0.06 1225/0.07 1400/0.08 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC 36.2 36.8 39.7 43.8 36.9 37.4 40.3 ...

  • Carrier 13 50XP - page 13

    13 50XP P erf ormance data (cont)- Standar d ECM Indoor Motor COOLING CAP A CITIES 50XP048 COOLING PERFORMANCE TABLE Temp (F) Outdoor Air Entering Condenser Evaporator Air—CFM/BF 1260/0.06 1400/0.06 1600/0.08 Evaporator Air — Ewb (F) 62 63* 67 72 62 63* 67 72 62 63* 67 72 75 TC 45.0 45.8 49.6 54.7 46.7 47.3 51.2 56.3 48.1 48.7 52.5 57.8 SHC 39. ...

  • Carrier 13 50XP - page 14

    14 50XP P erf ormance data (cont) ECONOMIZER 1-in. FIL TER PRESSURE DR OP (in. wg) MUL TIPLICA TION F A CTORS Example: 15.0 kW (at 240v) heater on 208 v = 15.0 (.75 mult f actor) = 11.25 capacity at 208 v UNIT50XP PRESSURE DROP 024-036 0.20 042-060 0.25 HEA TER kW RA TING VO LT AG E DISTRIBUTION MUL TIPLICA TION F ACT OR 240 200 208 230 240 .69 .75 ...

  • Carrier 13 50XP - page 15

    15 50XP 50XP ECM DR Y COIL AIRFLO W–SMALL CABINET 50XP ECM DR Y COIL AIRFLO W–LARGE CABINET 50XP ECM WET COIL PRESSURE DROP UNIT SIZE CFM ADJUST PIN SELECT LO PIN NOM PIN HI PIN EXTERNAL STATIC PRESSURE RANGE 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0 0.0–0.39 0.4–0.69 0.7–1.0 024 COOLING 800 725 — 885 805 730 990 9 ...

  • Carrier 13 50XP - page 16

    16 50XP INDOOR THERMOST A T DISCONNECT PER NEC* FROM POWER SOURCE RETURN AIR T OP CO VER *NEC - NA TIONAL ELECTRICAL CODE Typical piping and wiring ROOF RETURN-AIR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BO X (FIELD-SUPPLIED) SUPPL Y -AIR FLEXIBLE DUCT ROOF-MOUNTING CURB C00023 C00063 50XP ...

  • Carrier 13 50XP - page 17

    17 50XP Condensate trap — A 2-in. condensate trap must be fi eld supplied. Ductwork — Secure do wn fl ow dischar ge ductwork to roof curb . For horizontal dischar ge applications, attach ductwork to unit with fl anges. T o con vert a unit to down fl o w discharge — Units are equipped with factory-installed inserts in the do wn fl ow open ...

  • Carrier 13 50XP - page 18

    18 50XP Electrical data UNIT SIZE 50XP V -PH-Hz V O LTAG E RANGE COMPRESSOR OUTDOOR F AN MOT OR INDOOR F AN MOT OR ELECTRIC HEA T PO WER SUPPL Y Min Max RLA LRA FLA FLA Nominal kW* FLA UNIT MCA MAX FUSE or CKT . BKR. MOCP 024 208/230-1-60 187 253 13.5 61.0 0.8 4.3 —/— 3.8/5 5.4/7.2 7.5/10 —/— 18.1/20.8 26/30 36.1/41.7 22.0/22.0 27.9/31.4 37 ...

  • Carrier 13 50XP - page 19

    19 50XP 4 5 2=5v 4 5 7=7v 4 5 5=2v LEGEND FLA — Full Load Amps LRA — Lock ed Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Ov ercurrent Protection RLA — Rated Load Amps NO TES: 1. In compliance with NEC (National Electr ical Code) requirements for multimotor and combination load equipment (refer to NEC Ar ticles 430 and 440), the o ...

  • Carrier 13 50XP - page 20

    20 50XP T ypical wiring schematic— 208/230-1-60 C01037 ...

  • Carrier 13 50XP - page 21

    21 50XP T ypical wiring schematic— 208/230-3-60 C03026 ...

  • Carrier 13 50XP - page 22

    22 50XP Operating sequence Cooling — When the system thermostat calls for cooling, 24 V is supplied to the “Y” and “G” terminals of the thermostat. This completes the circuit to the contactor coil (C) and indoor (e vaporator) fan time delay relay (TDR). The normally open contacts of C close and complete the circuit to compressor motor (CO ...

  • Carrier 13 50XP - page 23

    23 50XP Packaged Electric Cooling Units Constant Volume Application HVAC Guide Specifications Size Range: 2 to 5 Tons, Nominal Cooling Carrier Model Number: 50XP Part 1—General SYSTEM DESCRIPTION Outdoor rooftop or ground mounted, electric cooling unit utilizing a hermetic compressor for cooling duty and optional electric heating. Unit shall disc ...

  • Carrier 13 50XP - page 24

    Copyright 2005 Carrier Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 Printed in U.S.A. edition date: 10/05 Manufacturer reserves the right to change, at any time, specifications or designs without notice and obligations Catalog No: 50XP-4PD Replaces: 50XP-3PD L. Grille 1. Louvered Grille: Louvered grille shall be standard on all units. M. ...

Fabricant Carrier Catégorie Fan

Les documents que nous recevons du fabricant de l'appareilCarrier 13 50XP peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Carrier
- manuels d’utilisations 13 50XP
- fiches produit Carrier
- dépliants
- ou étiquettes-énergie Carrier 13 50XP
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Carrier 13 50XP.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Carrier 13 50XP, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Carrier 13 50XP. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Carrier 13 50XP.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Carrier 13 50XP, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Carrier 13 50XP par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Carrier 13 50XP.

Le manuel d’utilisation complet Carrier, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Carrier 13 50XP - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Carrier 13 50XP, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lCarrier 13 50XP qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Carrier 13 50XP - qui devraient nous aider dans les premières étapes lors de l'utilisation Carrier 13 50XP
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Carrier 13 50XP
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Carrier 13 50XP dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Carrier 13 50XP?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Carrier 13 50XP, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Carrier 13 50XP il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)