Goodman Mfg GPC14H - page 1
SS-GPC14H www .goodmanmfg.com 7/11 Supersedes 6/11 Product Featur es • Energ y-efcientcompressor withinternalrelief valve • EEMblowermotor • Quiethorizontaldischarge • Coppertube/aluminumncoil • T otall yenclosed,permanentlylubricated condenserfanmotor ? ...
-
Goodman Mfg GPC14H - page 2
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 2 www .goodmanmfg.com SS-GPC14H n omenclA TURe Brand Engineering G Goodman Minor Revision or Distinctions™ Product Category Engineering P Packaged Unit Major Revision Type Voltage Designator H Heat Pump 1 208-230/1/60 C Air Conditioner 3 208-230/3/60 4 460/3/60 Efficiency Refrigerant 13 13 SEER ...
-
Goodman Mfg GPC14H - page 3
P roduct S Pecifica tionS P roduct S Pecifica tionS SS-GPC14H www .goodmanmfg.com 3 S Pecifica tionS Models GPC14 24H41AC GPC14 30H41AA GPC14 30H41AC GPC14 36H41AA GPC14 36H41AC Cooling Cap acity Cooling Capacity (BTU/h) 24,600 28,400 28,400 35,600 35,600 Sensible BTU/h 18,200 21,600 21,600 27,100 27,100 SEER / EER 14.5 / 12.1 14.0 / 12.1 14.0 / 12 ...
-
Goodman Mfg GPC14H - page 4
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 4 www .goodmanmfg.com SS-GPC14H S PeciFicA TionS Models GPC14 42H41AA GPC14 42H41AC GPC14 48H41AA GPC14 48H41AC GPC14 60H41A* Cooling Cap acity Cooling Capacity (BTU/h) 40,000 40,000 46,500 46,500 57,500 Sensible BTU/h 30,400 30,400 35,300 35,300 40,800 SEER / EER 14.2 / 12.0 14.2 / 12.0 14.5 / 12 ...
-
Goodman Mfg GPC14H - page 5
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 5 A iRFl ow D A T A Model Speed V ol ts E.S.P . (In. of H₂O) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 GPC14 24H41** T1 230 CFM 934 759 755 638 581 489 - - 95 77 76 73 83 90 - - T2, T3 230 CFM 990 837 801 744 696 652 601 - 107 94 105 110 119 133 14 ...
-
Goodman Mfg GPC14H - page 6
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 6 www .goodmanmfg.com SS-GPC14H e xP AnDeD c ooling D A TA — gPc1 424H4 1Ac Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 920 MBh 24.1 25.0 27.4 - 23.5 24.4 26.7 - 23. ...
-
Goodman Mfg GPC14H - page 7
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 7 e xP AnDeD c ooling D A TA — gPc1 424H4 1Ac ( conT .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 920 MBh 25.0 25.5 27.2 29.1 24.4 24 ...
-
Goodman Mfg GPC14H - page 8
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 8 www .goodmanmfg.com SS-GPC14H e xP AnDeD c ooling D A TA — gPc1 430H4 1AA Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1180 MBh 27.8 28.8 31.6 - 27.2 28.2 30.9 - 26 ...
-
Goodman Mfg GPC14H - page 9
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 9 e xP AnDeD c ooling D A TA — gPc1 430H4 1AA ( conT .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1180 MBh 28.8 29.4 31.4 33.6 28.1 2 ...
-
Goodman Mfg GPC14H - page 10
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 10 www .goodmanmfg.com SS-GPC14H e xP AnDeD c ooling D A TA — gPc1 430H4 1Ac Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1145 MBh 27.8 28.8 31.6 - 27.2 28.2 30.9 - 2 ...
-
Goodman Mfg GPC14H - page 11
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 11 e xP AnDeD c ooling D A TA — gPc1 430H4 1Ac ( conT .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1145 MBh 28.8 29.4 31.4 33.6 28.1 ...
-
Goodman Mfg GPC14H - page 12
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 12 www .goodmanmfg.com SS-GPC14H e xP AnDeD c ooling D A TA — gPc1 436H4 1AA Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1349 MBh 34.9 36.2 39.6 - 34.1 35.3 38.7 - 3 ...
-
Goodman Mfg GPC14H - page 13
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 13 e xP AnDeD c ooling D A TA — gPc1 436H4 1AA ( conT .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1349 MBh 36.1 36.9 39.4 42.1 35.3 ...
-
Goodman Mfg GPC14H - page 14
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 14 www .goodmanmfg.com SS-GPC14H e xP AnDeD c ooling D A TA — gPc1 436H4 1Ac Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1350 MBh 35.8 37.1 40.7 - 35.0 36.3 39.8 - 3 ...
-
Goodman Mfg GPC14H - page 15
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 15 e xP AnDeD c ooling D A TA — gPc1 436H4 1Ac ( conT .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1350 MBh 37.1 37.9 40.5 43.3 36.2 ...
-
Goodman Mfg GPC14H - page 16
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 16 www .goodmanmfg.com SS-GPC14H Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1461 MBh 39.7 41.1 45.1 - 38.8 40.2 44.0 - 37.8 39.2 43.0 - 36.9 38.3 41.9 - 35.1 36.4 39. ...
-
Goodman Mfg GPC14H - page 17
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 17 Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1461 MBh 41.1 42.0 44.8 47.9 40.1 41.0 43.8 46.8 39.2 40.0 42.8 45.7 38.2 39.0 41.7 44.6 3 ...
-
Goodman Mfg GPC14H - page 18
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 18 www .goodmanmfg.com SS-GPC14H e xP AnDeD c ooling D A TA — gPc1 442H41A c Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1432 MBh 39.8 41.3 45.2 - 38.9 40.3 44.1 - 3 ...
-
Goodman Mfg GPC14H - page 19
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 19 e xP AnDeD c ooling D A TA — gPc1 442H41A c ( conT .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1432 MBh 41.2 42.1 45.0 48.1 40.2 ...
-
Goodman Mfg GPC14H - page 20
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 20 www .goodmanmfg.com SS-GPC14H e xP AnDeD c ooling D A TA — gPc1 448H41AA Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1800 MBh 45.6 47.2 51.7 - 44.5 46.1 50.5 - 43 ...
-
Goodman Mfg GPC14H - page 21
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 21 e xP AnDeD c ooling D A TA — gPc1 448H41AA ( conT .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1800 MBh 47.2 48.2 51.5 55.0 46.1 4 ...
-
Goodman Mfg GPC14H - page 22
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 22 www .goodmanmfg.com SS-GPC14H e xP AnDeD c ooling D A TA — gPc1 448H41A c Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1777 MBh 46.1 47.8 52.4 - 45.1 46.7 51.2 - 4 ...
-
Goodman Mfg GPC14H - page 23
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 23 e xP AnDeD c ooling D A TA — gPc1 448H41A c ( conT .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1777 MBh 47.7 48.8 52.1 55.7 46.6 ...
-
Goodman Mfg GPC14H - page 24
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 24 www .goodmanmfg.com SS-GPC14H e xP AnDeD c ooling D A TA — gPc1 460H41A * Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1800 MBh 56.3 58.4 64.0 - 55.0 57.0 62.5 - 5 ...
-
Goodman Mfg GPC14H - page 25
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 25 e xP AnDeD c ooling D A TA — gPc1 460H41A * ( conT .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1800 MBh 58.3 59.6 63.7 68.1 57.0 ...
-
Goodman Mfg GPC14H - page 26
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 26 www .goodmanmfg.com SS-GPC14H H eA T k iT e lecTRicAl D AT A (B loweR o nl y , H eA T m oDe ) Model and Hea t Kit Usage Cir cuit #1 Circuit #2 A c tual kW / BTU@ 240V MCA¹ MOD² MCA¹ MOD² GPC1424H41* 1.5 / 1.5 -- -- -- -- HKR-05*, HKR-05C* 24 / 27 30 / 30 -- -- 4.75 / 16,200 HKR-08*, HKR-08C ...
-
Goodman Mfg GPC14H - page 27
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 27 D imenSionS m inimAl c leARAnceS A Dimensions Model Chassis Size Height GPC1424 GPC1430 GPC1436 GPC1442 GPC1448 GPC1460 38¾ A ...
-
Goodman Mfg GPC14H - page 28
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 28 www .goodmanmfg.com SS-GPC14H w iRing D iA gRAm — gPc1 42 4-60H4 1AA Wiring is subject to change. Always refer to the wiring diagram or the unitforthe mostup-to-datewiring . ⚠ W arninG High V oltage: Disconnect all power bef ...
-
Goodman Mfg GPC14H - page 29
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 29 w iRing D iA gRAm — gPc1 42 4-48H4 1A c Wiring is subject to change. Always refer to the wiring diagram or the unitforthe mostup-to-datewiring . ⚠ W arninG High V oltage: Disconnect all power be ...
-
Goodman Mfg GPC14H - page 30
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 30 www .goodmanmfg.com SS-GPC14H A cceSSoRieS Item Descrip tion OT /EHR18-60 Emergency Heat R elay kit OT18-60A Out door Thermostat Kit with Lock out Stat PCCP102/103 Roof Curb f or for Medium/Large Chassis PCE102/103 Downow Ec onomizer for f or Medium/Large Chassis PCEF102/103 Elbow & Flas ...
-
Goodman Mfg GPC14H - page 31
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS SS-GPC14H www .goodmanmfg.com 31 n o TeS ...
-
Goodman Mfg GPC14H - page 32
P RoDUcT S PeciFicA TionS P RoDUcT S PeciFicA TionS 32 www .goodmanmfg.com SS-GPC14H Goodman Manufacturing Company , L.P ., reserves the right to discontinue, or change a t any time, specications or desig ns without notice or without incurring obligations. © 2011 • Goodman Manufacturing Company , L.P . • Houston, T exas • Printed in the U ...
¿Tienes una pregunta acerca de Goodman Mfg GPC14H?
Utiliza el formulario que se encuentra abajo
Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Goodman Mfg GPC14H, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Goodman Mfg GPC14H probablemente compartirá una forma de solucionarlo.