    V ektor -CD Dir ect or Belt Drive The V ektor -CD fan is a side inlet centrifugal blower with a high plume dilution nozzle designed for laboratory exhaust systems. Available in either dir ect or belt drive configurations, the V ektor -CD is capable of up to 14 inches wg of static pressur e and 100,000 cfm and can be constructed to AMCA spark B or ...

  • Greenheck Fan 47555 - page 2

    Remove any accumulations of dirt, water , ice or snow and wipe dry before moving to indoor storage. T o avoid “sweating” of metal parts allow cold parts to reach r oom temperature. T o dry parts and packages use a portable electric heater to get rid of any moisture build up. Leave coverings loose to permit air circulation and to allow for perio ...

  • Greenheck Fan 47555 - page 3

    3 V ektor -CD Centrifugal Laboratory Exhaust ® REMOVING FROM ST ORAGE As fans are r emoved from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the fan equipment goes into operation. Prior to assembly and installation of the V ektor fan and system components, inspect the fan ass ...

  • Greenheck Fan 47555 - page 4

    4 V ektor -CD Centrifugal Laboratory Exhaust ® Curb Installations Greenheck supplies gasketing material for all multi- section curbs and/or plenums. Install gasketing prior to bolting split curbs and or plenums together . NOTE: Steel, concrete or wood support is per structural engineer and in accordance with load requir ements and applicable build ...

  • Greenheck Fan 47555 - page 5

    5 V ektor -CD Centrifugal Laboratory Exhaust ® Riser Installation Check curb or structural supports for levelness. Both must be level to ensure pr oper drainage from plenum and fan(s). For side inlet fans, remove panel at end of plenum. This opening is the designed connection spot for user connected ductwork from building. Lab Exhaust Riser Riser ...

  • Greenheck Fan 47555 - page 6

    6 V ektor -CD Centrifugal Laboratory Exhaust ® Plenum Installation The figures depicted illustrate thr ee common methods used to install V ektor -CD bypass plenums. Methods used to attach a V ektor unit are dependent on local codes, roof construction design and r oof construction materials. Consult an architect or structural engineer for proper m ...

  • Greenheck Fan 47555 - page 7

    7 V ektor -CD Centrifugal Laboratory Exhaust ® Fan Installation Fan Housing Installation If the windband is shipped attached to the fan housing or if the windband is secured to the fan housing prior to mounting to the plenum, the fan / windband assembly should be lifted by the lifting lugs located on the fan housing. Do not lift this assembly by t ...

  • Greenheck Fan 47555 - page 8

    8 V ektor -CD Centrifugal Laboratory Exhaust ® Plenum and Fan Drainage Piping and T rap Detail (by others) There ar e multiple locations for pipe connections, one on each plenum section, and another on each tubular fan housing located at the bottom of the scroll. Each drain should be properly connected to a drainage system to ensure pr oper dispos ...

  • Greenheck Fan 47555 - page 9

    9 V ektor -CD Centrifugal Laboratory Exhaust ® Disconnect is mounted to fan housing. T ransformer is mounted to bypass air plenum near isolation damper actuator motor . For systems that ship un-assembled because of physical size, this connection at disconnect from transformer must be field installed. Wires with conduit and fitting are pr ovided ...

  • Greenheck Fan 47555 - page 10

    10 V ektor -CD Centrifugal Laboratory Exhaust ® Unit Start-Up 1. Disconnect and lock-out all power switches to fan. 2. Check for bearing alignment and lubrication. 3. Check the V -belt drive for proper alignment and tension (belt drive). 4. Check rigid coupling for proper alignment and connect between motor shaft and fan shaft (direct drive). 5. C ...

  • Greenheck Fan 47555 - page 11

    11 V ektor -CD Centrifugal Laboratory Exhaust ® Serviceable Components Windband Bypass Air Plenum Bypass Damper Weatherhood Isolation Damper Nozzle Fan Assembly Roof Curb or Structural Support Fan Operation All fans should be run every thirty (30) days, or at least “bumped” every thirty days. It is preferr ed that each fan is run as this cause ...

  • Greenheck Fan 47555 - page 12

    12 V ektor -CD Centrifugal Laboratory Exhaust ® Motors Motor maintenance is generally limited to cleaning and lubrication. Cleaning should be limited to exterior surfaces only . Removing dust and grease buildup on the motor housing assists proper motor cooling. Never wash-down motor with high pressur e spray . Greasing of motors is only intended w ...

  • Greenheck Fan 47555 - page 13

    13 V ektor -CD Centrifugal Laboratory Exhaust ® Bearing Replacement Both drive bearings are accessible fr om the ground on all V ektor -CD fans. Whether direct or belt driven, the bearings, along with other serviceable drive components (belts, motors, sheaves) are accessible by removing the motor cover panel. Please contact Greenheck Fan Corporati ...

  • Greenheck Fan 47555 - page 14

    14 V ektor -CD Centrifugal Laboratory Exhaust ® Problem Cause Corrective Action Excessive noise Wheel rubbing inlet Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars on shaft. V -belt drive Tighten sheaves on motor/fan shaft. Adjust belt tension. Align sheaves properly (see pr ocedure). Replace worn belts or sheaves. Bearings Re ...

  • Greenheck Fan 47555 - page 15

    15 V ektor -CD Centrifugal Laboratory Exhaust ® Date __________________ Time _____________ AM/PM Notes:___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ Da ...

  • Greenheck Fan 47555 - page 16

    16 471555 • Model V ektor -CD IOM, Rev. 1, February 2008 Copyright 2008 © Greenheck Fan Corp. Greenheck warrants this equipment to be fr ee from defects in material and workmanship for a period of thr ee years from the pur chase date. Any units or parts which prove defective during the warranty period will be r eplaced at our option when returne ...

Fabricante Greenheck Fan Categoría Blower

Los documentos del dispositivo Greenheck Fan 47555 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Greenheck Fan
- manuales de instrucciones 47555
- hojas de producto Greenheck Fan
- folletos informativos
- o etiquetas energéticas Greenheck Fan 47555
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Greenheck Fan 47555.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Greenheck Fan 47555, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Greenheck Fan 47555. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Greenheck Fan 47555.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Greenheck Fan 47555, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Greenheck Fan 47555. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Greenheck Fan 47555.

El manual de instrucciones completo de Greenheck Fan debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Greenheck Fan 47555 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Greenheck Fan 47555, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Greenheck Fan 47555 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Greenheck Fan 47555 - que deben facilitarnos los primeros pasos durante el uso de Greenheck Fan 47555
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Greenheck Fan 47555
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Greenheck Fan 47555 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Greenheck Fan 47555?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Greenheck Fan 47555, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Greenheck Fan 47555 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)