    V ektor -CD Dir ect or Belt Drive The V ektor -CD fan is a side inlet centrifugal blower with a high plume dilution nozzle designed for laboratory exhaust systems. Available in either dir ect or belt drive configurations, the V ektor -CD is capable of up to 14 inches wg of static pressur e and 100,000 cfm and can be constructed to AMCA spark B or ...

  • Greenheck Fan 47555 - page 2

    Remove any accumulations of dirt, water , ice or snow and wipe dry before moving to indoor storage. T o avoid “sweating” of metal parts allow cold parts to reach r oom temperature. T o dry parts and packages use a portable electric heater to get rid of any moisture build up. Leave coverings loose to permit air circulation and to allow for perio ...

  • Greenheck Fan 47555 - page 3

    3 V ektor -CD Centrifugal Laboratory Exhaust ® REMOVING FROM ST ORAGE As fans are r emoved from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the fan equipment goes into operation. Prior to assembly and installation of the V ektor fan and system components, inspect the fan ass ...

  • Greenheck Fan 47555 - page 4

    4 V ektor -CD Centrifugal Laboratory Exhaust ® Curb Installations Greenheck supplies gasketing material for all multi- section curbs and/or plenums. Install gasketing prior to bolting split curbs and or plenums together . NOTE: Steel, concrete or wood support is per structural engineer and in accordance with load requir ements and applicable build ...

  • Greenheck Fan 47555 - page 5

    5 V ektor -CD Centrifugal Laboratory Exhaust ® Riser Installation Check curb or structural supports for levelness. Both must be level to ensure pr oper drainage from plenum and fan(s). For side inlet fans, remove panel at end of plenum. This opening is the designed connection spot for user connected ductwork from building. Lab Exhaust Riser Riser ...

  • Greenheck Fan 47555 - page 6

    6 V ektor -CD Centrifugal Laboratory Exhaust ® Plenum Installation The figures depicted illustrate thr ee common methods used to install V ektor -CD bypass plenums. Methods used to attach a V ektor unit are dependent on local codes, roof construction design and r oof construction materials. Consult an architect or structural engineer for proper m ...

  • Greenheck Fan 47555 - page 7

    7 V ektor -CD Centrifugal Laboratory Exhaust ® Fan Installation Fan Housing Installation If the windband is shipped attached to the fan housing or if the windband is secured to the fan housing prior to mounting to the plenum, the fan / windband assembly should be lifted by the lifting lugs located on the fan housing. Do not lift this assembly by t ...

  • Greenheck Fan 47555 - page 8

    8 V ektor -CD Centrifugal Laboratory Exhaust ® Plenum and Fan Drainage Piping and T rap Detail (by others) There ar e multiple locations for pipe connections, one on each plenum section, and another on each tubular fan housing located at the bottom of the scroll. Each drain should be properly connected to a drainage system to ensure pr oper dispos ...

  • Greenheck Fan 47555 - page 9

    9 V ektor -CD Centrifugal Laboratory Exhaust ® Disconnect is mounted to fan housing. T ransformer is mounted to bypass air plenum near isolation damper actuator motor . For systems that ship un-assembled because of physical size, this connection at disconnect from transformer must be field installed. Wires with conduit and fitting are pr ovided ...

  • Greenheck Fan 47555 - page 10

    10 V ektor -CD Centrifugal Laboratory Exhaust ® Unit Start-Up 1. Disconnect and lock-out all power switches to fan. 2. Check for bearing alignment and lubrication. 3. Check the V -belt drive for proper alignment and tension (belt drive). 4. Check rigid coupling for proper alignment and connect between motor shaft and fan shaft (direct drive). 5. C ...

  • Greenheck Fan 47555 - page 11

    11 V ektor -CD Centrifugal Laboratory Exhaust ® Serviceable Components Windband Bypass Air Plenum Bypass Damper Weatherhood Isolation Damper Nozzle Fan Assembly Roof Curb or Structural Support Fan Operation All fans should be run every thirty (30) days, or at least “bumped” every thirty days. It is preferr ed that each fan is run as this cause ...

  • Greenheck Fan 47555 - page 12

    12 V ektor -CD Centrifugal Laboratory Exhaust ® Motors Motor maintenance is generally limited to cleaning and lubrication. Cleaning should be limited to exterior surfaces only . Removing dust and grease buildup on the motor housing assists proper motor cooling. Never wash-down motor with high pressur e spray . Greasing of motors is only intended w ...

  • Greenheck Fan 47555 - page 13

    13 V ektor -CD Centrifugal Laboratory Exhaust ® Bearing Replacement Both drive bearings are accessible fr om the ground on all V ektor -CD fans. Whether direct or belt driven, the bearings, along with other serviceable drive components (belts, motors, sheaves) are accessible by removing the motor cover panel. Please contact Greenheck Fan Corporati ...

  • Greenheck Fan 47555 - page 14

    14 V ektor -CD Centrifugal Laboratory Exhaust ® Problem Cause Corrective Action Excessive noise Wheel rubbing inlet Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars on shaft. V -belt drive Tighten sheaves on motor/fan shaft. Adjust belt tension. Align sheaves properly (see pr ocedure). Replace worn belts or sheaves. Bearings Re ...

  • Greenheck Fan 47555 - page 15

    15 V ektor -CD Centrifugal Laboratory Exhaust ® Date __________________ Time _____________ AM/PM Notes:___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ Da ...

  • Greenheck Fan 47555 - page 16

    16 471555 • Model V ektor -CD IOM, Rev. 1, February 2008 Copyright 2008 © Greenheck Fan Corp. Greenheck warrants this equipment to be fr ee from defects in material and workmanship for a period of thr ee years from the pur chase date. Any units or parts which prove defective during the warranty period will be r eplaced at our option when returne ...

Fabricant Greenheck Fan Catégorie Blower

Les documents que nous recevons du fabricant de l'appareilGreenheck Fan 47555 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Greenheck Fan
- manuels d’utilisations 47555
- fiches produit Greenheck Fan
- dépliants
- ou étiquettes-énergie Greenheck Fan 47555
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Greenheck Fan 47555.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Greenheck Fan 47555, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Greenheck Fan 47555. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Greenheck Fan 47555.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Greenheck Fan 47555, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Greenheck Fan 47555 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Greenheck Fan 47555.

Le manuel d’utilisation complet Greenheck Fan, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Greenheck Fan 47555 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Greenheck Fan 47555, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lGreenheck Fan 47555 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Greenheck Fan 47555 - qui devraient nous aider dans les premières étapes lors de l'utilisation Greenheck Fan 47555
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Greenheck Fan 47555
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Greenheck Fan 47555 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Greenheck Fan 47555?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Greenheck Fan 47555, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Greenheck Fan 47555 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)