    SSZ 14 SEER S plit System Heat Pumps • Refer to Service Manual RS6200005 for installation, op- eration, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. RT6213005 May 2006 TECHNICAL INFORMA TION MANUAL Copyright ? ...

  • Goodman Mfg SSZ140181A - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to d ...

  • Goodman Mfg SSZ140181A - page 3

    PRODUCT IDENTIFICA TION 3 WARNING WARNING WARNING WARNING To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance. Do not connect or use any device that is not design certified by Goodman for use with this unit. Serio ...

  • Goodman Mfg SSZ140181A - page 4

    PRODUCT DESIGN 4 SSZ14 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for ...

  • Goodman Mfg SSZ140181A - page 5

    HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...

  • Goodman Mfg SSZ140181A - page 6

    6 COOLING PERFORMANCE DA T A SSZ140181A* EXPA NDED PERFORMAN CE DA TA COOLING OPE RA TION MODEL: SSZ140181A * / CA *F3131*6 A* +TXV / M BR800**-1 D esign Subcooling 9 ± 3 °F @ the liqui d service valve, A RI 95 test conditio ns Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature I D B * A i r f l o w 5 96 36 77 1 ...

  • Goodman Mfg SSZ140181A - page 7

    7 COOLING PERFORMANCE DA T A SSZ140181A* EXPA NDED PERFORMAN CE DATA COOLING O PERATION MODEL: SSZ140 181A * / CA *F3131*6A * +TXV / M BR800**-1 D esign Subc ooling 9 ±3 °F @ t he liquid service v alve, A RI 95 test c onditio ns Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor W et Bulb Temperatur e I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg SSZ140181A - page 8

    8 COOLING PERFORMANCE DA T A SSZ140241A* EXPA ND ED PERFORM A NCE DATA COOLING OP ERA TION MODEL: SS Z140241A * / CA *F3636*6 A *+TXV / MBR80 0**-1 Design Subco oling 9 ±3 °F @ the liquid service val v e, A RI 95 tes t condition s Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperatur e I D B * A i r f l o w 5 96 3 6 ...

  • Goodman Mfg SSZ140181A - page 9

    9 COOLING PERFORMANCE DA T A SSZ140241A* EXPA NDED PERFO RMA NCE DA T A COOLING OPERA TION MO DEL: SSZ140241A* / CA *F3636* 6A *+TXV / MB R800**-1 Design Subcoo ling 9 ±3 °F @ the liqui d service valv e, ARI 95 test condit ion s Out door A mbient Temp eratur e 65 75 85 95 105 115 Enteri ng I ndoor W et Bulb Temperatur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg SSZ140181A - page 10

    10 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION M ODEL: SSZ140301A* / CA *F3642*6A*+TXV / MBR1600**-1 Design Subcooling 9 ±3 °F @ the liquid service valv e, AR I 95 test conditio ns Outdoor A mbient Temperature 65 75 85 95 105 1 15 Enterin g Indo or W et Bul b Temperatur e I D B * A i r f l o w 5 96 36 77 ...

  • Goodman Mfg SSZ140181A - page 11

    11 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFORMA NC E DA TA COOLING OPERA TION M ODEL: SSZ 140301A * / CA*F3642*6A *+T XV / MB R1600**-1 Design Subcooling 9 ±3 °F @ th e liquid serv ice valve, ARI 95 test conditio ns Outdoor A mbi ent Temper atu re 65 75 85 95 105 115 Enterin g Indo or W et Bulb Temperature I D B * A i r f l o w 5 96 ...

  • Goodman Mfg SSZ140181A - page 12

    12 COOLING PERFORMANCE DA T A SSZ140361A* EXPA NDED PER FOR M A NCE DA T A MODEL: SSZ140 361A * / CA*F4860*6A*+TXV / M BR1600 **- 1 Desig n Subco oli ng 9 ±3 ° F @ th e li qu id serv i ce va lv e, A RI 95 t est co ndi ti o ns Outdo or A mbient T emperature 65 75 85 9 5 105 115 Entering I ndoor Wet Bulb Te mperature IDB Airfl ow 59 63 67 71 59 63 ...

  • Goodman Mfg SSZ140181A - page 13

    13 COOLING PERFORMANCE DA T A SSZ140361A* EXPA ND ED PERFO RM A NCE D A TA COOLING OP ERATION MODEL: SSZ140361A* / CA *F4860*6A*+TXV / M BR1600 **- 1 Desig n Subco oli ng 9 ±3 ° F @ th e li qu id serv i ce va lv e, A RI 95 te st cond it i o ns Outdo or A mbient T emper ature 65 75 85 9 5 105 115 Entering I ndoor Wet Bulb Te mperature I D B * A i ...

  • Goodman Mfg SSZ140181A - page 14

    14 COOLING PERFORMANCE DA T A SSZ140421A* EXPA NDED PERFORMA NCE DA T A MODEL: S SZ1404 21A * / CA *F4860*6 A*+TXV / M BR2000 **-1 Design Sub cooling 9 ±3 °F @ the li quid service valve, A RI 95 test conditio ns Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB A irf lo w 59 63 67 71 59 63 6 7 71 59 63 67 7 ...

  • Goodman Mfg SSZ140181A - page 15

    15 COOLING PERFORMANCE DA T A SSZ140421A* EXPANDED PERFORMANCE DA T A COOLING OP ERA TION MODEL: SSZ14 0421A * / CA *F4860*6A *+TXV / MBR2000 **-1 Design Sub cooli ng 9 ±3 °F @ the liquid s ervice valve, A RI 95 test condi t io ns Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg SSZ140181A - page 16

    16 COOLING PERFORMANCE DA T A SSZ140481A* EXPA NDED PERFORMANCE DA TA COOLING O PERA TION MODEL: SS Z140 481A * / CA *F48 60*6A *+TXV / MBR20 00**-1 Design Sub cooling 9 ±3 °F @ the liq uid service va lve, A RI 95 test con ditio ns Outdoor A mbient Temperatur e 65 75 85 95 1 05 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 ...

  • Goodman Mfg SSZ140181A - page 17

    17 COOLING PERFORMANCE DA T A SSZ140481A* EXPA NDED PERFORMA NCE DATA COOLING O PERA TI ON MODEL: S S Z140481 A* / C A*F4 860*6A *+TXV / MBR2000**-1 Design S ubcool ing 9 ±3 °F @ the liquid s ervice valve, A RI 95 tes t conditio ns Outdoor A mbient Temperature 65 75 85 95 1 05 115 Entering Indoor Wet Bulb Temperatur e I D B * A i r f l o w 5 96 3 ...

  • Goodman Mfg SSZ140181A - page 18

    18 COOLING PERFORMANCE DA T A SSZ140601A* EXPA NDED PERFORMA N CE DA TA COOLING O PERATION MODEL: SSZ140 601A * / CA *F4860*6A *+TXV / MBE200 0**-1 Design S ubcooling 9 ±3 ° F @ the liquid s ervice valve, A RI 95 test conditio ns Outdoor A mbie nt Temperat ure 65 75 85 9 5 105 115 Entering Indoor W et Bulb Temperature IDB A irf lo w 59 63 67 71 5 ...

  • Goodman Mfg SSZ140181A - page 19

    19 COOLING PERFORMANCE DA T A SSZ140601A* EXPA NDED PERFORMA NCE DAT A COOLING O PE RA TI ON MODEL: SSZ140 601A * / CA *F4860*6 A *+TXV / MBE2000** -1 Design Subcooling 9 ±3 ° F @ the liquid service valve , A RI 95 test conditio ns Outdoor A mbie nt Temperat ure 65 75 85 9 5 105 115 Entering Indoor W et Bulb Temperature I D B * A i r f l o w 5 96 ...

  • Goodman Mfg SSZ140181A - page 20

    20 PERFORMANCE DA T A Out door Temp. ° F . Tota l Btuh Sen sibl e Btu h La te nt Btuh Total Wat ts 75° 36,330 24,713 11,617 2,662 80° 35,898 24,729 11,169 2,742 85° 35,465 24,738 10,727 2,822 90° 35,033 24,830 10,203 2,892 95° 34,600 24,912 9,688 2,963 100° 33,735 24,749 8,986 3,023 105° 32,870 24,563 8,307 3,083 110° 31,659 23,757 7,902 3 ...

  • Goodman Mfg SSZ140181A - page 21

    21 EXPA NDED PERFORM ANCE DA TA M ODEL: SSZ140361A * / CA*F4860C6A *+T XV / M BR1600**-1 HEATING O PERATION Outdoo r Ambient Tem p era ture 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 MBh 43.5 41.2 38.8 36.2 34.6 33.5 31. 1 28.7 28.8 26.6 24.5 23. 1 22. 3 20.0 17.7 1 5.5 13.2 10.8 Delta T 38.4 36.3 34.2 31.9 30.5 29.6 27.5 2 5.3 2 5.4 23.5 ...

  • Goodman Mfg SSZ140181A - page 22

    22 EXPANDED PERFORM ANCE DA TA MO DEL: SSZ140481A* / CA*F4860*6A *+TX V / MBR 2000**-1 HEA T ING OP ERATION Outdoor A mbient Te mperat ure 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -1 0 MBh 57.8 5 4.7 5 1.5 48. 2 46. 0 44.6 41 .4 38.2 36 .6 33 . 8 31.1 29. 4 28.3 25 .4 22 .5 19.6 16. 8 13.7 D e l t a T 3 4 . 53 2 . 73 0 . 8 2 8 . 8 2 7 . 5 2 ...

  • Goodman Mfg SSZ140181A - page 23

    23 HEA TING SPECIFICA TIONS capacit y btuh c.o.p. 4.8 9.6 1 4.4 19.2 65 22.63 4.23 39.01 55.39 71.77 88.16 60 21.42 4.09 37.80 54.18 70.57 86.95 55 20.16 3.93 36.54 52.92 69.31 85.69 50 18.85 3.75 35.23 51.61 67.99 84.38 45 17.44 3.54 33.82 50.21 66.59 82.97 40 16.20 3.36 32.58 48.96 65.35 81.73 35 14.94 3.16 31.32 47.70 64.09 80.47 30 12.80 2.70 2 ...

  • Goodman Mfg SSZ140181A - page 24

    24 HEA TING SPECIFICA TIONS capaci t y btuh c. o.p . 4. 8 9. 6 14.4 19 . 2 65 51.5 4 4. 44 67. 92 84. 30 1 00. 68 117. 07 60 48.7 9 4. 28 65. 17 81. 55 9 7.9 4 114 .32 55 45.9 2 4. 11 62. 30 78. 68 9 5.0 7 111 .45 50 42.9 3 3. 92 59. 31 75. 69 9 2.0 7 108 .46 45 39.7 3 3. 70 56. 11 72. 49 8 8.8 8 105 .26 40 36.9 0 3. 50 53. 28 69. 66 8 6.0 5 102 .4 ...

  • Goodman Mfg SSZ140181A - page 25

    25 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...

  • Goodman Mfg SSZ140181A - page 26

    WIRING DIAGRAMS 26 TO AVOID POSSI BLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DI SCONNECT THE POWER BEFORE SERVI CING. WARNING ! Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. SSZ140[18-60]1A* COM P IO T1 C M A I N R A U X 5 S SR SA 2 1 RCCF SC T2 C L1 L2 C H C F M A I N A U X IO CM ...

Fabricante Goodman Mfg Categoría Heat Pump

Los documentos del dispositivo Goodman Mfg SSZ140181A que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Goodman Mfg
- manuales de instrucciones SSZ140181A
- hojas de producto Goodman Mfg
- folletos informativos
- o etiquetas energéticas Goodman Mfg SSZ140181A
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Goodman Mfg SSZ140181A.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Goodman Mfg SSZ140181A, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Goodman Mfg SSZ140181A. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Goodman Mfg SSZ140181A.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Goodman Mfg SSZ140181A, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Goodman Mfg SSZ140181A. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Goodman Mfg SSZ140181A.

El manual de instrucciones completo de Goodman Mfg debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Goodman Mfg SSZ140181A - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Goodman Mfg SSZ140181A, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Goodman Mfg SSZ140181A que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Goodman Mfg SSZ140181A - que deben facilitarnos los primeros pasos durante el uso de Goodman Mfg SSZ140181A
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Goodman Mfg SSZ140181A
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Goodman Mfg SSZ140181A en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Goodman Mfg SSZ140181A?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Goodman Mfg SSZ140181A, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Goodman Mfg SSZ140181A probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)