    SSZ 14 SEER S plit System Heat Pumps • Refer to Service Manual RS6200005 for installation, op- eration, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information. RT6213005 May 2006 TECHNICAL INFORMA TION MANUAL Copyright ? ...

  • Goodman Mfg SSZ140181A - page 2

    PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to d ...

  • Goodman Mfg SSZ140181A - page 3

    PRODUCT IDENTIFICA TION 3 WARNING WARNING WARNING WARNING To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance. Do not connect or use any device that is not design certified by Goodman for use with this unit. Serio ...

  • Goodman Mfg SSZ140181A - page 4

    PRODUCT DESIGN 4 SSZ14 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet. These units are designed for ...

  • Goodman Mfg SSZ140181A - page 5

    HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only. Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial ...

  • Goodman Mfg SSZ140181A - page 6

    6 COOLING PERFORMANCE DA T A SSZ140181A* EXPA NDED PERFORMAN CE DA TA COOLING OPE RA TION MODEL: SSZ140181A * / CA *F3131*6 A* +TXV / M BR800**-1 D esign Subcooling 9 ± 3 °F @ the liqui d service valve, A RI 95 test conditio ns Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature I D B * A i r f l o w 5 96 36 77 1 ...

  • Goodman Mfg SSZ140181A - page 7

    7 COOLING PERFORMANCE DA T A SSZ140181A* EXPA NDED PERFORMAN CE DATA COOLING O PERATION MODEL: SSZ140 181A * / CA *F3131*6A * +TXV / M BR800**-1 D esign Subc ooling 9 ±3 °F @ t he liquid service v alve, A RI 95 test c onditio ns Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor W et Bulb Temperatur e I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg SSZ140181A - page 8

    8 COOLING PERFORMANCE DA T A SSZ140241A* EXPA ND ED PERFORM A NCE DATA COOLING OP ERA TION MODEL: SS Z140241A * / CA *F3636*6 A *+TXV / MBR80 0**-1 Design Subco oling 9 ±3 °F @ the liquid service val v e, A RI 95 tes t condition s Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperatur e I D B * A i r f l o w 5 96 3 6 ...

  • Goodman Mfg SSZ140181A - page 9

    9 COOLING PERFORMANCE DA T A SSZ140241A* EXPA NDED PERFO RMA NCE DA T A COOLING OPERA TION MO DEL: SSZ140241A* / CA *F3636* 6A *+TXV / MB R800**-1 Design Subcoo ling 9 ±3 °F @ the liqui d service valv e, ARI 95 test condit ion s Out door A mbient Temp eratur e 65 75 85 95 105 115 Enteri ng I ndoor W et Bulb Temperatur e I D B * A i r f l o w 5 96 ...

  • Goodman Mfg SSZ140181A - page 10

    10 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFORMA NCE DA TA COOLING OPERA TION M ODEL: SSZ140301A* / CA *F3642*6A*+TXV / MBR1600**-1 Design Subcooling 9 ±3 °F @ the liquid service valv e, AR I 95 test conditio ns Outdoor A mbient Temperature 65 75 85 95 105 1 15 Enterin g Indo or W et Bul b Temperatur e I D B * A i r f l o w 5 96 36 77 ...

  • Goodman Mfg SSZ140181A - page 11

    11 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFORMA NC E DA TA COOLING OPERA TION M ODEL: SSZ 140301A * / CA*F3642*6A *+T XV / MB R1600**-1 Design Subcooling 9 ±3 °F @ th e liquid serv ice valve, ARI 95 test conditio ns Outdoor A mbi ent Temper atu re 65 75 85 95 105 115 Enterin g Indo or W et Bulb Temperature I D B * A i r f l o w 5 96 ...

  • Goodman Mfg SSZ140181A - page 12

    12 COOLING PERFORMANCE DA T A SSZ140361A* EXPA NDED PER FOR M A NCE DA T A MODEL: SSZ140 361A * / CA*F4860*6A*+TXV / M BR1600 **- 1 Desig n Subco oli ng 9 ±3 ° F @ th e li qu id serv i ce va lv e, A RI 95 t est co ndi ti o ns Outdo or A mbient T emperature 65 75 85 9 5 105 115 Entering I ndoor Wet Bulb Te mperature IDB Airfl ow 59 63 67 71 59 63 ...

  • Goodman Mfg SSZ140181A - page 13

    13 COOLING PERFORMANCE DA T A SSZ140361A* EXPA ND ED PERFO RM A NCE D A TA COOLING OP ERATION MODEL: SSZ140361A* / CA *F4860*6A*+TXV / M BR1600 **- 1 Desig n Subco oli ng 9 ±3 ° F @ th e li qu id serv i ce va lv e, A RI 95 te st cond it i o ns Outdo or A mbient T emper ature 65 75 85 9 5 105 115 Entering I ndoor Wet Bulb Te mperature I D B * A i ...

  • Goodman Mfg SSZ140181A - page 14

    14 COOLING PERFORMANCE DA T A SSZ140421A* EXPA NDED PERFORMA NCE DA T A MODEL: S SZ1404 21A * / CA *F4860*6 A*+TXV / M BR2000 **-1 Design Sub cooling 9 ±3 °F @ the li quid service valve, A RI 95 test conditio ns Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature IDB A irf lo w 59 63 67 71 59 63 6 7 71 59 63 67 7 ...

  • Goodman Mfg SSZ140181A - page 15

    15 COOLING PERFORMANCE DA T A SSZ140421A* EXPANDED PERFORMANCE DA T A COOLING OP ERA TION MODEL: SSZ14 0421A * / CA *F4860*6A *+TXV / MBR2000 **-1 Design Sub cooli ng 9 ±3 °F @ the liquid s ervice valve, A RI 95 test condi t io ns Outdoor A mbient Temperature 65 75 85 95 105 115 Entering Indoor Wet Bulb Temperature I D B * A i r f l o w 5 96 36 7 ...

  • Goodman Mfg SSZ140181A - page 16

    16 COOLING PERFORMANCE DA T A SSZ140481A* EXPA NDED PERFORMANCE DA TA COOLING O PERA TION MODEL: SS Z140 481A * / CA *F48 60*6A *+TXV / MBR20 00**-1 Design Sub cooling 9 ±3 °F @ the liq uid service va lve, A RI 95 test con ditio ns Outdoor A mbient Temperatur e 65 75 85 95 1 05 115 Entering Indoor Wet Bulb Te mperature I D B * A i r f l o w 5 96 ...

  • Goodman Mfg SSZ140181A - page 17

    17 COOLING PERFORMANCE DA T A SSZ140481A* EXPA NDED PERFORMA NCE DATA COOLING O PERA TI ON MODEL: S S Z140481 A* / C A*F4 860*6A *+TXV / MBR2000**-1 Design S ubcool ing 9 ±3 °F @ the liquid s ervice valve, A RI 95 tes t conditio ns Outdoor A mbient Temperature 65 75 85 95 1 05 115 Entering Indoor Wet Bulb Temperatur e I D B * A i r f l o w 5 96 3 ...

  • Goodman Mfg SSZ140181A - page 18

    18 COOLING PERFORMANCE DA T A SSZ140601A* EXPA NDED PERFORMA N CE DA TA COOLING O PERATION MODEL: SSZ140 601A * / CA *F4860*6A *+TXV / MBE200 0**-1 Design S ubcooling 9 ±3 ° F @ the liquid s ervice valve, A RI 95 test conditio ns Outdoor A mbie nt Temperat ure 65 75 85 9 5 105 115 Entering Indoor W et Bulb Temperature IDB A irf lo w 59 63 67 71 5 ...

  • Goodman Mfg SSZ140181A - page 19

    19 COOLING PERFORMANCE DA T A SSZ140601A* EXPA NDED PERFORMA NCE DAT A COOLING O PE RA TI ON MODEL: SSZ140 601A * / CA *F4860*6 A *+TXV / MBE2000** -1 Design Subcooling 9 ±3 ° F @ the liquid service valve , A RI 95 test conditio ns Outdoor A mbie nt Temperat ure 65 75 85 9 5 105 115 Entering Indoor W et Bulb Temperature I D B * A i r f l o w 5 96 ...

  • Goodman Mfg SSZ140181A - page 20

    20 PERFORMANCE DA T A Out door Temp. ° F . Tota l Btuh Sen sibl e Btu h La te nt Btuh Total Wat ts 75° 36,330 24,713 11,617 2,662 80° 35,898 24,729 11,169 2,742 85° 35,465 24,738 10,727 2,822 90° 35,033 24,830 10,203 2,892 95° 34,600 24,912 9,688 2,963 100° 33,735 24,749 8,986 3,023 105° 32,870 24,563 8,307 3,083 110° 31,659 23,757 7,902 3 ...

  • Goodman Mfg SSZ140181A - page 21

    21 EXPA NDED PERFORM ANCE DA TA M ODEL: SSZ140361A * / CA*F4860C6A *+T XV / M BR1600**-1 HEATING O PERATION Outdoo r Ambient Tem p era ture 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 MBh 43.5 41.2 38.8 36.2 34.6 33.5 31. 1 28.7 28.8 26.6 24.5 23. 1 22. 3 20.0 17.7 1 5.5 13.2 10.8 Delta T 38.4 36.3 34.2 31.9 30.5 29.6 27.5 2 5.3 2 5.4 23.5 ...

  • Goodman Mfg SSZ140181A - page 22

    22 EXPANDED PERFORM ANCE DA TA MO DEL: SSZ140481A* / CA*F4860*6A *+TX V / MBR 2000**-1 HEA T ING OP ERATION Outdoor A mbient Te mperat ure 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -1 0 MBh 57.8 5 4.7 5 1.5 48. 2 46. 0 44.6 41 .4 38.2 36 .6 33 . 8 31.1 29. 4 28.3 25 .4 22 .5 19.6 16. 8 13.7 D e l t a T 3 4 . 53 2 . 73 0 . 8 2 8 . 8 2 7 . 5 2 ...

  • Goodman Mfg SSZ140181A - page 23

    23 HEA TING SPECIFICA TIONS capacit y btuh c.o.p. 4.8 9.6 1 4.4 19.2 65 22.63 4.23 39.01 55.39 71.77 88.16 60 21.42 4.09 37.80 54.18 70.57 86.95 55 20.16 3.93 36.54 52.92 69.31 85.69 50 18.85 3.75 35.23 51.61 67.99 84.38 45 17.44 3.54 33.82 50.21 66.59 82.97 40 16.20 3.36 32.58 48.96 65.35 81.73 35 14.94 3.16 31.32 47.70 64.09 80.47 30 12.80 2.70 2 ...

  • Goodman Mfg SSZ140181A - page 24

    24 HEA TING SPECIFICA TIONS capaci t y btuh c. o.p . 4. 8 9. 6 14.4 19 . 2 65 51.5 4 4. 44 67. 92 84. 30 1 00. 68 117. 07 60 48.7 9 4. 28 65. 17 81. 55 9 7.9 4 114 .32 55 45.9 2 4. 11 62. 30 78. 68 9 5.0 7 111 .45 50 42.9 3 3. 92 59. 31 75. 69 9 2.0 7 108 .46 45 39.7 3 3. 70 56. 11 72. 49 8 8.8 8 105 .26 40 36.9 0 3. 50 53. 28 69. 66 8 6.0 5 102 .4 ...

  • Goodman Mfg SSZ140181A - page 25

    25 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures increase, a ...

  • Goodman Mfg SSZ140181A - page 26

    WIRING DIAGRAMS 26 TO AVOID POSSI BLE ELECTRICAL SHOCK, PERSONAL INJURY, OR DEATH, DI SCONNECT THE POWER BEFORE SERVI CING. WARNING ! Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring. SSZ140[18-60]1A* COM P IO T1 C M A I N R A U X 5 S SR SA 2 1 RCCF SC T2 C L1 L2 C H C F M A I N A U X IO CM ...

Fabricant Goodman Mfg Catégorie Heat Pump

Les documents que nous recevons du fabricant de l'appareilGoodman Mfg SSZ140181A peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Goodman Mfg
- manuels d’utilisations SSZ140181A
- fiches produit Goodman Mfg
- dépliants
- ou étiquettes-énergie Goodman Mfg SSZ140181A
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Goodman Mfg SSZ140181A.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Goodman Mfg SSZ140181A, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Goodman Mfg SSZ140181A. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Goodman Mfg SSZ140181A.

Manuel d’utilisation complet de l’appareil Goodman Mfg SSZ140181A, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Goodman Mfg SSZ140181A par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Goodman Mfg SSZ140181A.

Le manuel d’utilisation complet Goodman Mfg, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Goodman Mfg SSZ140181A - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Goodman Mfg SSZ140181A, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lGoodman Mfg SSZ140181A qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Goodman Mfg SSZ140181A - qui devraient nous aider dans les premières étapes lors de l'utilisation Goodman Mfg SSZ140181A
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Goodman Mfg SSZ140181A
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Goodman Mfg SSZ140181A dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Goodman Mfg SSZ140181A?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Goodman Mfg SSZ140181A, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Goodman Mfg SSZ140181A il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)