Manual de instrucciones National Instruments EIGHT CHANNEL SPST RELAY MODULE

14 de páginas 0.35 mb
Descargar

Pasar a la página of 14

Summary
  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 1

    323617A-01 May 2003 © 2003 National I nstruments Corp. Al l rights res erved. FieldPoint™, Nati onal Instruments™, NI™, and ni.com™ are trademarks of National Instruments Corporation. Product and company names ment ioned herein are trademark s or trade names of their respecti ve companies. For patents covering National Inst ruments product ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 2

    cFP-RLY-421 2 ni.com Before you conf igure a FieldPoint system that uses a cFP-RL Y -421 module, calculate the total power consumption of the I/O modules on the FieldPoint bank. Y ou ca n find the po wer requirement specification in the operating inst ructions for ea ch I/O module . The maximum power the netw ork module can supply is specified in t ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 3

    © National Instruments Corp. 3 cFP-RLY-421 Figure 1. Installing the cFP-RL Y -421 Wiring the cFP-RL Y -421 The cFP-CB- x connector block has conne ctions for each of the eight cFP-RL Y -421 relay channels and for an external supply to power f ield devices. If you are using the cFP-RL Y - 421 in a hazardous voltage application, you mu st use the cF ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 4

    cFP-RLY-421 4 ni.com T able 1 li sts the terminal assign ments for the signals of each channel. All of the COM terminals are conne cted internally and all of the V SUP terminals are connected inte rnally . NI does not recommend using them with the cFP-RL Y -421. Caution Cascading power between two modules defeats isolation between those modules. Ca ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 5

    © National Instruments Corp. 5 cFP-RLY-421 Connecting Loads to the cFP-RL Y -421 W ire an external po wer supply to the load and IC terminal of the individu al channel as shown in Figure 2. This method of wiring keeps the electrical connections of the cFP-RL Y -421 within safe current limits. Figure 2. Connecting a Load The cFP-RL Y -421 has eight ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 6

    cFP-RLY-421 6 ni.com In addition, the cFP-RL Y -421 has internal protection MO Vs to pre vent excessiv ely high voltag e from being applied across the contacts. The MO Vs are located between the NO and IC contacts of each relay . Howe ver , National Instruments still recommends the use of a protection circuit across an inductive load. The flyback p ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 7

    © National Instruments Corp. 7 cFP-RLY-421 Diode Circuit CR Circuits Varistor Circuit Diagram Notes Use in DC applications only . Compared to RC type, circuit delays release time (2 to 5 times values stated in catalog). For lar ger voltages, use diode with rev erse breakdo wn 10 times circu it voltage an d forward load circuit. For smaller v oltag ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 8

    cFP-RLY-421 8 ni.com In-Rush Current The type of l oad and its in-rush current charac teristics, together with switching frequency , can ca use contact welding. For loads with in-rush current, measure the steady state current and in-rush current to determine the proper rela y . Some typical types of loads and the in-rush current they create are sum ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 9

    © National Instruments Corp. 9 cFP-RLY-421 Upgrading the FieldPoint Firmware Y ou may need to upgrade the FieldPoint f irmware when you add ne w I/O modules to the FieldPoi nt system. For information on determining which fi rmware you need and ho w to upgrade the firmw are, go to ni.com/info and enter fpmatrix . Isolation and Sa fety Guidelines Ca ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 10

    cFP-RLY-421 10 ni.com •D o not share the exter nal supply voltages (the V and C terminals) with other de vices (including othe r FieldPoint de vices), unless those devices ar e isolated from human contact. • Y ou must connect the protecti ve ea rth (PE) ground terminal on the cFP-BP- x backplane to the syst em safety ground. The backplane PE gr ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 11

    © National Instruments Corp. 11 cFP-RLY-421 Specifications The follo wing specifications ar e typical for a range of – 40 to 60 °C unless otherwise noted. Relay Characteristics Number of channels ..................... ..... 8 Relay type ......... ...................... .......... 1 SPST , nonlatching Maximum switching ca pacity (resisti ve load ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 12

    cFP-RLY-421 12 ni.com Physical Indicators ..... .............. ........... ........... . Green POWER and READY indicators, 8 green output state indicators W eight cFP-RL Y -421 .................... .......... 130 g (4.5 oz) Power Requirements Power from network modul e ............ 1,700 mW Isolation Voltage Maximum isolation v oltage ............. ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 13

    © National Instruments Corp. 13 cFP-RLY-421 Safety This product is designed to meet the requirements of the following standards of safety for electric al equipment for measurement, control, and laboratory use: • IEC 61010-1, EN 61010-1 • UL 3121-1, UL 61010C-1 • CAN/CSA C22.2 No. 1010.1 For UL, hazardous location, and othe r safety certifica ...

  • National Instruments EIGHT CHANNEL SPST RELAY MODULE - page 14

    cFP-RLY-421 14 ni.com Where to Go for Support For more information about settin g up the FieldPoint system, refer to these National Instruments documents: • FieldPoint network module user manual • Other FieldPo int I/O m odule operating instructions • FieldPoint connector bl ock operating instructions Go to ni.com/support for the most current ...

Fabricante National Instruments Categoría Electronic Accessory

Los documentos del dispositivo National Instruments EIGHT CHANNEL SPST RELAY MODULE que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos National Instruments
- manuales de instrucciones EIGHT CHANNEL SPST RELAY MODULE
- hojas de producto National Instruments
- folletos informativos
- o etiquetas energéticas National Instruments EIGHT CHANNEL SPST RELAY MODULE
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones National Instruments EIGHT CHANNEL SPST RELAY MODULE.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje National Instruments EIGHT CHANNEL SPST RELAY MODULE, instrucciones de servicio, instrucciones cortas o instrucciones de usuario National Instruments EIGHT CHANNEL SPST RELAY MODULE. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto National Instruments EIGHT CHANNEL SPST RELAY MODULE.

El manual de instrucciones del dispositivo National Instruments EIGHT CHANNEL SPST RELAY MODULE, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar National Instruments EIGHT CHANNEL SPST RELAY MODULE. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de National Instruments EIGHT CHANNEL SPST RELAY MODULE.

El manual de instrucciones completo de National Instruments debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual National Instruments EIGHT CHANNEL SPST RELAY MODULE - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice National Instruments EIGHT CHANNEL SPST RELAY MODULE, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de National Instruments EIGHT CHANNEL SPST RELAY MODULE que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo National Instruments EIGHT CHANNEL SPST RELAY MODULE - que deben facilitarnos los primeros pasos durante el uso de National Instruments EIGHT CHANNEL SPST RELAY MODULE
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con National Instruments EIGHT CHANNEL SPST RELAY MODULE
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de National Instruments EIGHT CHANNEL SPST RELAY MODULE en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de National Instruments EIGHT CHANNEL SPST RELAY MODULE?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con National Instruments EIGHT CHANNEL SPST RELAY MODULE, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con National Instruments EIGHT CHANNEL SPST RELAY MODULE probablemente compartirá una forma de solucionarlo.