    INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS W A381 W A423 W A484 W A491 W A602 Manual : 2100-398 Supersedes: File: V olume III T ab 16 Date: 01-28-02 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. © Copyright 2002 ...

  • Bard WA491 - page 2

    Contents Figures Figure 1 Unit Dimensions ...................................... 3 Figure 2 Fresh Air Damper Assembly ................... 6 Figure 3 Mounting Instructions .............................. 8 Figure 4 Electric Heat Clearance .......................... 9 Figure 5 W all Mounting Instructions .................... 10 Figure 6 W all Mounting ...

  • Bard WA491 - page 3

    Manual 2100-398 Page 1 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code ...................... ANSI/NFPA 70 ...

  • Bard WA491 - page 4

    Manual 2100-398 Page 2 W ALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE W A 42 3 – A 10 X N X X X A NOTE: All vent options are without exhaust capability. May require separate field supplied barometric relief in building. TABLE 1 ELECTRIC HEAT TABLE s l e d o M A - 1 8 3 A W A - 3 2 4 A W A - 4 8 4 A W A - 1 9 4 A W A - 2 ...

  • Bard WA491 - page 5

    Manual 2100-398 Page 3 MIS-1262 FIGURE 1 UNIT DIMENSIONS l e d o M h t d i W ) W ( h t p e D ) D ( t h g i e H ) H ( y l p p u Sn r u t e R EF G I J K L M N O P Q R S T A BCB 8 3 A W 2 4 A W 8 4 A W 9 4 A W 0 6 A W 5 7 0 . 2 42 3 4 . 2 25 7 8 . 4 88 8 . 98 8 . 9 28 8 . 5 18 8 . 9 28 8 . 3 40 1 . 9 16 6 . 1 30 0 . 0 38 6 . 2 34 9 . 6 29 6 . 4 33 4 . ...

  • Bard WA491 - page 6

    Manual 2100-398 Page 4 j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. k Based on 75 ° C copper wire. All wiring must conform to NEC and all local codes. l These “ Minimum Circuit Ampacity ” values are to be used for sizing the field power conductors. Refer to the National Electric ...

  • Bard WA491 - page 7

    Manual 2100-398 Page 5 j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. k Based on 75 ° C copper wire. All wiring must conform to NEC and all local codes. l These “ Minimum Circuit Ampacity ” values are to be used for sizing the field power conductors. Refer to the National Electric ...

  • Bard WA491 - page 8

    Manual 2100-398 Page 6 FILTERS A one inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A one inch washable filter and two inch pleated filter are also available as optional accessories. The internal filter brackets a ...

  • Bard WA491 - page 9

    Manual 2100-398 Page 7 INST ALLA TION INSTRUCTIONS W ARNING Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death. WALL MOUNTING INFORMATION 1. Two holes for the supply and return air openings must be cut through the wall as shown i ...

  • Bard WA491 - page 10

    Manual 2100-398 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS-416 ...

  • Bard WA491 - page 11

    Manual 2100-398 Page 9 FIGURE 4 ELECTRIC HEAT CLEARANCE SIDE SECTION VIEW OF SUPPL Y AIR DUCT FOR W ALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURF ACES. MIS-277 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is i ...

  • Bard WA491 - page 12

    Manual 2100-398 Page 10 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS-548 MIS-549 SEE FIGURE 3 – MOUNTING INSTRUCTIONS SUPPLY AIR OPENING RETURN AIR OPENING RETURN AIR OPENING SUPPLY AIR OPENING BOTTOM MOUNTING BRACKET. MOUNT ON WALL BEFORE INSTALLING UNIT. RETURN AIR OPENING SUPPLY AIR OPENING WALL STRUCTURE FACTORY ...

  • Bard WA491 - page 13

    Manual 2100-398 Page 11 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS-550 ...

  • Bard WA491 - page 14

    Manual 2100-398 Page 12 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of el ...

  • Bard WA491 - page 15

    Manual 2100-398 Page 13 FIGURE 8 UNIT 24V TERMINAL BOARD MIS-1373A ...

  • Bard WA491 - page 16

    Manual 2100-398 Page 14 ST ART UP IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. HIGH PRESSURE SWITCH The WA381, WA484, WA491 and WA602 models are supplied with a remote reset high pressure switch. If tripped, this pressure switch may be reset by turning the thermostat off then back on ...

  • Bard WA491 - page 17

    Manual 2100-398 Page 15 SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase of constant air circulation. On all 230 vo ...

  • Bard WA491 - page 18

    Manual 2100-398 Page 16 REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. 3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws. FIGURE 9 FAN BLADE SETTING TROUBLESHOOTING 4. Unwire condenser fan motor. 5. Slide complete motor, f ...

  • Bard WA491 - page 19

    Manual 2100-398 Page 17 TABLE 7A INDOOR BLOWER PERFORMANCE CFM @ 230V / 460V . P . S . E n I H 2 O 1 8 3 A W1 9 4 A W d e e p S h g i Hd e e p S m u i d e Md e e p S w o Ld e e p S h g i Hd e e p S m u i d e M y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C ...

  • Bard WA491 - page 20

    Manual 2100-398 Page 18 Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions. NOTE: Pressure table based on high ...

  • Bard WA491 - page 21

    Manual 2100-398 Page 19 TABLE 11 OPTIONAL ACCESSORIES WA381-A WA381-B WA381-C WA423-A WA423-B WA423-C WA484-A WA484-B WA484-C WA491-A WA491-B WA491-C WA602-A WA602-B WA602-C t r a P r e b m u Nn o i t p i r c s e D 5 0 A - 5 0 A W H E 8 0 A - 5 0 A W H E 0 1 A - 5 0 A W H E 5 1 A - 5 0 A W H E s e g a k c a P r e t a e H s e g a k c a P r e t a e H ...

Fabricante Bard Categoría Air Conditioner

Los documentos del dispositivo Bard WA491 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Bard
- manuales de instrucciones WA491
- hojas de producto Bard
- folletos informativos
- o etiquetas energéticas Bard WA491
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Bard WA491.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Bard WA491, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Bard WA491. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Bard WA491.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Bard WA491, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Bard WA491. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Bard WA491.

El manual de instrucciones completo de Bard debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Bard WA491 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Bard WA491, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Bard WA491 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Bard WA491 - que deben facilitarnos los primeros pasos durante el uso de Bard WA491
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Bard WA491
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Bard WA491 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Bard WA491?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Bard WA491, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Bard WA491 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)