    INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS W A381 W A423 W A484 W A491 W A602 Manual : 2100-398 Supersedes: File: V olume III T ab 16 Date: 01-28-02 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. © Copyright 2002 ...

  • Bard WA491 - page 2

    Contents Figures Figure 1 Unit Dimensions ...................................... 3 Figure 2 Fresh Air Damper Assembly ................... 6 Figure 3 Mounting Instructions .............................. 8 Figure 4 Electric Heat Clearance .......................... 9 Figure 5 W all Mounting Instructions .................... 10 Figure 6 W all Mounting ...

  • Bard WA491 - page 3

    Manual 2100-398 Page 1 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code ...................... ANSI/NFPA 70 ...

  • Bard WA491 - page 4

    Manual 2100-398 Page 2 W ALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE W A 42 3 – A 10 X N X X X A NOTE: All vent options are without exhaust capability. May require separate field supplied barometric relief in building. TABLE 1 ELECTRIC HEAT TABLE s l e d o M A - 1 8 3 A W A - 3 2 4 A W A - 4 8 4 A W A - 1 9 4 A W A - 2 ...

  • Bard WA491 - page 5

    Manual 2100-398 Page 3 MIS-1262 FIGURE 1 UNIT DIMENSIONS l e d o M h t d i W ) W ( h t p e D ) D ( t h g i e H ) H ( y l p p u Sn r u t e R EF G I J K L M N O P Q R S T A BCB 8 3 A W 2 4 A W 8 4 A W 9 4 A W 0 6 A W 5 7 0 . 2 42 3 4 . 2 25 7 8 . 4 88 8 . 98 8 . 9 28 8 . 5 18 8 . 9 28 8 . 3 40 1 . 9 16 6 . 1 30 0 . 0 38 6 . 2 34 9 . 6 29 6 . 4 33 4 . ...

  • Bard WA491 - page 6

    Manual 2100-398 Page 4 j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. k Based on 75 ° C copper wire. All wiring must conform to NEC and all local codes. l These “ Minimum Circuit Ampacity ” values are to be used for sizing the field power conductors. Refer to the National Electric ...

  • Bard WA491 - page 7

    Manual 2100-398 Page 5 j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. k Based on 75 ° C copper wire. All wiring must conform to NEC and all local codes. l These “ Minimum Circuit Ampacity ” values are to be used for sizing the field power conductors. Refer to the National Electric ...

  • Bard WA491 - page 8

    Manual 2100-398 Page 6 FILTERS A one inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A one inch washable filter and two inch pleated filter are also available as optional accessories. The internal filter brackets a ...

  • Bard WA491 - page 9

    Manual 2100-398 Page 7 INST ALLA TION INSTRUCTIONS W ARNING Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death. WALL MOUNTING INFORMATION 1. Two holes for the supply and return air openings must be cut through the wall as shown i ...

  • Bard WA491 - page 10

    Manual 2100-398 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS-416 ...

  • Bard WA491 - page 11

    Manual 2100-398 Page 9 FIGURE 4 ELECTRIC HEAT CLEARANCE SIDE SECTION VIEW OF SUPPL Y AIR DUCT FOR W ALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURF ACES. MIS-277 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3 feet of ducting. It is i ...

  • Bard WA491 - page 12

    Manual 2100-398 Page 10 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS-548 MIS-549 SEE FIGURE 3 – MOUNTING INSTRUCTIONS SUPPLY AIR OPENING RETURN AIR OPENING RETURN AIR OPENING SUPPLY AIR OPENING BOTTOM MOUNTING BRACKET. MOUNT ON WALL BEFORE INSTALLING UNIT. RETURN AIR OPENING SUPPLY AIR OPENING WALL STRUCTURE FACTORY ...

  • Bard WA491 - page 13

    Manual 2100-398 Page 11 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS-550 ...

  • Bard WA491 - page 14

    Manual 2100-398 Page 12 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of el ...

  • Bard WA491 - page 15

    Manual 2100-398 Page 13 FIGURE 8 UNIT 24V TERMINAL BOARD MIS-1373A ...

  • Bard WA491 - page 16

    Manual 2100-398 Page 14 ST ART UP IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. HIGH PRESSURE SWITCH The WA381, WA484, WA491 and WA602 models are supplied with a remote reset high pressure switch. If tripped, this pressure switch may be reset by turning the thermostat off then back on ...

  • Bard WA491 - page 17

    Manual 2100-398 Page 15 SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase of constant air circulation. On all 230 vo ...

  • Bard WA491 - page 18

    Manual 2100-398 Page 16 REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. 3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws. FIGURE 9 FAN BLADE SETTING TROUBLESHOOTING 4. Unwire condenser fan motor. 5. Slide complete motor, f ...

  • Bard WA491 - page 19

    Manual 2100-398 Page 17 TABLE 7A INDOOR BLOWER PERFORMANCE CFM @ 230V / 460V . P . S . E n I H 2 O 1 8 3 A W1 9 4 A W d e e p S h g i Hd e e p S m u i d e Md e e p S w o Ld e e p S h g i Hd e e p S m u i d e M y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C ...

  • Bard WA491 - page 20

    Manual 2100-398 Page 18 Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions. NOTE: Pressure table based on high ...

  • Bard WA491 - page 21

    Manual 2100-398 Page 19 TABLE 11 OPTIONAL ACCESSORIES WA381-A WA381-B WA381-C WA423-A WA423-B WA423-C WA484-A WA484-B WA484-C WA491-A WA491-B WA491-C WA602-A WA602-B WA602-C t r a P r e b m u Nn o i t p i r c s e D 5 0 A - 5 0 A W H E 8 0 A - 5 0 A W H E 0 1 A - 5 0 A W H E 5 1 A - 5 0 A W H E s e g a k c a P r e t a e H s e g a k c a P r e t a e H ...

Fabbricante Bard Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoBard WA491 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bard
- manuali per l’uso WA491
- schede prodotto Bard
- opuscoli
- o etichette energetiche Bard WA491
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bard WA491.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bard WA491, manuali di manutenzione, brevi manuali o manuali utente Bard WA491. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bard WA491.

Manuali per l’uso simili

Manuale completo del dispositivo Bard WA491, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bard WA491 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bard WA491.

Il manuale per l’uso completo Bard, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bard WA491 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bard WA491, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bard WA491 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bard WA491 - che ci dovrebbe aiutare nei primi passi durante l'uso Bard WA491
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bard WA491
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bard WA491 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bard WA491?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bard WA491 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bard WA491 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)