Manual de instrucciones Bryant 697C

36 de páginas 0.18 mb
Descargar

Pasar a la página of 36

Summary
  • Bryant 697C - page 1

    Form No. PDS 697C.18.3B SPLIT-SYSTEM HEAT PUMP UNITS 697C (60 HZ) Sizes 018 thru 060 The AeroQuiet System (AQS) consists of 4 design features to achieve ultra-low sound ratings. Aerocoustic Design featuring the Aeromax opening and wire dome top results in quieter and more efficient operation. Energy-Efficient Fan and Fan Motor provide a slower fan ...

  • Bryant 697C - page 2

    —2— DIMENSIONS A94148 ACCESS PANEL 1 1 / 4 "  1. Allow 30 in. clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. Minimum outdoor operating ambient in cooling mode is 55 ° F (unless low ambient control is used) max 125 ° F. 2. Maximum o ...

  • Bryant 697C - page 3

    —3— RECOMMENDED TUBE DIAMETERS * For tube set over 50 ft, consult Long-Line Application Guideline. METERING DEVICE * TXV must be installed when indoor coil is not equipped with a TXV. TXV listed is for any approved coil combination. All TXVs are bi-flow, hard shutoff. UNIT SIZE TUBE LENGTH (Ft)* LIQUID TUBE DIAMETER (In.) VAPOR TUBE DIAMETER (I ...

  • Bryant 697C - page 4

    —4— SPECIFICATIONS See notes on page 5. UNIT SIZE-SERIES 018-B 024-B 030-B 036-B 042-B Operating Weight (Lb) 198 198 221 211 231 ELECTRICAL Unit Volts-Hertz-Phase 208/230-60-1 Operating Voltage Range 187—253 Unit Ampacity for Wire Sizing 16.1 17.5 18.7 21.0 32.0 Min Wire Size (60 ° C/75 ° C Copper) (AWG)* 14/14 14/14 14/14 12/12 8/10 Maximu ...

  • Bryant 697C - page 5

    —5— SPECIFICATIONS Continued * If wire is applied at ambient greater than 30 ° C (86 ° F), consult T ab le 310-16 of the NEC (ANSI/NFP A 70). If other than uncoated (non-plated), 60 ° or 75 ° C (140 ° or 167 ° F) insulation, copper wire (solid wire f or 10 A WG and smaller , str anded wire f or larger than 10 AWG) is used, consult applica ...

  • Bryant 697C - page 6

    —6— ACCESSORY USAGE GUIDELINE * For tubing line sets between 50 and 175 ft, refer to Residential’s Split System Long-Line Application Guidelines. † For buried line applications, refer to Residential’s Split Systems Buried Line Application Guidelines. ‡ Only when low-pressure switch is used. ACCESSORY DESCRIPTION AND USAGE (Listed Alphab ...

  • Bryant 697C - page 7

    —7— ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued 1 3. Secondary Outdoor Thermostat An SPDT temperature actuated switch which turns on a third stage of supplemental electric heaters when outdoor air temperature drops below the second- stage set point. SUGGESTED USE: Heat pump installations where 3-stage operation of suppleme ...

  • Bryant 697C - page 8

    —8— COMBINA TION RA TINGS* See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP 018-B 72 FC4 ...

  • Bryant 697C - page 9

    —9— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP 02 ...

  • Bryant 697C - page 10

    —1 0— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP ...

  • Bryant 697C - page 11

    —1 1— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP ...

  • Bryant 697C - page 12

    —1 2— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP ...

  • Bryant 697C - page 13

    —1 3— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP ...

  • Bryant 697C - page 14

    —1 4— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP ...

  • Bryant 697C - page 15

    —1 5— COMBINA TION RA TINGS* Continued * Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on: Cooling Standard: 80 ° F (27 ° C) db 67 ° F (19 ° C) wb indoor entering air temperature and 95 ° F (35 ° C) db air entering outdoor unit. High-Temp Heating Standa ...

  • Bryant 697C - page 16

    —1 6— 697C BALANCE POINT WORKSHEET BUILDING HEAT LOSS, 1000 BTU/HR UNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HR Printed in U.S.A. 11-95 838-756 OUTDOOR TEMPERATURE, °F -10 0 10 20 30 40 50 60 70 80 2.9 5.9 8.8 11.7 14.7 17.6 20.5 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT. AIR AT 70°F AND AT RATED CFM 23.4 80 697CN024-A/B FC4BNF030 697CN030 ...

  • Bryant 697C - page 17

    —1 7— DET AILED COOLING CAP ACITIES* See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw* ...

  • Bryant 697C - page 18

    —1 8— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Tota ...

  • Bryant 697C - page 19

    —1 9— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 20

    —2 0— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 21

    —2 1— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System KW** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 22

    —2 2— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 23

    —2 3— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 24

    —2 4— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 25

    —2 5— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 26

    —2 6— DET AILED COOLING CAP ACITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-89. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. † Total and sensible capacities are net capacities. Blower ...

  • Bryant 697C - page 27

    —2 7— HEA T PUMP HEA TING PERFORMANCE See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 76 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacit ...

  • Bryant 697C - page 28

    —2 8— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 76 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total P ...

  • Bryant 697C - page 29

    —2 9— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr ...

  • Bryant 697C - page 30

    —3 0— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr ...

  • Bryant 697C - page 31

    —3 1— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr ...

  • Bryant 697C - page 32

    —3 2— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr ...

  • Bryant 697C - page 33

    —3 3— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr ...

  • Bryant 697C - page 34

    —3 4— HEA T PUMP HEA TING PERFORMANCE Continued * The Btuh heating capacity values shown are net “integrated’’ values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity. † The kw values include the compressor, outdoor fan motor, and ...

  • Bryant 697C - page 35

    —3 5— System Design 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55 ° F (12.8 ° C). 3. Maximum outdoor operating air temperature for cooling m ...

  • Bryant 697C - page 36

    —3 6— SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 697C.18.2B ©1997 Bryant Heating & Cooling Systems, 7310 W. Morris Street, Indianapolis, IN 46231 PRINTED IN U.S.A. Catalog No. BY-3269-711 3-97 SERVICE TRAINING Packaged Service Training programs are an exc ...

Fabricante Bryant Categoría Heat Pump

Los documentos del dispositivo Bryant 697C que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Bryant
- manuales de instrucciones 697C
- hojas de producto Bryant
- folletos informativos
- o etiquetas energéticas Bryant 697C
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Bryant 697C.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Bryant 697C, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Bryant 697C. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Bryant 697C.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Bryant 697C, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Bryant 697C. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Bryant 697C.

El manual de instrucciones completo de Bryant debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Bryant 697C - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Bryant 697C, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Bryant 697C que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Bryant 697C - que deben facilitarnos los primeros pasos durante el uso de Bryant 697C
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Bryant 697C
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Bryant 697C en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Bryant 697C?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Bryant 697C, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Bryant 697C probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)