    Form No. PDS 697C.18.3B SPLIT-SYSTEM HEAT PUMP UNITS 697C (60 HZ) Sizes 018 thru 060 The AeroQuiet System (AQS) consists of 4 design features to achieve ultra-low sound ratings. Aerocoustic Design featuring the Aeromax opening and wire dome top results in quieter and more efficient operation. Energy-Efficient Fan and Fan Motor provide a slower fan ...

  • Bryant 697C - page 2

    —2— DIMENSIONS A94148 ACCESS PANEL 1 1 / 4 "  1. Allow 30 in. clearance to service end of unit, 48 in. above unit, 6 in. on one side, 12 in. on remaining side, and 24 in. between units for proper airflow. Minimum outdoor operating ambient in cooling mode is 55 ° F (unless low ambient control is used) max 125 ° F. 2. Maximum o ...

  • Bryant 697C - page 3

    —3— RECOMMENDED TUBE DIAMETERS * For tube set over 50 ft, consult Long-Line Application Guideline. METERING DEVICE * TXV must be installed when indoor coil is not equipped with a TXV. TXV listed is for any approved coil combination. All TXVs are bi-flow, hard shutoff. UNIT SIZE TUBE LENGTH (Ft)* LIQUID TUBE DIAMETER (In.) VAPOR TUBE DIAMETER (I ...

  • Bryant 697C - page 4

    —4— SPECIFICATIONS See notes on page 5. UNIT SIZE-SERIES 018-B 024-B 030-B 036-B 042-B Operating Weight (Lb) 198 198 221 211 231 ELECTRICAL Unit Volts-Hertz-Phase 208/230-60-1 Operating Voltage Range 187—253 Unit Ampacity for Wire Sizing 16.1 17.5 18.7 21.0 32.0 Min Wire Size (60 ° C/75 ° C Copper) (AWG)* 14/14 14/14 14/14 12/12 8/10 Maximu ...

  • Bryant 697C - page 5

    —5— SPECIFICATIONS Continued * If wire is applied at ambient greater than 30 ° C (86 ° F), consult T ab le 310-16 of the NEC (ANSI/NFP A 70). If other than uncoated (non-plated), 60 ° or 75 ° C (140 ° or 167 ° F) insulation, copper wire (solid wire f or 10 A WG and smaller , str anded wire f or larger than 10 AWG) is used, consult applica ...

  • Bryant 697C - page 6

    —6— ACCESSORY USAGE GUIDELINE * For tubing line sets between 50 and 175 ft, refer to Residential’s Split System Long-Line Application Guidelines. † For buried line applications, refer to Residential’s Split Systems Buried Line Application Guidelines. ‡ Only when low-pressure switch is used. ACCESSORY DESCRIPTION AND USAGE (Listed Alphab ...

  • Bryant 697C - page 7

    —7— ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued 1 3. Secondary Outdoor Thermostat An SPDT temperature actuated switch which turns on a third stage of supplemental electric heaters when outdoor air temperature drops below the second- stage set point. SUGGESTED USE: Heat pump installations where 3-stage operation of suppleme ...

  • Bryant 697C - page 8

    —8— COMBINA TION RA TINGS* See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP 018-B 72 FC4 ...

  • Bryant 697C - page 9

    —9— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP 02 ...

  • Bryant 697C - page 10

    —1 0— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP ...

  • Bryant 697C - page 11

    —1 1— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP ...

  • Bryant 697C - page 12

    —1 2— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP ...

  • Bryant 697C - page 13

    —1 3— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP ...

  • Bryant 697C - page 14

    —1 4— COMBINA TION RA TINGS* Continued See notes on page 15. UNIT SIZE- SERIES AND SOUND RATING (dBA) INDOOR UNIT ARI STANDARD RATINGS* Cooling Heating TC Seasonal Efficiency SEER High-Temp Low-Temp Seasonal Efficiency HSPF/HSPF with LSV Factory- Supplied Enhance- ment Standard Rating Field-Supplied Accessory‡ TXV TXV&TDR** TC COP TC COP ...

  • Bryant 697C - page 15

    —1 5— COMBINA TION RA TINGS* Continued * Ratings are net values reflecting the effects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on: Cooling Standard: 80 ° F (27 ° C) db 67 ° F (19 ° C) wb indoor entering air temperature and 95 ° F (35 ° C) db air entering outdoor unit. High-Temp Heating Standa ...

  • Bryant 697C - page 16

    —1 6— 697C BALANCE POINT WORKSHEET BUILDING HEAT LOSS, 1000 BTU/HR UNIT INTEGRATED HEATING CAPACITY, 1000 BTU/HR Printed in U.S.A. 11-95 838-756 OUTDOOR TEMPERATURE, °F -10 0 10 20 30 40 50 60 70 80 2.9 5.9 8.8 11.7 14.7 17.6 20.5 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT. AIR AT 70°F AND AT RATED CFM 23.4 80 697CN024-A/B FC4BNF030 697CN030 ...

  • Bryant 697C - page 17

    —1 7— DET AILED COOLING CAP ACITIES* See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw* ...

  • Bryant 697C - page 18

    —1 8— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Total Sys. Kw** Capacity MBtuh† Tota ...

  • Bryant 697C - page 19

    —1 9— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 20

    —2 0— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 21

    —2 1— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System KW** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 22

    —2 2— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 23

    —2 3— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 24

    —2 4— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 25

    —2 5— DET AILED COOLING CAP ACITIES* Continued See notes on page 26. EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES ° F 85 95 105 115 CFM EWB Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Capacity MBtuh† Total System Kw** Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ ...

  • Bryant 697C - page 26

    —2 6— DET AILED COOLING CAP ACITIES* Continued * Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-89. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur. † Total and sensible capacities are net capacities. Blower ...

  • Bryant 697C - page 27

    —2 7— HEA T PUMP HEA TING PERFORMANCE See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 76 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacit ...

  • Bryant 697C - page 28

    —2 8— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 76 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total P ...

  • Bryant 697C - page 29

    —2 9— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr ...

  • Bryant 697C - page 30

    —3 0— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr ...

  • Bryant 697C - page 31

    —3 1— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr ...

  • Bryant 697C - page 32

    —3 2— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr ...

  • Bryant 697C - page 33

    —3 3— HEA T PUMP HEA TING PERFORMANCE Continued See notes on page 34. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERATURES ° F – 3 7 1 72 73 74 75 7 EDB CFM Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr Capacity (MBtuh) Total Pwr ...

  • Bryant 697C - page 34

    —3 4— HEA T PUMP HEA TING PERFORMANCE Continued * The Btuh heating capacity values shown are net “integrated’’ values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capacity. † The kw values include the compressor, outdoor fan motor, and ...

  • Bryant 697C - page 35

    —3 5— System Design 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature for cooling mode without low-ambient operation accessory is 55 ° F (12.8 ° C). 3. Maximum outdoor operating air temperature for cooling m ...

  • Bryant 697C - page 36

    —3 6— SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 697C.18.2B ©1997 Bryant Heating & Cooling Systems, 7310 W. Morris Street, Indianapolis, IN 46231 PRINTED IN U.S.A. Catalog No. BY-3269-711 3-97 SERVICE TRAINING Packaged Service Training programs are an exc ...

Manufacturer Bryant Category Heat Pump

Documents that we receive from a manufacturer of a Bryant 697C can be divided into several groups. They are, among others:
- Bryant technical drawings
- 697C manuals
- Bryant product data sheets
- information booklets
- or energy labels Bryant 697C
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bryant 697C.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bryant 697C, service manual, brief instructions and user manuals Bryant 697C. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bryant 697C.

Similar manuals

A complete manual for the device Bryant 697C, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bryant 697C by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bryant 697C.

A complete Bryant manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bryant 697C - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bryant 697C, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bryant 697C, that we can find in the current document
3. Tips how to use the basic functions of the device Bryant 697C - which should help us in our first steps of using Bryant 697C
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bryant 697C
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bryant 697C in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bryant 697C?

Use the form below

If you did not solve your problem by using a manual Bryant 697C, ask a question using the form below. If a user had a similar problem with Bryant 697C it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)