    TECHNICAL GUIDE AFFINITY SPLIT -SYSTEM AIR CONDITIONERS 13 SEER – R-410A MODELS: CZB018 THRU 060 (1.5 THRU 5 NOMINAL TONS ) Due to continuous pr od uct improvement, sp eci fications are subject to change without n otice. Visit us on the web at www .yor k.com Additional rating informa tion can be foun d at www .ari.or g/aridirector y LISTED ISO 90 ...

  • York CZB018 THRU 060 - page 2

    246723-YTG-J-1006 2 Unitary Products Group All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. PHYSICAL AND ELECTRICAL DA T A MODEL CZB0181 1 CZB0241 1 C ZB0301 1 CZB0361 1 C ZB0421 1 CZB0481 1 CZB0601 1 Unit Supply V oltage 208-230V , 1 φ, 60Hz Normal V oltage Range 1 187 to ...

  • York CZB018 THRU 060 - page 3

    246723-YTG-J-1006 Unitary Products Group 3 Additional R-410A Charge / TXV Size f or V arious Matche d Sy stems Out door Unit CZB0181 1 CZB0241 1 C ZB0301 1 CZB0361 1 C ZB0421 1 CZB0481 1 CZB0601 1 Unit Orifice (s) 1 TVM901 1 TVM903 1 T VM903 1 TVM903 1 TVM904 1T V M 4 C 1 1 T VM905 1 TVM905 Factory R-410A Charge, lbs- oz 5-13 6-4 7-4 6-4 8-13 8-12 ...

  • York CZB018 THRU 060 - page 4

    246723-YTG-J-1006 4 Unitary Products Group PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refrig erant for the condenser, the smallest evaporator and 15 feet of intercon- necting line tubing. 2. V erify the TXV and additional char ge required for specific evaporator coil in th e system using the above table. 3. Additional ...

  • York CZB018 THRU 060 - page 5

    246723-YTG-J-1006 Unitary Products Group 5 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL ELECTRIC HEA T KW 2 W RA TED CFM NET MBH SEER EER TOT AL SENS. 1 PH 13 SEER AC WITH MA CZB0181 1 MA08B 2,5,8,10 17 FC/MC18B 600 18.0 12.1 13.00 1 1.00 MA08B 2,5,8,10 17 FC/MC24B 600 18.0 12.1 13.00 1 1.00 MA08B 2,5 ...

  • York CZB018 THRU 060 - page 6

    246723-YTG-J-1006 6 Unitary Products Group 1 PH 13 SEER AC WITH AHP/ SHP / F*FP CZB0181 1 AHP18 2,5,8 17 – 600 18.0 12.1 13.00 1 1.00 AHP24 2,5,8,10 17 – 600 18.0 12.3 13.00 1 1.00 F*FP024 5,8,1 0 17 – 600 18.0 12.1 13.00 1 1.00 CZB0241 1 AHP24 2,5,8,10 17 – 800 23.0 16.9 13.00 1 1.00 F*FP030 5,8,10,15 17 – 800 23.0 16.7 13.00 1 1.00 CZB0 ...

  • York CZB018 THRU 060 - page 7

    246723-YTG-J-1006 Unitary Products Group 7 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER 1,2 EER TOT AL SENS. CZB0181 1 450 750 14,17 FC/MC/PC/UC18 600 18.0 12.1 13.00 1 1.00 14,17 FC/MC/PC/UC24 600 18.0 12.1 13.00 1 1.00 14,17 FC/MC/ ...

  • York CZB018 THRU 060 - page 8

    246723-YTG-J-1006 8 Unitary Products Group COOLING CAP ACITY - With V ariable Spe ed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER AC WITH V ARIABLE SPEED FURNACES 2 CZB0181 1 PV8*A12 FC/MC/PC24A 14 600 18.0 12.2 14.00 1 1.50 PV9*A12 FC/MC/PC24A 14 600 18.0 12.2 14.0 ...

  • York CZB018 THRU 060 - page 9

    246723-YTG-J-1006 Unitary Products Group 9 CZB0421 1 PV8*C16 FC/MC/PC48C 21 1400 41 .0 30.2 13 .50 1 1.00 PV8*C20 FC/MC/PC48C 21 1400 41 .0 30.2 13 .50 1 1.00 PV9*C16 FC/MC/PC48C 21 1400 41 .0 30.2 13 .50 1 1.00 PV9*C20 FC/MC/PC48C 21 1400 41 .0 30.2 13 .50 1 1.00 PV9*D20 FC/MC/PC48D 24 1400 41 .0 30.2 13 .50 1 1.00 PV8*C20 HC60 21 1400 40.5 29.8 1 ...

  • York CZB018 THRU 060 - page 10

    246723-YTG-J-1006 10 Unitary Products Group ACCESSORIES* Hard St art Kit (024-31994-000, 024-319 95-000) - Provides increased starting torque for areas w ith low voltage. TXV Kits - 1 TV09 series thermal exp ans ion valves precisely meter refrigerant for optimum performance Low Ambient Pressure Switch Kit (2LA 06700424) - Allows use of air conditio ...

  • York CZB018 THRU 060 - page 11

    246723-YTG-J-1006 Unitary Products Group 11 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible cap acity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York CZB018 THRU 060 - page 12

    246723-YTG-J-1006 12 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increa ses by 1060 BTUH per 100 0 CFM per degree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree be ...

  • York CZB018 THRU 060 - page 13

    246723-YTG-J-1006 Unitary Products Group 13 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible cap acity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York CZB018 THRU 060 - page 14

    246723-YTG-J-1006 14 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increa ses by 1060 BTUH per 100 0 CFM per degree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree be ...

  • York CZB018 THRU 060 - page 15

    246723-YTG-J-1006 Unitary Products Group 15 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible cap acity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York CZB018 THRU 060 - page 16

    246723-YTG-J-1006 16 Unitary Products Group Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increa ses by 1060 BTUH per 100 0 CFM per degree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree be ...

  • York CZB018 THRU 060 - page 17

    246723-YTG-J-1006 Unitary Products Group 17 Multipliers for determining th e performance with other indoor sec tions. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible cap acity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York CZB018 THRU 060 - page 18

    246723-YTG-J-1006 18 Unitary Products Group NOTES ...

  • York CZB018 THRU 060 - page 19

    246723-YTG-J-1006 Unitary Products Group 19 NOTES ...

  • York CZB018 THRU 060 - page 20

    Subject to change without notice. Printe d in U.S.A. 246723-YTG-J-1006 Copyright © by York International/JCI 2006. All righ ts reserved. Supersedes: 246723-YTG-H-0906 Unitary 5005 Norman Product s Y ork OK Group Drive 73069 NOTES ...

Fabricante York Categoría Air Conditioner

Los documentos del dispositivo York CZB018 THRU 060 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos York
- manuales de instrucciones CZB018 THRU 060
- hojas de producto York
- folletos informativos
- o etiquetas energéticas York CZB018 THRU 060
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones York CZB018 THRU 060.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje York CZB018 THRU 060, instrucciones de servicio, instrucciones cortas o instrucciones de usuario York CZB018 THRU 060. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto York CZB018 THRU 060.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo York CZB018 THRU 060, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar York CZB018 THRU 060. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de York CZB018 THRU 060.

El manual de instrucciones completo de York debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual York CZB018 THRU 060 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice York CZB018 THRU 060, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de York CZB018 THRU 060 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo York CZB018 THRU 060 - que deben facilitarnos los primeros pasos durante el uso de York CZB018 THRU 060
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con York CZB018 THRU 060
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de York CZB018 THRU 060 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de York CZB018 THRU 060?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con York CZB018 THRU 060, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con York CZB018 THRU 060 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)