    Battery Inst allation MGE™ Galaxy™ 3 00 10-40 kV A 380/400/415 V 10-40 kVA ...

  • APC 300 - page 2

    ...

  • APC 300 - page 3

    Content s MGE™ Galaxy ™ 300 10-40 kVA 3: 3 - 380/400 /415 V, 10-30 kVA 3:1 - 380/4 00/415 V Installatio n i Overview . ............. ......... ............. ...... ...... ......... ............. .... 1 IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Product Overview...... ... ...

  • APC 300 - page 4

    MGE™ Ga laxy™ 300 1 0-40 kVA 3:3 - 380 /400/415 V , 10-30 kVA 3:1 - 3 80/400/415 V Insta llation ii Checklist.... ............. ...... ......... ............. ......... ............. ...... 15 Appendi x .......... ............ ...... ....... ......... ............ ....... ...... ... 16 One-line diagrams . . . . . . . . . . . . . . . . . . . . . ...

  • APC 300 - page 5

    1 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation Overview IMPORT ANT SAFETY INSTRUCTIONS - SA VE THESE INSTRUCTIONS W arning: ALL safety i nstructions in t he Safety S heet (990-3620 ) must be r ead, understo od and followed when ins t alli ng the UPS and XR Battery e nclsour e(s). Failur e to do so c ould r esu ...

  • APC 300 - page 6

    MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 2 Product Overview  Battery shelves  Battery circuit breaker  Ground cable conn ect ion (from the UP S)  Battery temperature sensor (A TIZ)  Connection terminal Front view         ...

  • APC 300 - page 7

    3 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation Cables and Batteries Note: The batter y enclosure mu st be inst alled on a non-i nflammable, level and solid floor . Prep are for Cab les 1. Open the fr ont door . 2. Remove both si de panels . Front view    Front view ...

  • APC 300 - page 8

    MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 4 Battery enclos ure with p re-inst alled batteries W arning: Remove al l card board used to pr otect the batter ies during transport. Make sur e that cables and coppe r bars are se parated. Note: A maximum of t wo batter y enclosures can be connect ed to the UPS (one ...

  • APC 300 - page 9

    5 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation 2. Connect th e batteries to the batt ery breaker by running t he cables from the ba ttery br eaker to each shel ve. Note! Make sure to run th e cab les in this order . Battery enclos ure withou t pre-install ed batteries W arning: APC by Schne ider is no t re spo ...

  • APC 300 - page 10

    MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 6 Note: A maximum of t wo batter y enclosures can be connect ed to the UPS (one XR Bat tery enclos ure with a circ uit breake r plus one en closure wi thout a circuit b r eaker ) by a batch cable betwe en the UPS an d the circuit br eaker in th e batter y enclosure. 1 ...

  • APC 300 - page 11

    7 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation Connect Co mmunicatio n Cables between the UPS and Ba ttery En closure External battery tempera ture (A TIZ) and externa l battery breaker signal Note: The A TIZ c able is f or external bat tery tempe rature detect ion si gnal (cab le is pre- instal led). Note: Th ...

  • APC 300 - page 12

    MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 8 Connect the Battery Cable s between th e UPS and Battery Enclosure W arning: This pr ocedure de scribes how to connect t he initi al battery ca bles between the UPS and XR befor e star t-up. If the UPS is up running, se e “Connect an XR Batt ery Enclosur e to a ru ...

  • APC 300 - page 13

    9 MGE™ Galax y™ 300 10-4 0 kVA 3:3, 10-30 kVA 3:1 - 3 80/400 /415 V Inst allation 5. Connect th e battery cable s to the batter y terminal s in the UPS. See the UPS inst allation manual for info rmation on how to remove the I/ O sheet metal c over . 6. Re-insta ll the UPS covers. See the UPS installatio n manual for more information . Ba t t e ...

  • APC 300 - page 14

    MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 10 Connect an XR Battery Enclosure to a r unning UPS W arning: Befor e connecting an XR bat tery encl osure , ALL safety instructi ons in the Safety S heet (990-3620) must be r ead, understood and followed. Fai lur e to do so could re sult in equipment da mage, seriou ...

  • APC 300 - page 15

    11 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Electrica l Hazard: Check the DC volta ges with a DC volt age multimeter versus the bat t ery voltage before continui ng. 7. T urn the XR batter y breaker (QFB) to the ON ( closed) posit i on. 8. T urn the UPS back in to normal operati on: a. T urn the stati c bypa ...

  • APC 300 - page 16

    MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 12 Replace t he Batteries W arning: Befo re battery replace ment, A LL sa fety ins truc tions in the S afety S heet ( 990- 3620) must be r ead, understood and followed. Fa ilur e to do so could r esult in equ ipment damage, ser i ous i njury , or death. Caution: Batte ...

  • APC 300 - page 17

    13 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation S pecifications Battery Output Recommended Cable Sizes Caution: All wirin g must co mply with all appl icable nationa l and/or e lectrical co des. Note: AC cable si zes a re deter mined for : - the TNS s ystem for copper , singl e-core c ables, ty pe U1000 R02V , 1 ...

  • APC 300 - page 18

    MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 14 Recommended Bolt and Lug Size T orque sp ecifications Battery T erminal Bolt size T orque CSB 910-0631 c lip 910-0633 M6 5.4 NM (max 8.2 NM) YUASA 912-0001 M5 2.5 NM (max 6 NM) 910-0632 M6 4.8 NM (max 6 NM) ...

  • APC 300 - page 19

    15 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Checklist  Make sure th at all cardb oard and st rappings h ave been r emoved.  Check that the power wiring is torqued as described in the torque specification table above.  V erify clockw ise phase-r otation (BA T+, N and BA T -) and make sure t hat a neu ...

  • APC 300 - page 20

    MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 16 Appe ndix One-li ne diagrams Note: Use the bel ow table as a hel p to find t he diagram that f its your system. Note: - marked cables are a ssembled by the manufacturer . - marked cables are asse m ble d on site b y APC by Schneider or a sub contractor . Black di a ...

  • APC 300 - page 21

    17 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Battery cabling YUASA 15 kV A 60 min. No. Item Description Part no. Qty . A Battery Y uasa battery SWL 1 100 912-000 1 30 B Copper b ar 70*25*2 880-275 5 20 C Power cable W ire 16 mm 2 Ivory 380 mm 0W5032 3 D Power cable W ire 16 mm 2 Ivory 640 mm 0W5035 3 E Power ...

  • APC 300 - page 22

    MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 18 Battery cabling YUASA 20/30 kV A 60 min. No. Item Description Part no. Qty . A Battery Y uasa battery SWL 185 0 910-0632 30 B Copper bar 1 10*25*3 880-2754 14 C Power cable W ire 16 mm 2 Ivory 380 mm 0W5032 4 D Power cable W ire 16 mm 2 Ivory 64 0mm 0W5035 6 E P ow ...

  • APC 300 - page 23

    19 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Battery cabling YUASA 40 kV A 60 min. No. Item Description Part no. Qty . A Battery Y uasa battery SWL 1 100 912-0001 64 B Copper bar 70*25*2 880-2755 40 C Power cable W ire 16 mm 2 Ivory 380 mm 0W5032 4 D Power cable W ire 16 mm 2 Ivory 64 0mm 0W5035 12 E P ower c ...

  • APC 300 - page 24

    MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 20 Battery cabling CSB 15 kV A 60 min. No. Item Description Part no. Qty . A Batter y CSB bat tery GP121 20 910-0631 90 B Power cabl e Wire 10 BLK 12 0 mm 0W4946 72 C Power cabl e Wire A wg 10 BLK 520 mm 0W4969 6 D Power cabl e Wire A wg 10 BLK 640 mm 0W4 971 6 E Powe ...

  • APC 300 - page 25

    21 MGE™ Galaxy™ 3 00 10-40 k VA 3:3, 10-30 kVA 3 :1 - 380/400/415 V Installation Battery cabling CSB 30 kV A 60 min. No. Item Description Part no. Qty . A Batter y CSB bat tery GP123 40 910-0633 64 B Copper ba r Copper bar CU-ETP Bat tery G P12340 880-6019 36 C Power cable Wire 16mm 2 Ivory 520 mm 0W5033 12 D Power cable Wire 16mm 2 Iv ory 640 ...

  • APC 300 - page 26

    MGE™ Ga laxy™ 300 10-40 kVA 3:3, 10 -30 kVA 3:1 - 380/ 400/415 V Installation 22 Battery cabling CSB 40 kV A 60 min. No. Item Description Part no. Qty . A Batte ry CSB battery GP12340 910-0633 90 B Copper b ar Copper bar CU-ETP B attery GP 12340 880-6019 60 C Power cable W ire 16 mm 2 Ivory 52 0mm 0W5033 12 D Power cable W ire 16 mm 2 Ivory 64 ...

  • APC 300 - page 27

    ...

  • APC 300 - page 28

    6/2010 990-3617-001 *990-3617-001* APC W orldwide Customer Support Customer s upport for this or any other AP C product is avai lable at no char ge in any of the foll owing ways: • V isit th e APC W eb site to acce ss docu ments in t he APC Knowledge Base a nd to subm it custo m er support requests. – www .apc.com ( Corpora te Head quarters ) C ...

Fabricant APC Catégorie Battery Charger

Les documents que nous recevons du fabricant de l'appareilAPC 300 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques APC
- manuels d’utilisations 300
- fiches produit APC
- dépliants
- ou étiquettes-énergie APC 300
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation APC 300.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation APC 300, manuels d’entretien, brefs manuels ou manuels de l’utilisateur APC 300. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit APC 300.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil APC 300, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser APC 300 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs APC 300.

Le manuel d’utilisation complet APC, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel APC 300 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières APC 300, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lAPC 300 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil APC 300 - qui devraient nous aider dans les premières étapes lors de l'utilisation APC 300
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de APC 300
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service APC 300 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de APC 300?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec APC 300, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec APC 300 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)