    036-21031 -004 Rev. A (0603) FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE ® TECHNIC AL GUIDE STELLAR PLUS TM 12 SEER SPLIT -SYSTEM HEA T P UMPS MOD ELS: E*FH018 Thru E*FH06 0 (1.5 THRU 5 NOMINAL TONS) Due to cont inuous produc t improvem ent, specifi cations are subje ct to change w ithout notice. Vis it us on the web at www ...

  • York E*FH060 - page 2

    036-2103 1-004 Re v. A (0603 ) 2 Unitary Produ cts Grou p All dim ensions are in inches. They are subje ct to ch ange withou t notice. Certif ied dimens ions will be provide d upon request. PHYSICAL AND ELECTRICAL DA T A MODEL E4FH018 E4FH024 E4FH030 E4F H036 E4FH045 E5FH048 E4FH060 Unit Supply V olt age 208/230-1-60 Normal V olt age Range 1 1. Rat ...

  • York E*FH060 - page 3

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 3 PROCEDURES: 1. Unit factory charge list ed on the unit nameplate includes refigerant for the condenser , the smallest evaporator and for 15 f eet of intercon- necting line tubing. 2. V erify the orifice size and the additional charge required for the specific evaporator coil in the system using ...

  • York E*FH060 - page 4

    036-2103 1-004 Re v. A (0603 ) 4 Unitary Produ cts Grou p - = No t appl icab le COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 1. G2 FD co ils av ailab le wi th a f acto ry in sta lle d hori zont al drain pan. See p rice pag es for spec ific m ode l number . COO LING MODEL ELEC TRIC HEA T K W 2 2. Sing le phas e unit ...

  • York E*FH060 - page 5

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 5 * Require s a 2F D Blower T ime De lay unl ess a standa rd furn ace is e quipped with one . ** Refer to Qu ick Selection Chart for specific fu rnace m atch-u p. COOLING CAP ACITY - With Up flow , Downflow and Horizont al Furnace and Coils UNIT MODE L FURNACE** COIL MODEL COO LING NOMINAL AIRFLO ...

  • York E*FH060 - page 6

    036-2103 1-004 Re v. A (0603 ) 6 Unitary Produ cts Grou p HEA TING PERFORMANCE - Air Handler and Mu lti-position Coils UNIT MODE L COIL 1 MODE L ARI HEA TING 2 OUTD O O R TE M P 3 47 ° F 17 ° FH S P F- 3 ° F 7 ° F1 7 ° F 27 ° F 37 ° F 47 ° F5 7 ° F MBH COP MBH COP STD. V . S. MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW E4FH018 F2RP/F2 ...

  • York E*FH060 - page 7

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 7 COP equa ls MBH output divided b y (total KW inp ut x 3.4 12). HSPF ( Heating Seasonal Perfo rmanc e Factor) is the to tal heati ng outpu t duri ng a nor mal ann ual usa ge per iod for heating divided by t he total ele ctric power input du ring th e same period . — = Not Applicable. HEA TING ...

  • York E*FH060 - page 8

    036-2103 1-004 Re v. A (0603 ) 8 Unitary Produ cts Grou p ACCESSORIES Refer to Price Ma nual for sp ecific mod el numbe rs. St art Ass ist Kit (2SA067*) Blow er Ti me Del ay - Avail able to in crease ef fic iency whe n inst alled. Ins tal ls on indoor sec tion an d maint ains blowe r for approxi mately on e minute af ter c ooling therm osta t has b ...

  • York E*FH060 - page 9

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 9 TYPICAL INST ALLA TION TYPICAL FIELD WIRING - (AIR HANDLER / ELECTRICAL HEA T ) THERMOST A T TO INDOOR BLOWER TO COIL NEC CLASS 2 WIRING NEC CLASS 1 WIRING TO POWER SUPPL Y WEA THERPROOF DISCONNECT SWITCH Seal open ing(s) with per magum or equivalent 24” SERVICE ACCESS CLEARANCE 48” OVERHEA ...

  • York E*FH060 - page 10

    036-2103 1-004 Re v. A (0603 ) 10 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. NOTE: For dry bu lb te mpera ture s dif fer ent th an t hose liste d (bet ween 73-87 F), s e nsib le ca pac ity in crea ses b y 1060 BTUH pe r 10 00 CFM per deg ree ab ove t he listed tem pera ture an d decreas es by 1 ...

  • York E*FH060 - page 11

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 11 Multipliers for determining the performance with oth er indoor sections. NOTE: For dry b ulb tem peratu res differe nt than tho se list ed (be tween 7 3-87 F), sensibl e capacity increase s by 10 60 BTUH p er 100 0 CFM per de gree a bove th e lis t ed t e mper atur e and de cre a ses by 106 0 ...

  • York E*FH060 - page 12

    036-2103 1-004 Re v. A (0603 ) 12 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. NOTE: For dry bu lb te mpera ture s dif fer ent th an t hose liste d (bet ween 73-87 F), s e nsib le ca pac ity in crea ses b y 1060 BTUH pe r 10 00 CFM per deg ree ab ove t he listed tem pera ture an d decreas es by 1 ...

  • York E*FH060 - page 13

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 13 Multipliers for determining the performance with oth er indoor sections. NOTE: For dry b ulb tem peratu res differe nt than tho se list ed (be tween 7 3-87 F), sensibl e capacity increase s by 10 60 BTUH p er 100 0 CFM per de gree a bove th e lis t ed t e mper atur e and de cre a ses by 106 0 ...

  • York E*FH060 - page 14

    036-2103 1-004 Re v. A (0603 ) 14 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. NOTE: For dry bu lb te mpera ture s dif fer ent th an t hose liste d (bet ween 73-87 F), s e nsib le ca pac ity in crea ses b y 1060 BTUH pe r 10 00 CFM per deg ree ab ove t he listed tem pera ture an d decreas es by 1 ...

  • York E*FH060 - page 15

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 15 Multipliers for determining the performance with oth er indoor sections. NOTE: For dry b ulb tem peratu res differe nt than tho se list ed (be tween 7 3-87 F), sensibl e capacity increase s by 10 60 BTUH p er 100 0 CFM per de gree a bove th e lis t ed t e mper atur e and de cre a ses by 106 0 ...

  • York E*FH060 - page 16

    036-2103 1-004 Re v. A (0603 ) 16 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. NOTE: For dry bu lb te mpera ture s dif fer ent th an t hose liste d (bet ween 73-87 F), s e nsib le ca pac ity in crea ses b y 1060 BTUH pe r 10 00 CFM per deg ree ab ove t he listed tem pera ture an d decreas es by 1 ...

  • York E*FH060 - page 17

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 17 Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO. E4FH018S06 EV APORA TOR COIL MODEL NO. F 2RP/F2FP024 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 600 650 700 MBTUH K.W . C. O.P . MBTUH K. ...

  • York E*FH060 - page 18

    036-2103 1-004 Re v. A (0603 ) 18 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO. E4FH024S06 EV APORA TOR COIL MODEL NO. F 2RP/F2FP030 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 750 800 850 MBTUH K.W . C.O.P . MBTUH ...

  • York E*FH060 - page 19

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 19 Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E4FH30S06 EV APORA TOR COIL MODEL NO G2FD030(S,H)17 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 950 1050 1 150 MBTUH K.W . C. O.P . MBTUH K ...

  • York E*FH060 - page 20

    036-2103 1-004 Re v. A (0603 ) 20 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO. E4FH036S06 EV APORA TOR COIL MODEL NO. F 2RP/F2FP036 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 1 150 1250 1350 MBTUH K.W . C.O.P . MB ...

  • York E*FH060 - page 21

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 21 Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E4FH042S06 EV APORA TOR COIL MODEL NO F2RP/F2FP042 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 1200 1400 1000 MBTUH K.W . C. O.P . MBTUH K. ...

  • York E*FH060 - page 22

    036-2103 1-004 Re v. A (0603 ) 22 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E5FH048S06 EV APORA TOR COIL MODEL NO F2FP048 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 1450 1600 1750 MBTUH K.W . C.O.P . MBTUH K.W . ...

  • York E*FH060 - page 23

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 23 Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E4FH060S06 EV APORA TOR COIL MODEL NO G2FD060(S,H)24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 1700 1850 2000 MBTUH K.W . C. O.P . MBTUH ...

  • York E*FH060 - page 24

    Subject to change without notice. Printed in U.S.A. 036-21031-004 Rev. A (0603) Copyright © by Y ork International Corp. 2003. All rights reserved. Supersedes: 036-21031-003 Rev . A (0403) Unit ary 5005 Norma n Product Y ork OK Group Drive 7306 9 MA TCHING INDOOR COMP ONENTS G1UA 1/2 CASED UPFLOW G1HD HORIZONT AL DUCT G2FD* MUL TI-POSITION (UPFLOW ...

Fabricant York Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilYork E*FH060 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques York
- manuels d’utilisations E*FH060
- fiches produit York
- dépliants
- ou étiquettes-énergie York E*FH060
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation York E*FH060.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation York E*FH060, manuels d’entretien, brefs manuels ou manuels de l’utilisateur York E*FH060. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit York E*FH060.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil York E*FH060, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser York E*FH060 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs York E*FH060.

Le manuel d’utilisation complet York, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel York E*FH060 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières York E*FH060, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lYork E*FH060 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil York E*FH060 - qui devraient nous aider dans les premières étapes lors de l'utilisation York E*FH060
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de York E*FH060
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service York E*FH060 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de York E*FH060?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec York E*FH060, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec York E*FH060 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)