    www.rosemount.com ¢00825-0100-4801J¤ Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S Rosemount 3051S Series Pressure T ransmitter with HART ® Protocol Rosemount 3051SF Series Flowmeter T ransmitter with HART ® Protocol Sta r t End Step 1: Mount the T ransmitter Step 2: Consider Housing Rotation Step 3: Set Switch ...

  • Emerson 3051S - page 2

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 2 © 2010 Rose mount Inc. Al l right s reserved. Al l marks prop erty of owner . Rosemount and th e Rosemount logo type are register ed trademarks of Rosemount Inc. Rosemount Inc. 8200 Market Bou levard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906 - ...

  • Emerson 3051S - page 3

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 3 S TEP 1: M OUNT THE T RANSMITTER Liquid Flow Applications 1. Place tap s to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward. Gas Flow Applications 1. Place tap s in the top or side of ...

  • Emerson 3051S - page 4

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 4 S TEP 1 CO NTINU ED ... Panel Mount Pipe Mount Coplan ar ™ Flange T raditional Flange In-line Housings PlantWeb ™ Junction Box Remote Mount Display 4801_QIG_RevKB.fm Page 4 Fr iday , December 3, 2010 1:17 AM ...

  • Emerson 3051S - page 5

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 5 S TEP 1 CO NTINU ED ... Bolting Considerations If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. ...

  • Emerson 3051S - page 6

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 6 S TEP 1 CO NTINU ED ... Figure 2. T orque values for the flange and fla nge adapter bolts O-rings with Flange Adapte rs W ARNING Whenever the flanges or adapters are removed, visually inspect the o-rings. Replace them if there are any signs of damage, such as nicks or ...

  • Emerson 3051S - page 7

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 7 S TEP 1 CO NTINU ED ... Inline Gage T ransmitter Orientation The low side pressure port (atmospheric refe rence) on the inline gage transmitter is located under the sensor module neck label. (See Figure 3.) Keep the vent path free of any obstruction, incl uding but no ...

  • Emerson 3051S - page 8

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 8 S TEP 4: C ONNECT W IRIN G AND P OWER U P Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field T erminals.” 2. Connect the positive lead to the “+” termi nal, and the negative lead to the “–” terminal. NOTE Do not co ...

  • Emerson 3051S - page 9

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 9 S TEP 4 CO NTINU ED ... Signal Wi ring Groundin g Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the sensor module and inside the T erminal Compartment. These grounds are ...

  • Emerson 3051S - page 10

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 10 S TEP 4 CO NTINU ED ... Remote Display Wiring and Power Up The Remote Mount Display and Interface system consists of a local transmitter and a remote mount LCD display assembly . The local 3051S transmitter assembly includes a Junction Box housing with a three positio ...

  • Emerson 3051S - page 11

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 11 S TEP 4 CO NTINU ED ... Intrinsic Safety Consideration: The tra nsmitter assembly with remote display has been approved with Belden 3084A DeviceNet cable. Alte rnate cable may be used as long as the transmitter with remote display and cable is co nfigur ed according ...

  • Emerson 3051S - page 12

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 12 S TEP 4 CO NTINU ED ... NOTE Wire colors provided on page 1 1 are per Belde n 3084A DeviceNet cable. Wire color may vary depending on cable selected. Belden 3084A DeviceNet cable includes a ground shield. This shield must be connected to earth ground at either the sen ...

  • Emerson 3051S - page 13

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 13 S TEP 4 CO NTINU ED ... Conduit Electrica l Connector W iring (Option GE or GM) For 3051S transmitters with conduit electrical connectors GE or GM, refer to the cor dset manufacturer ’ s installation instructions for wiring details. For FM Intrinsically Safe, non-i ...

  • Emerson 3051S - page 14

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 14 S TEP 5: V ERIFY C ONFI GURATION Use any HART -compliant master to commun icate with and verify configuration of the 3051S. For the HART Diagnostics transmitte r (option code DA1), DD revision 3051S HDT Dev . 1 Rev . 1 is required. Field Communi ca to r User Interface ...

  • Emerson 3051S - page 15

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 15 A check ( ⻫ ) indicates the basic configuration parame ters. At a minimum, these parameters should be verified as part of the configuration and startup procedure. T able 1. Traditio nal Interface - Device Revision 6 or 7 and DD Revision 7 Fast Key Sequence Function ...

  • Emerson 3051S - page 16

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 16 T able 2. Device Dashboard - Device Revision 7 and DD Revision 9 Fast Key Sequence Function Fast Key Sequence Alarm and Saturat ion Levels 2,2,1,7 Burst Mode Control 2,2,4,2 Burst Op tion 2,2,4,3 Custom Display Configuration 2,1,3 ⻫ Damping 2,2,1,5 Date 2,2,5,4 Desc ...

  • Emerson 3051S - page 17

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 17 S TEP 6: T RIM THE T RANSMI TTER T ransmitters are shipped fully calibrated per r equest or by the factory default of full scale (lower range value = zero, upper range value = upper r ange limit). Zero T rim A zero trim is a single-point adjustment used for compensat ...

  • Emerson 3051S - page 18

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 18 S AFETY I NSTRUMENTED S YSTEMS Additional Safety Instrumented Systems inform ation is available in t he Rosemount 3051S reference manual (document number 00809-0100-4801) . The manual is available electronically on www .r osemount.com or by contacting an Emerson Proce ...

  • Emerson 3051S - page 19

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 19 NOTES 1. T ransmitter output is not safety-rated during t he follo wing: configuration changes, multidrop, loop test. Alternative means should be used to ensure process safety during tra nsmitter configuration and maintenance activities. 2. DCS or safety logic solver ...

  • Emerson 3051S - page 20

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 20 Operation and Maintenance Proof T est and Inspectio n The following proof tests are recommended. Proof test results and corrective actions taken must be documented at http://rosemount.d1asia.ph/rosemount/safety/ReportAFailure_newweb.asp in the event that an error is f ...

  • Emerson 3051S - page 21

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 21 Reference Certification The 3051S Safety-Certified Pressure Transmi tter was designed, developed, and audited to be compliant to IEC 61508 safety-certified SIL 2 Claim Limit. Specifications The 3051S Safety-Certified Pressure Transmitter must be operated in accordanc ...

  • Emerson 3051S - page 22

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 22 P RODUCT C ERTIFICATIONS Approved Manufactur ing Locations Rosemount Inc. — Chan hassen, Minnesota USA Fisher-Ros emount Gm bH & Co. — W esslin g, Germany Emerson Process Management Asia Pacific Priva te Limited — Singapore Beijing Rosemou nt Far Eas t Instr ...

  • Emerson 3051S - page 23

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 23 European Certifications I1 A TEX Intrinsic Safety -HART/Remote Display/Quick Connect/HART Diagnostics Certificate No.: BAS01A TEX1303X II 1 G Ex ia IIC T4 (-60 °C  T amb  70 °C) 1 180 Special Conditions for Safe Use (X) 1. The apparatus, excluding the T ...

  • Emerson 3051S - page 24

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 24 ND A TEX Dust Certificate No.: BAS01A TEX1374X II 1 D Ex tD A20 T105 °C (-20 °C  T amb  85 °C) V max = 42.4 volts max A = 22 m A IP66 1 180 Special Conditions for safe use (x): 1. Cable entries must be used which maintain the ingress protection of the enclosu ...

  • Emerson 3051S - page 25

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 25 Jap anese Certifications E4 TIIS Flameproof Ex d IIC T6 China (NEPSI) Certifications E3 China Flameproof, Dust Ignition-proof Certificate No. (manufactured in Chanhassen, MN): GYJ091035 Certificate No. (manufactured in Beijing, China): GYJ06366 Certificate No. (manuf ...

  • Emerson 3051S - page 26

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 26 INMETRO Certifications I2 Brazilian Approval (INMETRO Approval) - Intrinsic Safety Certificate number: CEPEL-EX-0722/05X (manufacturing in Chanhassen, MN) Certificate number: CEPEL-EX-1414/07X (manufacturing in Brazil) INMETRO Marking: BR-Ex ia IIC T4 IP 66W Special c ...

  • Emerson 3051S - page 27

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 27 IECEx Dust Certificate No. IECExBAS09.0014X Ex tD A20 T105 °C (-20 °C ≤ Ta m b ≤ 85 °C) Vmax = 42.4 V A = 22 m A IP66 Special conditions for safe use (x) 1. Cable entries must be used which maintain the ingress protectio n of the enclosure to at least IP66. 2. ...

  • Emerson 3051S - page 28

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 28 N7 IECEx T ype n Certificate No.: IECExBAS04.0018X Ex nC IIC T5 (T a = -40 ° C to 70 °C) Ui = 45 Vdc MAX IP66 Special conditions for safe use (x) The apparatus is not capable of withstanding the 500 V insulation test requir ed by Clause 6.8.1 of IEC 60079-15. Combin ...

  • Emerson 3051S - page 29

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 29 DOC 4801_QIG_RevKB.fm Page 29 Frid ay, December 3, 2010 1:17 AM ...

  • Emerson 3051S - page 30

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 30 4801_QIG_RevKB.fm Page 30 Frid ay, December 3, 2010 1:17 AM ...

  • Emerson 3051S - page 31

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 31 Schedule EC Declaration of Conformity RMD 1044 Rev. I File ID: 3051S CE Marking Page 3 of 5 K:prodapprEUCDOCS3051S_RMD1044I(3).doc PED Directive (97/23/EC) 3051S series Pressure Transmitters Model 3051S_CA4; 3051S_CD2, 3, 4, 5 (also with P9 option) Pressure Transm ...

  • Emerson 3051S - page 32

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 32 4801_QIG_RevKB.fm Page 32 Frid ay, December 3, 2010 1:17 AM ...

  • Emerson 3051S - page 33

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 33 4801_QIG_RevKB.fm Page 33 Frid ay, December 3, 2010 1:17 AM ...

  • Emerson 3051S - page 34

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 34 4801_QIG_RevKB.fm Page 34 Frid ay, December 3, 2010 1:17 AM ...

Fabricant Emerson Catégorie Marine Instruments

Les documents que nous recevons du fabricant de l'appareilEmerson 3051S peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Emerson
- manuels d’utilisations 3051S
- fiches produit Emerson
- dépliants
- ou étiquettes-énergie Emerson 3051S
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Emerson 3051S.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Emerson 3051S, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Emerson 3051S. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Emerson 3051S.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Emerson 3051S, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Emerson 3051S par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Emerson 3051S.

Le manuel d’utilisation complet Emerson, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Emerson 3051S - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Emerson 3051S, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lEmerson 3051S qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Emerson 3051S - qui devraient nous aider dans les premières étapes lors de l'utilisation Emerson 3051S
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Emerson 3051S
5. FAQ - questions fréquemment posées