Manuale per l’uso Emerson 3051S

34 pagine 2.49 mb
Scarica

Vai alla pagina of 34

Summary
  • Emerson 3051S - page 1

    www.rosemount.com ¢00825-0100-4801J¤ Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S Rosemount 3051S Series Pressure T ransmitter with HART ® Protocol Rosemount 3051SF Series Flowmeter T ransmitter with HART ® Protocol Sta r t End Step 1: Mount the T ransmitter Step 2: Consider Housing Rotation Step 3: Set Switch ...

  • Emerson 3051S - page 2

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 2 © 2010 Rose mount Inc. Al l right s reserved. Al l marks prop erty of owner . Rosemount and th e Rosemount logo type are register ed trademarks of Rosemount Inc. Rosemount Inc. 8200 Market Bou levard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906 - ...

  • Emerson 3051S - page 3

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 3 S TEP 1: M OUNT THE T RANSMITTER Liquid Flow Applications 1. Place tap s to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward. Gas Flow Applications 1. Place tap s in the top or side of ...

  • Emerson 3051S - page 4

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 4 S TEP 1 CO NTINU ED ... Panel Mount Pipe Mount Coplan ar ™ Flange T raditional Flange In-line Housings PlantWeb ™ Junction Box Remote Mount Display 4801_QIG_RevKB.fm Page 4 Fr iday , December 3, 2010 1:17 AM ...

  • Emerson 3051S - page 5

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 5 S TEP 1 CO NTINU ED ... Bolting Considerations If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. ...

  • Emerson 3051S - page 6

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 6 S TEP 1 CO NTINU ED ... Figure 2. T orque values for the flange and fla nge adapter bolts O-rings with Flange Adapte rs W ARNING Whenever the flanges or adapters are removed, visually inspect the o-rings. Replace them if there are any signs of damage, such as nicks or ...

  • Emerson 3051S - page 7

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 7 S TEP 1 CO NTINU ED ... Inline Gage T ransmitter Orientation The low side pressure port (atmospheric refe rence) on the inline gage transmitter is located under the sensor module neck label. (See Figure 3.) Keep the vent path free of any obstruction, incl uding but no ...

  • Emerson 3051S - page 8

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 8 S TEP 4: C ONNECT W IRIN G AND P OWER U P Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field T erminals.” 2. Connect the positive lead to the “+” termi nal, and the negative lead to the “–” terminal. NOTE Do not co ...

  • Emerson 3051S - page 9

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 9 S TEP 4 CO NTINU ED ... Signal Wi ring Groundin g Do not run signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. Grounding terminations are provided on the sensor module and inside the T erminal Compartment. These grounds are ...

  • Emerson 3051S - page 10

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 10 S TEP 4 CO NTINU ED ... Remote Display Wiring and Power Up The Remote Mount Display and Interface system consists of a local transmitter and a remote mount LCD display assembly . The local 3051S transmitter assembly includes a Junction Box housing with a three positio ...

  • Emerson 3051S - page 11

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 11 S TEP 4 CO NTINU ED ... Intrinsic Safety Consideration: The tra nsmitter assembly with remote display has been approved with Belden 3084A DeviceNet cable. Alte rnate cable may be used as long as the transmitter with remote display and cable is co nfigur ed according ...

  • Emerson 3051S - page 12

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 12 S TEP 4 CO NTINU ED ... NOTE Wire colors provided on page 1 1 are per Belde n 3084A DeviceNet cable. Wire color may vary depending on cable selected. Belden 3084A DeviceNet cable includes a ground shield. This shield must be connected to earth ground at either the sen ...

  • Emerson 3051S - page 13

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 13 S TEP 4 CO NTINU ED ... Conduit Electrica l Connector W iring (Option GE or GM) For 3051S transmitters with conduit electrical connectors GE or GM, refer to the cor dset manufacturer ’ s installation instructions for wiring details. For FM Intrinsically Safe, non-i ...

  • Emerson 3051S - page 14

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 14 S TEP 5: V ERIFY C ONFI GURATION Use any HART -compliant master to commun icate with and verify configuration of the 3051S. For the HART Diagnostics transmitte r (option code DA1), DD revision 3051S HDT Dev . 1 Rev . 1 is required. Field Communi ca to r User Interface ...

  • Emerson 3051S - page 15

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 15 A check ( ⻫ ) indicates the basic configuration parame ters. At a minimum, these parameters should be verified as part of the configuration and startup procedure. T able 1. Traditio nal Interface - Device Revision 6 or 7 and DD Revision 7 Fast Key Sequence Function ...

  • Emerson 3051S - page 16

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 16 T able 2. Device Dashboard - Device Revision 7 and DD Revision 9 Fast Key Sequence Function Fast Key Sequence Alarm and Saturat ion Levels 2,2,1,7 Burst Mode Control 2,2,4,2 Burst Op tion 2,2,4,3 Custom Display Configuration 2,1,3 ⻫ Damping 2,2,1,5 Date 2,2,5,4 Desc ...

  • Emerson 3051S - page 17

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 17 S TEP 6: T RIM THE T RANSMI TTER T ransmitters are shipped fully calibrated per r equest or by the factory default of full scale (lower range value = zero, upper range value = upper r ange limit). Zero T rim A zero trim is a single-point adjustment used for compensat ...

  • Emerson 3051S - page 18

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 18 S AFETY I NSTRUMENTED S YSTEMS Additional Safety Instrumented Systems inform ation is available in t he Rosemount 3051S reference manual (document number 00809-0100-4801) . The manual is available electronically on www .r osemount.com or by contacting an Emerson Proce ...

  • Emerson 3051S - page 19

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 19 NOTES 1. T ransmitter output is not safety-rated during t he follo wing: configuration changes, multidrop, loop test. Alternative means should be used to ensure process safety during tra nsmitter configuration and maintenance activities. 2. DCS or safety logic solver ...

  • Emerson 3051S - page 20

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 20 Operation and Maintenance Proof T est and Inspectio n The following proof tests are recommended. Proof test results and corrective actions taken must be documented at http://rosemount.d1asia.ph/rosemount/safety/ReportAFailure_newweb.asp in the event that an error is f ...

  • Emerson 3051S - page 21

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 21 Reference Certification The 3051S Safety-Certified Pressure Transmi tter was designed, developed, and audited to be compliant to IEC 61508 safety-certified SIL 2 Claim Limit. Specifications The 3051S Safety-Certified Pressure Transmitter must be operated in accordanc ...

  • Emerson 3051S - page 22

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 22 P RODUCT C ERTIFICATIONS Approved Manufactur ing Locations Rosemount Inc. — Chan hassen, Minnesota USA Fisher-Ros emount Gm bH & Co. — W esslin g, Germany Emerson Process Management Asia Pacific Priva te Limited — Singapore Beijing Rosemou nt Far Eas t Instr ...

  • Emerson 3051S - page 23

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 23 European Certifications I1 A TEX Intrinsic Safety -HART/Remote Display/Quick Connect/HART Diagnostics Certificate No.: BAS01A TEX1303X II 1 G Ex ia IIC T4 (-60 °C  T amb  70 °C) 1 180 Special Conditions for Safe Use (X) 1. The apparatus, excluding the T ...

  • Emerson 3051S - page 24

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 24 ND A TEX Dust Certificate No.: BAS01A TEX1374X II 1 D Ex tD A20 T105 °C (-20 °C  T amb  85 °C) V max = 42.4 volts max A = 22 m A IP66 1 180 Special Conditions for safe use (x): 1. Cable entries must be used which maintain the ingress protection of the enclosu ...

  • Emerson 3051S - page 25

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 25 Jap anese Certifications E4 TIIS Flameproof Ex d IIC T6 China (NEPSI) Certifications E3 China Flameproof, Dust Ignition-proof Certificate No. (manufactured in Chanhassen, MN): GYJ091035 Certificate No. (manufactured in Beijing, China): GYJ06366 Certificate No. (manuf ...

  • Emerson 3051S - page 26

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 26 INMETRO Certifications I2 Brazilian Approval (INMETRO Approval) - Intrinsic Safety Certificate number: CEPEL-EX-0722/05X (manufacturing in Chanhassen, MN) Certificate number: CEPEL-EX-1414/07X (manufacturing in Brazil) INMETRO Marking: BR-Ex ia IIC T4 IP 66W Special c ...

  • Emerson 3051S - page 27

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 27 IECEx Dust Certificate No. IECExBAS09.0014X Ex tD A20 T105 °C (-20 °C ≤ Ta m b ≤ 85 °C) Vmax = 42.4 V A = 22 m A IP66 Special conditions for safe use (x) 1. Cable entries must be used which maintain the ingress protectio n of the enclosure to at least IP66. 2. ...

  • Emerson 3051S - page 28

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 28 N7 IECEx T ype n Certificate No.: IECExBAS04.0018X Ex nC IIC T5 (T a = -40 ° C to 70 °C) Ui = 45 Vdc MAX IP66 Special conditions for safe use (x) The apparatus is not capable of withstanding the 500 V insulation test requir ed by Clause 6.8.1 of IEC 60079-15. Combin ...

  • Emerson 3051S - page 29

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 29 DOC 4801_QIG_RevKB.fm Page 29 Frid ay, December 3, 2010 1:17 AM ...

  • Emerson 3051S - page 30

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 30 4801_QIG_RevKB.fm Page 30 Frid ay, December 3, 2010 1:17 AM ...

  • Emerson 3051S - page 31

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 31 Schedule EC Declaration of Conformity RMD 1044 Rev. I File ID: 3051S CE Marking Page 3 of 5 K:prodapprEUCDOCS3051S_RMD1044I(3).doc PED Directive (97/23/EC) 3051S series Pressure Transmitters Model 3051S_CA4; 3051S_CD2, 3, 4, 5 (also with P9 option) Pressure Transm ...

  • Emerson 3051S - page 32

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 32 4801_QIG_RevKB.fm Page 32 Frid ay, December 3, 2010 1:17 AM ...

  • Emerson 3051S - page 33

    Quick Installatio n Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 33 4801_QIG_RevKB.fm Page 33 Frid ay, December 3, 2010 1:17 AM ...

  • Emerson 3051S - page 34

    Quick Installation Guide 00825-0100-4801, Rev KB December 2010 Rosemount 3051S 34 4801_QIG_RevKB.fm Page 34 Frid ay, December 3, 2010 1:17 AM ...

Fabbricante Emerson Categoria Marine Instruments

I documenti che otteniamo dal fabbricante del dispositivoEmerson 3051S possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Emerson
- manuali per l’uso 3051S
- schede prodotto Emerson
- opuscoli
- o etichette energetiche Emerson 3051S
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Emerson 3051S.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Emerson 3051S, manuali di manutenzione, brevi manuali o manuali utente Emerson 3051S. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Emerson 3051S.

Manuali per l’uso simili

Manuale completo del dispositivo Emerson 3051S, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Emerson 3051S dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Emerson 3051S.

Il manuale per l’uso completo Emerson, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Emerson 3051S - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Emerson 3051S, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Emerson 3051S che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Emerson 3051S - che ci dovrebbe aiutare nei primi passi durante l'uso Emerson 3051S
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Emerson 3051S
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Emerson 3051S in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Emerson 3051S?

Utilizza il modulo sottostante

Se non hai risolto il problema con Emerson 3051S con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Emerson 3051S è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)