    279104-YTG-B-0307 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE TECHNICAL GUIDE SPLIT -SYSTEM HEA T PUMPS 10 SEER – R-22 MODELS: E*RA036 THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) MODELS: 036-048 (3 PH) MODELS: 060, 090 (3 PH) Due to continu ous product improv e ment, specific ations are subjec t to ch an ge without notice. Visit ...

  • York 090 - page 2

    279104-YTG-B-0307 2 Unitary Products Group All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provid ed upon request. Physical and Electrical Dat a MODEL E1RA036S25 E2RA048S25 E1RA060S25 E1RA036S46 E2RA048S46 E1RA060S46 Unit Supply V oltage 208/230-3-60 460 - 3 - 60 Normal V oltage Range 1 187 to 2 ...

  • York 090 - page 3

    279104-YTG-B-0307 Unitary Products Group 3 PROCEDURES: 1. Unit factory charge listed on the unit na meplate includes refri gerant for the condenser , the smallest evaporator and 15 feet of intercon- necting line tubing. 2. V er ify the o rifice size and additional charge required for specific evaportor coil in the system using t he above table. 3. ...

  • York 090 - page 4

    279104-YTG-B-0307 4 Unitary Products Group - = Not applicable COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL ELECTRI C 2 HEA T KW W RA TED CFM NET MBH SEER W/O TXV SEER WITH TXV 3 EER TOT AL SENS. 3 PH 10 SEER HP WITH MA / MC / N-AH / G2FD E1RA036S(25,46) MA12BN2,4 10 17 FC/MC35B3X 1250 34.4 25.3 10 – ...

  • York 090 - page 5

    279104-YTG-B-0307 Unitary Products Group 5 * Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up. COOLING CAP ACITY - Up flow , Downflow , & Horizontal Furnac es and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MB ...

  • York 090 - page 6

    279104-YTG-B-0307 6 Unitary Products Group COP equals MBH output divided by (t ot al KW input x 3.412). HSPF (Heating Seasonal Performa nce Factor) is the total heatin g output during a normal annual usage perio d for heating divided by the total electric power input during the same period. — = Not Applicable. COP equals MBH output divided by (t ...

  • York 090 - page 7

    279104-YTG-B-0307 Unitary Products Group 7 ACCESSORIES Refer to Price Manual for specific model numbers. S tart A ssist Kit (2SA067*) Blower Time Delay - A vailable to increase efficiency when installed. Installs on indoor section and maintains blower for approximately one minute a fter cooling thermostat has been satisfied. Hard St art Kit s - Pro ...

  • York 090 - page 8

    279104-YTG-B-0307 8 Unitary Products Group TYPICAL FIELD WIRING - 3 PH (036 - 060) TYPICAL FIELD WIRING - 3 PH (090) THERMOST A T INDOOR UNIT OUTDOOR UNIT LOW VOLT AGE TERMINAL BLOCK IN AIR HANDLER WITH ELECTRIC HEA T 3,4 DEFROST CONTROL 1 FIELD INST ALLED JUMPER GND. SCREW CONT ACTOR T2 T1 L2 L1 M R Lo rX Y O W G T 2 E 2 R R Y Y O O W2 W W1 C X G ...

  • York 090 - page 9

    279104-YTG-B-0307 Unitary Products Group 9 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif f erent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree belo ...

  • York 090 - page 10

    279104-YTG-B-0307 10 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif f erent than those listed (between 73 -87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperature and decre ases by 1060 BTUH per 1000 CFM per degree b ...

  • York 090 - page 11

    279104-YTG-B-0307 Unitary Products Group 11 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif f erent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York 090 - page 12

    279104-YTG-B-0307 12 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MODEL NO E1RA036S(25 ,46) EV APORA TOR COIL MODEL NO F2RP/F2FP036 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1000 1250 1400 MBTUH KW C.O.P . MBTU H KW C.O.P ...

  • York 090 - page 13

    279104-YTG-B-0307 Unitary Products Group 13 Multipliers for determining the performance with other indoor sections . HEA TING P ERFORMANCE DA T A CONDENSING UNIT MODEL NO E2RA048S(25 ,46) EV APORA TOR COIL MODEL NO F2RP/F2FP048 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1250 1400 1550 MBTUH KW C.O.P . MBTU H KW C.O.P . ...

  • York 090 - page 14

    279104-YTG-B-0307 14 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MODEL NO E1RA060S(25 ,46) EV APORA TOR COIL MODEL NO G2FD060(S,H)24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1600 1800 2000 MBTUH KW C.O.P . MBTU H KW C.O. ...

  • York 090 - page 15

    279104-YTG-B-0307 Unitary Products Group 15 NOTES ...

  • York 090 - page 16

    Subject to change without notice. Printed in U.S.A. 279104-YTG-B-0307 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 279104-YTG- A-1 106 Unitary 5005 Norman Product Y ork OK Group Drive 73069 NOTES ...

Fabricant York Catégorie Heat Pump

Les documents que nous recevons du fabricant de l'appareilYork 090 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques York
- manuels d’utilisations 090
- fiches produit York
- dépliants
- ou étiquettes-énergie York 090
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation York 090.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation York 090, manuels d’entretien, brefs manuels ou manuels de l’utilisateur York 090. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit York 090.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil York 090, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser York 090 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs York 090.

Le manuel d’utilisation complet York, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel York 090 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières York 090, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lYork 090 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil York 090 - qui devraient nous aider dans les premières étapes lors de l'utilisation York 090
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de York 090
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service York 090 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de York 090?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec York 090, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec York 090 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)