  • York 090 - page 1

    279104-YTG-B-0307 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE TECHNICAL GUIDE SPLIT -SYSTEM HEA T PUMPS 10 SEER – R-22 MODELS: E*RA036 THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) MODELS: 036-048 (3 PH) MODELS: 060, 090 (3 PH) Due to continu ous product improv e ment, specific ations are subjec t to ch an ge without notice. Visit ...

  • York 090 - page 2

    279104-YTG-B-0307 2 Unitary Products Group All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provid ed upon request. Physical and Electrical Dat a MODEL E1RA036S25 E2RA048S25 E1RA060S25 E1RA036S46 E2RA048S46 E1RA060S46 Unit Supply V oltage 208/230-3-60 460 - 3 - 60 Normal V oltage Range 1 187 to 2 ...

  • York 090 - page 3

    279104-YTG-B-0307 Unitary Products Group 3 PROCEDURES: 1. Unit factory charge listed on the unit na meplate includes refri gerant for the condenser , the smallest evaporator and 15 feet of intercon- necting line tubing. 2. V er ify the o rifice size and additional charge required for specific evaportor coil in the system using t he above table. 3. ...

  • York 090 - page 4

    279104-YTG-B-0307 4 Unitary Products Group - = Not applicable COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL ELECTRI C 2 HEA T KW W RA TED CFM NET MBH SEER W/O TXV SEER WITH TXV 3 EER TOT AL SENS. 3 PH 10 SEER HP WITH MA / MC / N-AH / G2FD E1RA036S(25,46) MA12BN2,4 10 17 FC/MC35B3X 1250 34.4 25.3 10 – ...

  • York 090 - page 5

    279104-YTG-B-0307 Unitary Products Group 5 * Requires a 2FD Blower Time Delay unless a standard furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up. COOLING CAP ACITY - Up flow , Downflow , & Horizontal Furnac es and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MB ...

  • York 090 - page 6

    279104-YTG-B-0307 6 Unitary Products Group COP equals MBH output divided by (t ot al KW input x 3.412). HSPF (Heating Seasonal Performa nce Factor) is the total heatin g output during a normal annual usage perio d for heating divided by the total electric power input during the same period. — = Not Applicable. COP equals MBH output divided by (t ...

  • York 090 - page 7

    279104-YTG-B-0307 Unitary Products Group 7 ACCESSORIES Refer to Price Manual for specific model numbers. S tart A ssist Kit (2SA067*) Blower Time Delay - A vailable to increase efficiency when installed. Installs on indoor section and maintains blower for approximately one minute a fter cooling thermostat has been satisfied. Hard St art Kit s - Pro ...

  • York 090 - page 8

    279104-YTG-B-0307 8 Unitary Products Group TYPICAL FIELD WIRING - 3 PH (036 - 060) TYPICAL FIELD WIRING - 3 PH (090) THERMOST A T INDOOR UNIT OUTDOOR UNIT LOW VOLT AGE TERMINAL BLOCK IN AIR HANDLER WITH ELECTRIC HEA T 3,4 DEFROST CONTROL 1 FIELD INST ALLED JUMPER GND. SCREW CONT ACTOR T2 T1 L2 L1 M R Lo rX Y O W G T 2 E 2 R R Y Y O O W2 W W1 C X G ...

  • York 090 - page 9

    279104-YTG-B-0307 Unitary Products Group 9 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif f erent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree belo ...

  • York 090 - page 10

    279104-YTG-B-0307 10 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif f erent than those listed (between 73 -87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperature and decre ases by 1060 BTUH per 1000 CFM per degree b ...

  • York 090 - page 11

    279104-YTG-B-0307 Unitary Products Group 11 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif f erent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York 090 - page 12

    279104-YTG-B-0307 12 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MODEL NO E1RA036S(25 ,46) EV APORA TOR COIL MODEL NO F2RP/F2FP036 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1000 1250 1400 MBTUH KW C.O.P . MBTU H KW C.O.P ...

  • York 090 - page 13

    279104-YTG-B-0307 Unitary Products Group 13 Multipliers for determining the performance with other indoor sections . HEA TING P ERFORMANCE DA T A CONDENSING UNIT MODEL NO E2RA048S(25 ,46) EV APORA TOR COIL MODEL NO F2RP/F2FP048 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1250 1400 1550 MBTUH KW C.O.P . MBTU H KW C.O.P . ...

  • York 090 - page 14

    279104-YTG-B-0307 14 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. HEA TING PE RFORMANCE DA T A CONDENSING UNIT MODEL NO E1RA060S(25 ,46) EV APORA TOR COIL MODEL NO G2FD060(S,H)24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1600 1800 2000 MBTUH KW C.O.P . MBTU H KW C.O. ...

  • York 090 - page 15

    279104-YTG-B-0307 Unitary Products Group 15 NOTES ...

  • York 090 - page 16

    Subject to change without notice. Printed in U.S.A. 279104-YTG-B-0307 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 279104-YTG- A-1 106 Unitary 5005 Norman Product Y ork OK Group Drive 73069 NOTES ...

Производитель York Категория Heat Pump

Документы, которые мы получаем от производителя устройства York 090 мы можем разделить на несколько групп. Это в частности:
- технические чертежи York
- инструкции обслуживания 090
- паспорта изделия York
- информационные брошюры
- энергетические этикетки York 090
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания York 090.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа York 090, инструкции обслуживания, короткие инструкции или инструкции пользователя York 090. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия York 090.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства York 090, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании York 090 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей York 090.

Полная инструкция обслуживания York, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией York 090 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания York 090, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся York 090, которое найдем в данном документе
3. Советы по использованию основных функций устройства York 090 - которые должны облегчить нам первые шаги во время использования York 090
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем York 090
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра York 090 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся York 090?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с York 090, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с York 090 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)