    SER VICE MANUAL (Basic Information) CM3212 / KMS0712 ( ✕ 2) + KMS1812 SPLIT SYSTEM AIR CONDITIONER 8526481017300 REFERENCE NO. WM – 700699 W Indoor Unit Outdoor Unit CM3212 KMS0712 KMS1812 92-131 S/M (Basic) 2/21/01 4:49 PM Page A ...

  • Sanyo KMS1812 - page 2

    92-131 S/M (Basic) 2/21/01 4:49 PM Page B ...

  • Sanyo KMS1812 - page 3

    ii WM – 700699 SER VICE MANU AL CM3212 / KMS0712 ( × 2) + KMS1812 (Basic Inf ormation) 92-131 S/M (Basic) 2/21/01 4:49 PM Page ii ...

  • Sanyo KMS1812 - page 4

    WM – 700699 iii IMPORT ANT! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: ● Carefully ...

  • Sanyo KMS1812 - page 5

    T able of Contents Page 1. OPERA TING RANGE ............................................................................................................................... 1 2. SPECIFICA TIONS .................................................................................................................................... 2 Unit Specifications .. ...

  • Sanyo KMS1812 - page 6

    1 WM – 700699 1. OPERA TING RANGE Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 95°F DB / 71°F WB 115°F DB Minimum 67°F DB / 57°F WB 67°F DB CM3212 / KMS0712 ( × 2) + KMS1812 92-131 S/M (Basic) 2/21/01 4:49 PM Page 1 ...

  • Sanyo KMS1812 - page 7

    DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Outside air temperature 95°F DB / 75°F WB Indoor unit entering air temperature 80°F DB / 67°F WB 2 WM – 700699 Model No. Outdoor unit CM3212 Applicable indoor unit KMS0712, KMS1812 Cooling No. of indoor units Capacity BTU/ h kW Phase, Frequency Hz Voltage rating V Availabl ...

  • Sanyo KMS1812 - page 8

    3 WM – 700699 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Outside air temperature 95°F DB/ 75°F WB Indoor unit entering air temperature 80°F DB/67°F WB Model No. KMS0712 Type Wall-mounted Cooling Capacity BTU/ h 7,000 / 7,700 kW 2.05 / 2.05 Air circulation (High) cu. ft./min. 220 / 210 Moisture removal (High) pints/ ...

  • Sanyo KMS1812 - page 9

    4 WM – 700699 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Outside air temperature 95°F DB/ 75°F WB Indoor unit entering air temperature 80°F DB/67°F WB Model No. KMS1812 Type Wall-mounted Cooling Capacity BTU/ h 18,000 / 17,600 kW 5.27 / 5.16 Air circulation (High) cu. ft./min. 440 / 420 Moisture removal (High) pint ...

  • Sanyo KMS1812 - page 10

    WM – 700699 5 3. DIMENSION AL D A T A Outdoor Unit: CM3212 Air intake 21/32 Air intake Air intake 21/32 25-1/16 26-3/8 21/32 26-3/8 25-1/16 4 × 15/32 dia. hole for fixing 26-7/32 Air dischange 1/4" narrow tubing service valve 1/2" wide tubing service valve 32-1/16 28-1/32 5-7/16 5-3/8 3-5/32 2-3/4 5-1/4 26-7/32 3/8" wide tubing se ...

  • Sanyo KMS1812 - page 11

    6 WM – 700699 Indoor Unit: KMS0712 Indoor Unit: KMS1812 Wireless remote control unit 31-1/2 7-3/32 7-11/64 17-23/32 Rear panel (center point of gravity) 6-23/32 13-19/32 1-49/64 3-3/4 15/32 1-49/64 1-3/8 5-1/2 1-49/64 Center of tubing hole (for right rear) O.D. 3/8" wide tubing O.D. 1/4" narrow tubing Drain hose O.D. 23/32 1-5/8 6-7/64 ...

  • Sanyo KMS1812 - page 12

    4. COOLING CAP A CITY 230V CM3622 / KMS0712 × 1 7 WM – 700699 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB Indoor unit entering air temperature 80°F DB / 67°F WB Rating Capacity: 7,000 BTU/ H Air Flow Rate: 220 CF ...

  • Sanyo KMS1812 - page 13

    8 WM – 700699 208V CM3622 / KMS0712 × 1 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB Indoor unit entering air temperature 80°F DB / 67°F WB Rating Capacity: 7,000 BTU/ H Air Flow Rate: 210 CFM Evaporator Condenser ...

  • Sanyo KMS1812 - page 14

    9 WM – 700699 230V CM3622 / KMS1812 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB Indoor unit entering air temperature 80°F DB / 67°F WB Rating Capacity: 18,000 BTU/ H Air Flow Rate: 440 CFM Evaporator Condenser Ent ...

  • Sanyo KMS1812 - page 15

    10 WM – 700699 208V CM3622 / KMS1812 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB Indoor unit entering air temperature 80°F DB / 67°F WB Rating Capacity: 17,600 BTU/ H Air Flow Rate: 420 CFM Evaporator Condenser En ...

  • Sanyo KMS1812 - page 16

    OUTDOOR UNIT INDOOR UNIT UNIT A Heat exchanger Heat exchanger INDOOR UNIT UNIT B Heat exchanger INDOOR UNIT UNIT C Heat exchanger Narrow tube service valve Capillary tube Drier A B C Check port A Check port B Check port C Accumulator Accumulator Accumulator Compressor C Compressor B Compressor A Narrow tube O.D. 1/4" (6.35 mm) O.D. 1/4" ( ...

  • Sanyo KMS1812 - page 17

    12 WM – 700699 6. ELECTRICAL D A T A ● Electrical Characteristics CM3212 / KMS0712 × 1 Remarks: Rating conditions are: Outside air temperature 95°F DB / 75°F WB Indoor unit entering air temperature 80°F DB/67°F WB Performance at Indoor Unit Outdoor Unit Complete Unit 230/208V – 1ø – 60Hz Fan Motor Fan Motor Compressor Rating Condition ...

  • Sanyo KMS1812 - page 18

    13 WM – 700699 CM3212 / KMS0712 + KMS1812 Remarks: Rating conditions are: Outside air temperature 95°F DB / 75°F WB Indoor unit entering air temperature 80°F DB/ 67°F WB Performance at Indoor Units Outdoor Unit Complete Unit 230/208V – 1ø – 60Hz Fan Motor Compressor Rating Conditions A 0.55 / 0.54 1.45 / 1.42 9.80 / 10.64 11.8 / 12.6 W 1 ...

  • Sanyo KMS1812 - page 19

    14 WM – 700699 ● Electrical Wiring Diagram Outdoor Unit: CM3212 CMA S C R WHT BLK RED CMB S C R BLK WHT RED CMC S C R BLK WHT RED 2 3 TO INDOOR UNIT A 1 2 3 1 2 3 1 2 Power supply 1 5 3 2 6 4 78 Fuse 1 5 3 2 6 4 78 1 5 3 2 6 4 78 P 5 4 3 2 1 6 5 4 3 2 1 1 Terminal plate (3P) A TO INDOOR UNIT B Terminal plate (3P) B TO INDOOR UNIT C Terminal pla ...

  • Sanyo KMS1812 - page 20

    15 WM – 700699 Indoor Unit: KMS0712 1 3 3 2 2 1 1 2 2 1 1 1 2 1 2 1 1 9 9 5 5 4 4 3 3 2 2 1 1 5 5 4 4 3 3 2 2 1 1 6 6 BLK BLK Thermistor 1 2 1 2 BLK BLK Thermistor 2P TH1 2P TH2 2P CM 3P Supply CONTROLLER Switch assy Receiver assy 9P SW Fan motor FM 2 3 1 2 1 2 2P SEC BRN PNK GRY YEL VLT WHT GRY YEL VLT WHT Connector (6P) 5P FM Capacitor PNK BRN ...

  • Sanyo KMS1812 - page 21

    16 WM – 700699 Indoor Unit: KMS1812 3 1 1 2 2 3 3 1 1 2 2 1 9 5 5 4 4 3 3 2 2 1 1 2P TH2 3P Supply CONTROLLER Switch assy Switch assy 2 1 1 2 1 2 5P FM GRY YEL VLT 2P LM Capacitor 1 2 1 2 2P SEC S P Louver motor RED WHT BLU BLK Terminal plate FROM OUTDOOR UNIT Power relay BLU 1 1 2 2 BLK 2P TH1 BLK 1 1 2 2 BLK 1 1 2 2 1 1 2 2 LM FM GRN 2P CM 2P P ...

  • Sanyo KMS1812 - page 22

    For parts or service contact SFS Corporation: 1200 West Artesia Blvd., Compton, California 90220 Printed in U.S.A. CORPORATION 1991/Nov./12M SANYO Canada Inc.: Toronto, Ont. M4H 1M6 In Canada WM – 700699 H406/12M Printed in U.S.A. 92-131 S/M (Basic) 2/21/01 4:49 PM Page 17 ...

Fabricant Sanyo Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilSanyo KMS1812 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Sanyo
- manuels d’utilisations KMS1812
- fiches produit Sanyo
- dépliants
- ou étiquettes-énergie Sanyo KMS1812
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Sanyo KMS1812.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Sanyo KMS1812, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Sanyo KMS1812. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Sanyo KMS1812.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Sanyo KMS1812, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Sanyo KMS1812 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Sanyo KMS1812.

Le manuel d’utilisation complet Sanyo, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Sanyo KMS1812 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Sanyo KMS1812, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lSanyo KMS1812 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Sanyo KMS1812 - qui devraient nous aider dans les premières étapes lors de l'utilisation Sanyo KMS1812
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Sanyo KMS1812
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Sanyo KMS1812 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Sanyo KMS1812?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Sanyo KMS1812, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Sanyo KMS1812 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)