    SER VICE MANUAL (Basic Information) CM3212 / KMS0712 ( ✕ 2) + KMS1812 SPLIT SYSTEM AIR CONDITIONER 8526481017300 REFERENCE NO. WM – 700699 W Indoor Unit Outdoor Unit CM3212 KMS0712 KMS1812 92-131 S/M (Basic) 2/21/01 4:49 PM Page A ...

  • Sanyo KMS1812 - page 2

    92-131 S/M (Basic) 2/21/01 4:49 PM Page B ...

  • Sanyo KMS1812 - page 3

    ii WM – 700699 SER VICE MANU AL CM3212 / KMS0712 ( × 2) + KMS1812 (Basic Inf ormation) 92-131 S/M (Basic) 2/21/01 4:49 PM Page ii ...

  • Sanyo KMS1812 - page 4

    WM – 700699 iii IMPORT ANT! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: ● Carefully ...

  • Sanyo KMS1812 - page 5

    T able of Contents Page 1. OPERA TING RANGE ............................................................................................................................... 1 2. SPECIFICA TIONS .................................................................................................................................... 2 Unit Specifications .. ...

  • Sanyo KMS1812 - page 6

    1 WM – 700699 1. OPERA TING RANGE Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 95°F DB / 71°F WB 115°F DB Minimum 67°F DB / 57°F WB 67°F DB CM3212 / KMS0712 ( × 2) + KMS1812 92-131 S/M (Basic) 2/21/01 4:49 PM Page 1 ...

  • Sanyo KMS1812 - page 7

    DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Outside air temperature 95°F DB / 75°F WB Indoor unit entering air temperature 80°F DB / 67°F WB 2 WM – 700699 Model No. Outdoor unit CM3212 Applicable indoor unit KMS0712, KMS1812 Cooling No. of indoor units Capacity BTU/ h kW Phase, Frequency Hz Voltage rating V Availabl ...

  • Sanyo KMS1812 - page 8

    3 WM – 700699 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Outside air temperature 95°F DB/ 75°F WB Indoor unit entering air temperature 80°F DB/67°F WB Model No. KMS0712 Type Wall-mounted Cooling Capacity BTU/ h 7,000 / 7,700 kW 2.05 / 2.05 Air circulation (High) cu. ft./min. 220 / 210 Moisture removal (High) pints/ ...

  • Sanyo KMS1812 - page 9

    4 WM – 700699 DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Outside air temperature 95°F DB/ 75°F WB Indoor unit entering air temperature 80°F DB/67°F WB Model No. KMS1812 Type Wall-mounted Cooling Capacity BTU/ h 18,000 / 17,600 kW 5.27 / 5.16 Air circulation (High) cu. ft./min. 440 / 420 Moisture removal (High) pint ...

  • Sanyo KMS1812 - page 10

    WM – 700699 5 3. DIMENSION AL D A T A Outdoor Unit: CM3212 Air intake 21/32 Air intake Air intake 21/32 25-1/16 26-3/8 21/32 26-3/8 25-1/16 4 × 15/32 dia. hole for fixing 26-7/32 Air dischange 1/4" narrow tubing service valve 1/2" wide tubing service valve 32-1/16 28-1/32 5-7/16 5-3/8 3-5/32 2-3/4 5-1/4 26-7/32 3/8" wide tubing se ...

  • Sanyo KMS1812 - page 11

    6 WM – 700699 Indoor Unit: KMS0712 Indoor Unit: KMS1812 Wireless remote control unit 31-1/2 7-3/32 7-11/64 17-23/32 Rear panel (center point of gravity) 6-23/32 13-19/32 1-49/64 3-3/4 15/32 1-49/64 1-3/8 5-1/2 1-49/64 Center of tubing hole (for right rear) O.D. 3/8" wide tubing O.D. 1/4" narrow tubing Drain hose O.D. 23/32 1-5/8 6-7/64 ...

  • Sanyo KMS1812 - page 12

    4. COOLING CAP A CITY 230V CM3622 / KMS0712 × 1 7 WM – 700699 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB Indoor unit entering air temperature 80°F DB / 67°F WB Rating Capacity: 7,000 BTU/ H Air Flow Rate: 220 CF ...

  • Sanyo KMS1812 - page 13

    8 WM – 700699 208V CM3622 / KMS0712 × 1 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB Indoor unit entering air temperature 80°F DB / 67°F WB Rating Capacity: 7,000 BTU/ H Air Flow Rate: 210 CFM Evaporator Condenser ...

  • Sanyo KMS1812 - page 14

    9 WM – 700699 230V CM3622 / KMS1812 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB Indoor unit entering air temperature 80°F DB / 67°F WB Rating Capacity: 18,000 BTU/ H Air Flow Rate: 440 CFM Evaporator Condenser Ent ...

  • Sanyo KMS1812 - page 15

    10 WM – 700699 208V CM3622 / KMS1812 TC: Total Cooling Capacity (BTU/ H) SHC: Sensible Heat Capacity (BTU/ H) kW: Compressor Input (kW) Remarks: Rating conditions (* mark) are: Outside ambient temperature 95°F DB Indoor unit entering air temperature 80°F DB / 67°F WB Rating Capacity: 17,600 BTU/ H Air Flow Rate: 420 CFM Evaporator Condenser En ...

  • Sanyo KMS1812 - page 16

    OUTDOOR UNIT INDOOR UNIT UNIT A Heat exchanger Heat exchanger INDOOR UNIT UNIT B Heat exchanger INDOOR UNIT UNIT C Heat exchanger Narrow tube service valve Capillary tube Drier A B C Check port A Check port B Check port C Accumulator Accumulator Accumulator Compressor C Compressor B Compressor A Narrow tube O.D. 1/4" (6.35 mm) O.D. 1/4" ( ...

  • Sanyo KMS1812 - page 17

    12 WM – 700699 6. ELECTRICAL D A T A ● Electrical Characteristics CM3212 / KMS0712 × 1 Remarks: Rating conditions are: Outside air temperature 95°F DB / 75°F WB Indoor unit entering air temperature 80°F DB/67°F WB Performance at Indoor Unit Outdoor Unit Complete Unit 230/208V – 1ø – 60Hz Fan Motor Fan Motor Compressor Rating Condition ...

  • Sanyo KMS1812 - page 18

    13 WM – 700699 CM3212 / KMS0712 + KMS1812 Remarks: Rating conditions are: Outside air temperature 95°F DB / 75°F WB Indoor unit entering air temperature 80°F DB/ 67°F WB Performance at Indoor Units Outdoor Unit Complete Unit 230/208V – 1ø – 60Hz Fan Motor Compressor Rating Conditions A 0.55 / 0.54 1.45 / 1.42 9.80 / 10.64 11.8 / 12.6 W 1 ...

  • Sanyo KMS1812 - page 19

    14 WM – 700699 ● Electrical Wiring Diagram Outdoor Unit: CM3212 CMA S C R WHT BLK RED CMB S C R BLK WHT RED CMC S C R BLK WHT RED 2 3 TO INDOOR UNIT A 1 2 3 1 2 3 1 2 Power supply 1 5 3 2 6 4 78 Fuse 1 5 3 2 6 4 78 1 5 3 2 6 4 78 P 5 4 3 2 1 6 5 4 3 2 1 1 Terminal plate (3P) A TO INDOOR UNIT B Terminal plate (3P) B TO INDOOR UNIT C Terminal pla ...

  • Sanyo KMS1812 - page 20

    15 WM – 700699 Indoor Unit: KMS0712 1 3 3 2 2 1 1 2 2 1 1 1 2 1 2 1 1 9 9 5 5 4 4 3 3 2 2 1 1 5 5 4 4 3 3 2 2 1 1 6 6 BLK BLK Thermistor 1 2 1 2 BLK BLK Thermistor 2P TH1 2P TH2 2P CM 3P Supply CONTROLLER Switch assy Receiver assy 9P SW Fan motor FM 2 3 1 2 1 2 2P SEC BRN PNK GRY YEL VLT WHT GRY YEL VLT WHT Connector (6P) 5P FM Capacitor PNK BRN ...

  • Sanyo KMS1812 - page 21

    16 WM – 700699 Indoor Unit: KMS1812 3 1 1 2 2 3 3 1 1 2 2 1 9 5 5 4 4 3 3 2 2 1 1 2P TH2 3P Supply CONTROLLER Switch assy Switch assy 2 1 1 2 1 2 5P FM GRY YEL VLT 2P LM Capacitor 1 2 1 2 2P SEC S P Louver motor RED WHT BLU BLK Terminal plate FROM OUTDOOR UNIT Power relay BLU 1 1 2 2 BLK 2P TH1 BLK 1 1 2 2 BLK 1 1 2 2 1 1 2 2 LM FM GRN 2P CM 2P P ...

  • Sanyo KMS1812 - page 22

    For parts or service contact SFS Corporation: 1200 West Artesia Blvd., Compton, California 90220 Printed in U.S.A. CORPORATION 1991/Nov./12M SANYO Canada Inc.: Toronto, Ont. M4H 1M6 In Canada WM – 700699 H406/12M Printed in U.S.A. 92-131 S/M (Basic) 2/21/01 4:49 PM Page 17 ...

メーカー Sanyo カテゴリー Air Conditioner

Sanyo KMS1812のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- KMS1812の取扱説明書
- Sanyoの製品カード
- パンフレット
- またはSanyo KMS1812の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Sanyo KMS1812の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Sanyo KMS1812の取り付け説明書、サービスマニュアル、簡易説明書、またはSanyo KMS1812のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Sanyo KMS1812の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Sanyo KMS1812デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがSanyo KMS1812を使用するのを助ける技術的文書のことです。説明書は通常、全てのSanyo KMS1812ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Sanyoの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Sanyo KMS1812の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははSanyo KMS1812の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Sanyo KMS1812に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Sanyo KMS1812デバイスの基本機能を使うにあたってのヒント。 Sanyo KMS1812のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Sanyo KMS1812に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるSanyo KMS1812のメーカー/サービスへの連絡先に関する情報。

Sanyo KMS1812についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもSanyo KMS1812の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがSanyo KMS1812で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)