    1 of 18 3015-4568 Revision 0 9/11/03 Installation Guide Bacharach HGM300 to LonWorks FT-10 Communications Adapter Introduction The Bacharach HGM300 to LonWorks Comm unications Adapter enables an HGM300 Refrigerant Monitor to communicate with a LonWorks FT-10 Free Topology network. Zone PPM readings, flow status, refrigerant selections, and HGM inte ...

  • Bacharach FT-10 - page 2

    2 of 18 front side of the door. Position the adap ter board over the s tandoffs mounted on the HGM door. Install the five remaining 6- 32 screws through the board and into the standoffs and tighten. Connect power wiring from the HGM300’s 120V Auxiliary Power term inal block to the adapter board’s POWER terminal block. Use UL approved wire. W ir ...

  • Bacharach FT-10 - page 3

    3 of 18 If an RDM800 remote display IS to be used w ith the adapter, refer to Figure 3 for wiring details. Note that when the RDM800 is used, TWO RS-485 cables must be run betw een the HGM300 and RDM800, so plan accordingly. In either case, be sure to set the HGM300’s in ternal “Terminator” s lide switch next to the RS-485 terminal block to t ...

  • Bacharach FT-10 - page 4

    4 of 18 ...

  • Bacharach FT-10 - page 5

    5 of 18 Setting HGM Communication Address On Adapter See Figure 4 for the location of adapter dipswitch ‘A’. Switches 5-8 on the adapter’s ‘A ’ dipswitch are used to matc h the node address set on the HGM’s address dipswitch (on HGM main boa rd). Values from 0-15 are possible: HGM address A5 A6 A7 A8 ----------------- ------------------ ...

  • Bacharach FT-10 - page 6

    6 of 18 ...

  • Bacharach FT-10 - page 7

    7 of 18 Configuring the HGM300 with RDM800 or Laptop PC The only HGM parameters that are cha ngeable through LonWorks are the alarm thresholds. Configuring the HGM for refriger ant type and length of tubing for each zone (zero length to disable a zone ) must be done with the RDM800 remote display or a laptop PC. Refer to the appropriate Bacharach i ...

  • Bacharach FT-10 - page 8

    8 of 18 HGM Alarm Acknowledge Options Two alarm acknowledge options are s upported—Auto Acknowledge and Network Acknowledge. In the Auto Acknowledge mode, the HGM will clear its alarm outputs the next tim e the alarmed zone is sampled and its PP M has dropped below the alarm thresholds. No intervention from the LonW or ks network is necessary. In ...

  • Bacharach FT-10 - page 9

    9 of 18 LonWorks Objects and Network Variables The adapter contains one Node Object, sixteen Zone Objects, one Ge neral Status Object, and one Alarm Control Object. There is one Zone Object fo r each refrigerant sampling zone. Object 0 – The Node Object Network input variable nviRequest allows the user to requ est information from different objec ...

  • Bacharach FT-10 - page 10

    10 of 18 Network output variable nvoStatus returns the information requested by nviRequest. The status response will indicate the status of the object that received the request. The status bits supported are list ed above under RQ_REPORT_MASK. One nvoStatus response will be returned for each nviRequest. The configuration variable nciMaxStsSendT can ...

  • Bacharach FT-10 - page 11

    11 of 18 Objects 1-16 – Zone Objects There is one Zone Object for each sampling zone in the HGM300 (16 total): Network output variable nvoHgmZonePPM shows the m easured gas concentration for a particular zone. The value will range from 0-65535 PPM. Network output variable nvoHgmZoneStatus is a text string that displays inform ation about the zone ...

  • Bacharach FT-10 - page 12

    12 of 18 CRITICAL FAULT Some critical fault pr events normal zone PPM m easurement. (View nvoHgmFaults for details on fault type) HGM BUSY Occurs with RDM800 insta lled when certain scr eens are displayed. COMM FAULT 1 Comm failure between HGM and adapter. COMM FAULT 2 Comm failure between adapter internal processors. HGM WARMING UP HGM must go thr ...

  • Bacharach FT-10 - page 13

    13 of 18 Object 17 – General Status Objec t The General Status Object provides info rmation about any HGM300 internal faults present and shows which zone is currently being sampled: Network output variable nvoHgmFaultAlert reports whenever ANY fault is detected within the HGM or adapter. It is of type S NVT_switch. It is useful for binding to a F ...

  • Bacharach FT-10 - page 14

    14 of 18 HGM Busy (if RDM800 attached a nd showing certain screens)(bit 4) Comm Fault 1 (communications fail ed between HGM and adapter)(bit 3) Comm Fault 2 (internal communicati ons failed within adapter)(bit 2) Unused (bit 1) Unused (bit 0)(least significant b it) Network output variable nvoZ oneSampling shows which zone is currently being sample ...

  • Bacharach FT-10 - page 15

    15 of 18 Object 18 – Alarm Control Object The Alarm Control Object provides information about any alarm s which are present in the HGM. It also provides mechanisms fo r acknowledging alarm s, and for viewing and setting the Leak, Spill, and Evacuate alarm thresholds for each zone: Network input variable nviHgmAlarmAck has a single parameter (unsi ...

  • Bacharach FT-10 - page 16

    16 of 18 Network input variable nviSetZoneThresh allows Leak, Spill, and Eva cuate alarm thresholds (in PPM) to be set for each m onitoring zone. nviSetZoneThresh has four parameters to be set by the user: Zone Specifier: a number 1-16 specifies which zone is having its thresholds changed Leak Alarm Threshold: a number 0–65535 PPM Spill Alarm Thr ...

  • Bacharach FT-10 - page 17

    17 of 18 Network output variable nvoHgmZoneThresh displays the following in formation for the zone specified by nviGetZoneThresh: 1. Zone (1-16) whose alarm th resholds are being displayed 2. Leak Alarm Threshold in PPM (0-65535) 3. Spill Alarm Threshold in PPM (0-65535) 4. Evacuate Alarm Threshold in PPM (0-65535) To change the Leak, Spill, or Eva ...

  • Bacharach FT-10 - page 18

    18 of 18 LED 1 and LED 2 will normally show activ ity about every 15 seconds. Since the refrigerant monitoring process is fairly slow and new data is only available every 15 seconds or so, the adapter po lls the HGM at a slow rate to reduce the com munications burden on the HGM main processor. Agai n, commands com ing in from LonWorks might occasio ...

Fabricant Bacharach Catégorie Network Card

Les documents que nous recevons du fabricant de l'appareilBacharach FT-10 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Bacharach
- manuels d’utilisations FT-10
- fiches produit Bacharach
- dépliants
- ou étiquettes-énergie Bacharach FT-10
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Bacharach FT-10.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Bacharach FT-10, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Bacharach FT-10. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Bacharach FT-10.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Bacharach FT-10, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Bacharach FT-10 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Bacharach FT-10.

Le manuel d’utilisation complet Bacharach, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Bacharach FT-10 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Bacharach FT-10, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lBacharach FT-10 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Bacharach FT-10 - qui devraient nous aider dans les premières étapes lors de l'utilisation Bacharach FT-10
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Bacharach FT-10
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Bacharach FT-10 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Bacharach FT-10?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Bacharach FT-10, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Bacharach FT-10 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)