    FieldPoint TM cFP-20 xx Quick Start Guide What Y ou Need to Get Set Up • cFP-20 xx LabVIEW RT controller • Mounting hardware (DIN rail, panel- mount, or rack-mount accessory) • I/O module(s) • Connectivity accessories: connector blocks, cables • 11–30 V power supply • Accessories: Ethernet cable, screwdriver • PC running Windows • ...

  • National Instruments CFP-20XX - page 2

    2 cFP-20xx Quick Start Guide ni.com Mounting the Backplane on a DIN Rail A. Fasten the DIN rail clip(s) to the cFP-BP- x using a number 2 Phillips screwdriver and the 8-32 × 5/16 in. countersink screws shipped with the clip(s). B. Insert one edge of the DIN rail into the deeper opening of the DIN rail clip. C. Press down firmly on the backplane to ...

  • National Instruments CFP-20XX - page 3

    Mounting the Backplane on a Panel A. Fasten the panel-mount plates to the back of the cFP-BP- x using a number 2 Phillips screwdriver and the 8-32 × 5/16 in. countersink screws shipped with the kit. B. Bolt or screw the panel-mount accessory to a panel. C. Connect the PE ground terminal on the cFP-BP- x to safety ground. N A TIO N A L IN S TR U M ...

  • National Instruments CFP-20XX - page 4

    Mounting the Backplane in a Standard 19-in. Rack A. Fasten the rack-mount bracket to the back of the cFP-BP- x using the captive screws on the bracket. B. Bolt the rack-mount accessory to a standard 19-in. rack. C. Connect the PE ground terminal on the cFP-BP- x to safety ground. C C A A U U T T I I O O N N Disconnect power before removing the back ...

  • National Instruments CFP-20XX - page 5

    I I n n s s t t a a l l l l t t h h e e c c F F P P - - 2 2 0 0 x x x x C C o o n n t t r r o o l l l l e e r r o o n n t t h h e e B B a a c c k k p p l l a a n n e e A. Make sure that no power is connected to the controller or the backplane. B. Make sure that the cFP-20 xx controller is right side up with the NI logo at the top, and align the cap ...

  • National Instruments CFP-20XX - page 6

    6 cFP-20xx Quick Start Guide ni.com I I n n s s t t a a l l l l I I / / O O M M o o d d u u l l e e s s o o n n t t h h e e B B a a c c k k p p l l a a n n e e A. Align the captive screws on the I/O module with the holes on the backplane. B. Press firmly to seat the I/O module on the backplane. C. Using a number 2 Phillips screwdriver with a shank ...

  • National Instruments CFP-20XX - page 7

    I I n n s s t t a a l l l l C C o o n n n n e e c c t t o o r r B B l l o o c c k k s s o o n n t t h h e e B B a a c c k k p p l l a a n n e e In order to connect I/O modules to input signals or to external loads, you need to install a cFP-CB- x connector block or other connectivity accessory for each I/O module on the backplane. Use the connector ...

  • National Instruments CFP-20XX - page 8

    C C o o n n n n e e c c t t t t h h e e c c F F P P - - 2 2 0 0 x x x x t t o o Y Y o o u u r r N N e e t t w w o o r r k k Connect the cFP-20 xx controller to an Ethernet network using the RJ-45 Ethernet port on the controller . Use a standard Category 5 Ethernet cable to connect the cFP-20 xx to an Ethernet hub, or use an Ethernet crossover cable ...

  • National Instruments CFP-20XX - page 9

    C. Use a separate power supply for each module that needs external power . D. Refer to the operating instructions for the power requirements of each I/O module. If a module requires external power , connect a power supply to the V and C inputs on the connector block for that module. If you want to power field I/O devices from a connector block, sup ...

  • National Instruments CFP-20XX - page 10

    I I n n s s t t a a l l l l S S o o f f t t w w a a r r e e o o n n t t h h e e H H o o s s t t P P C C A. Install the software packages you plan to use, such as LabVIEW , LabVIEW RT , Lookout, Measurement Studio, or LabWindows/CVI, before you install the FieldPoint software. The FieldPoint software installation installs the LabVIEW VIs and example ...

  • National Instruments CFP-20XX - page 11

    11 cFP-20xx Quick Start Guide © National Instruments Corporation C. Click the + + sign next to I I A A S S e e r r v v e e r r w w i i t t h h O O P P C C in the left pane to expand the view . Right-click F F i i e e l l d d P P o o i i n n t t and select A A d d d d a a c c o o m m m m r r e e s s o o u u r r c c e e t t o o t t h h i i s s s s e ...

  • National Instruments CFP-20XX - page 12

    G. Enter values on the Network Settings tab of the System Configuration dialog box, shown in the figure at right. If your network does not have a gateway server or DNS server , you should set those parameters to 0.0.0.0. • I I P P A A d d d d r r e e s s s s —The unique, computer-readable address of a device on your network. An IP address is ty ...

  • National Instruments CFP-20XX - page 13

    I. Enter an IP address for the T ime Server on the Servers tab of the System Configuration dialog box, shown in the figure at right. The time server is a networked computer that runs the National Instruments T ime Service installed by FieldPoint Explorer . Enter the IP address of the PC you are using. When you finish configuring the controller , th ...

  • National Instruments CFP-20XX - page 14

    14 cFP-20xx Quick Start Guide ni.com F F i i n n d d i i n n g g a a n n d d C C o o n n f f i i g g u u r r i i n n g g D D e e v v i i c c e e s s a a n n d d C C h h a a n n n n e e l l s s After you have configured the cFP-20 xx in FieldPoint Explorer , follow these steps to configure Compact FieldPoint devices and channels. A. In the Comm Reso ...

  • National Instruments CFP-20XX - page 15

    C. T o configure the hardware settings of a particular I/O module, right-click the device name and select E E d d i i t t t t h h i i s s d d e e v v i i c c e e . The Device Configuration dialog box appears, as shown in the figure above. For output modules, you can choose settings for Watchdog Configuration. Refer to the user manual for informatio ...

  • National Instruments CFP-20XX - page 16

    16 cFP-20xx Quick Start Guide ni.com D. Click C C h h a a n n n n e e l l C C o o n n f f i i g g u u r r a a t t i i o o n n to access the Channel Configuration dialog box, shown in the figure at right. Make your selections in this dialog box as follows: 1. Select the type of channel to show , then select the channel(s) that you want to change. T ...

  • National Instruments CFP-20XX - page 17

    17 cFP-20xx Quick Start Guide © National Instruments Corporation ...

  • National Instruments CFP-20XX - page 18

    18 cFP-20xx Quick Start Guide ni.com S S a a v v i i n n g g H H a a r r d d w w a a r r e e C C o o n n f f i i g g u u r r a a t t i i o o n n a a s s P P o o w w e e r r - - U U p p S S t t a a t t e e When you are satisfied with the hardware configuration of the FieldPoint system, you can save this configuration as the new power -up state for t ...

  • National Instruments CFP-20XX - page 19

    ni.com Go to ni.com/support for the most current manuals, examples, and troubleshooting information. For telephone support in the United States, create your service request at ni.com/ask and follow the calling instructions or dial 512 795 8248. For telephone support outside the United States, contact your local branch office: United States 512 683 ...

Fabricant National Instruments Catégorie Cell Phone

Les documents que nous recevons du fabricant de l'appareilNational Instruments CFP-20XX peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques National Instruments
- manuels d’utilisations CFP-20XX
- fiches produit National Instruments
- dépliants
- ou étiquettes-énergie National Instruments CFP-20XX
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation National Instruments CFP-20XX.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation National Instruments CFP-20XX, manuels d’entretien, brefs manuels ou manuels de l’utilisateur National Instruments CFP-20XX. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit National Instruments CFP-20XX.

Manuel d’utilisation complet de l’appareil National Instruments CFP-20XX, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser National Instruments CFP-20XX par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs National Instruments CFP-20XX.

Le manuel d’utilisation complet National Instruments, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel National Instruments CFP-20XX - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières National Instruments CFP-20XX, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lNational Instruments CFP-20XX qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil National Instruments CFP-20XX - qui devraient nous aider dans les premières étapes lors de l'utilisation National Instruments CFP-20XX
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de National Instruments CFP-20XX
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service National Instruments CFP-20XX dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de National Instruments CFP-20XX?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec National Instruments CFP-20XX, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec National Instruments CFP-20XX il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)