    TECHNICAL GUIDE LX SERIES SPLIT -SYSTEM AIR CONDITIONERS 13 SEER – R- 410A – 1 PHASE (1.5 THRU 5 NOMINAL TONS) MODELS: YCJD18 THRU 60 Due to continuous pro duct improvement, spec ifications are subject to cha nge with ou t notice. Visit us on the web at www .upgnet.com and www .york.com Additional rating informa tion can be foun d at: www .ahri ...

  • York YCJD18 THRU 60 - page 2

    840569-YTG-A-0612 2 Johnson Controls Unitary Products All dimensions are in inche s. They are subject to ch ange with- out notice. Certified dimensions will be provi ded upon request. Physical and Electr ical Dat a MODEL YCJD18 S41S1(H)(E) YCJD24 S41S1(H)(E) YCJD30 S41S1(H)(E) YCJD36 S41S1(H)(E) YCJD42 S41S2(H)(E) YCJD48 S41S1(H)(E) YCJD60 S41S1(E) ...

  • York YCJD18 THRU 60 - page 3

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 3 System Charge for V arious Matched Sy stems Out door Unit YCJD18 S41S1(H)(E) YCJD24 S41S1(H)(E) YCJD30 S41S1(H)(E) YCJD36 S41S1(H)(E) YCJD42 S41S2(H)(E) YCJD48 S41S1(H)(E) YCJD60 S41S1(E) Required Ori fice or TXV 1 , 2 0.048/4F1 0.055/4F1 0.061/4F1 0.065/4G1 0.073/4G1 0.073/4H1 0.087/4J1 Indoor ...

  • York YCJD18 THRU 60 - page 4

    840569-YTG-A-0612 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the out door unit, the smallest matc hed indoor unit, and 15 feet of interconnect i ng lin e tubing. 2. V erify the TXV or orifice and additional charge required for specific matched indoor unit in the syst ...

  • York YCJD18 THRU 60 - page 5

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL WIDTH RA TED CFM NET MBH SEER EER TOT AL SE N S. 13 SEER AC WITH AIR HANDLERS YCJD18S41S1(H)(E) AHE18B 17.5 – 610 17.9 13.8 14.75 12.25 AHP18 17.5 – 650 17.5 12.9 13.00 1 1.00 AHR18B 17.5 – 665 17 ...

  • York YCJD18 THRU 60 - page 6

    840569-YTG-A-0612 6 Johnson Controls Unitary Products YCJD36S41S1(H)(E) AHE36C 21.0 – 1 190 35.6 25.4 14.25 12 .00 AHE42D 24.5 – 1 180 35.8 25.8 14.50 12 .25 AHP36 21.0 – 1235 35.0 24.8 13.00 1 1.00 AHP42 21.0 – 1255 35.0 24.8 13.00 1 1.00 AHR36B 17.5 – 1245 34.6 24.6 13 .00 1 1.00 AHR42C 21.0 – 1230 35.6 25.4 13 .00 1 1.25 AHX36 21.0 ? ...

  • York YCJD18 THRU 60 - page 7

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 7 — = Not applicable. MA Modular Air Handlers use Coil Only Ratings. YCJD48S41S1(H)(E) AHE48D 24.5 – 1600 47.0 34.6 13.75 1 1.50 AHP48 24.5 – 167 5 48.0 34.4 13.00 1 1.00 AHP60 24.5 – 160 0 48.0 35.0 13.50 1 1.00 AHR48D 24.5 – 1610 48.0 34.6 13.00 1 1.00 AHX48 24.5 – 166 0 48.0 35.4 1 ...

  • York YCJD18 THRU 60 - page 8

    840569-YTG-A-0612 8 Johnson Controls Unitary Products MA Modular Air Handlers use Coil Only Ratings. PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Rating s. COOLING CAP ACITY - Up flow , Downflow & Horizo nt al Furnaces and Coils (Coil Only Ratings) UNIT MODEL COIL CFM RANGE (MIN.-MAX.) COOLING MODEL WIDTH RA TED CFM NET MBH SEE ...

  • York YCJD18 THRU 60 - page 9

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 9 COOLING CAP ACITY - With High Efficiency Motor Furna ces UNIT MODEL FURNACE COIL MODEL 1 COOLING MODEL WIDTH RA TED CFM NET MBH SEER EER TOT AL SE N S. 13 SEER AC WITH HIGH EFFICIENCY MOTOR FURNACES 2 YCJD18S41S1(H)(E) T*(8,L)V*A12 14.5 FC/MC/PC18A 620 17.5 12.7 14.50 12.50 T*(8,L)V*A12 14.5 UC ...

  • York YCJD18 THRU 60 - page 10

    840569-YTG-A-0612 10 Johnson Controls Unitary Products YCJD24S41S1(H)(E) Y*(8,L)C*A12 14.5 UC36A 805 23.6 16 .6 13.80 1 1.50 Y*(8,L)C*B12 17.5 FC/MC/PC35B 760 24.0 16.8 14.00 12 .00 Y*(8,L)C*B12 17.5 FC/MC/PC36B 765 24.0 17.0 14.00 12 .00 Y*(8,L)C*B12 17.5 FC/MC/PC43B 760 24.0 16.9 14.00 12 .00 Y*(8,L)C*B12 17.5 UC36B 765 23.6 16 .7 14.00 1 1.50 Y* ...

  • York YCJD18 THRU 60 - page 11

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 11 YCJD36S41S1(H)(E) T*(8,L)V*A12 14.5 FC/MC/PC37A 980 33.8 23.0 13.50 1 1.00 T*(8,L)V*B12 17.5 FC/MC/PC43B 1210 35.2 25.2 13.50 1 1.00 T*(8,L)V*C16 21.0 FC/MC/PC43C 1205 35.6 25.4 14.00 1 1.50 T*(8,L)V*C16 21.0 FC/MC/PC48C 1210 36.0 26.0 14.00 12.00 T*(8,L)V*C16 21.0 UC48C 1210 34.6 24.8 13.50 1 ...

  • York YCJD18 THRU 60 - page 12

    840569-YTG-A-0612 12 Johnson Controls Unitary Products YCJD42S41S2(H)(E) T*(8,L)V*B12 17.5 FC/MC/PC43B 1270 41.0 28.8 13.25 1 1.25 T*(8,L)V*C16 21.0 FC/MC/PC43C 1390 42.0 30 .2 13.50 1 1.50 T*(8,L)V*C16 21.0 FC/MC/PC48C 1330 42.0 29 .8 13.50 1 1.50 T*(8,L)V*C16 21.0 FC/MC/PC48D 1330 42.0 29 .8 13.50 1 1.50 T*(8,L)V*C16 21.0 FC/MC/PC60D 1420 42.0 30 ...

  • York YCJD18 THRU 60 - page 13

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 13 YCJD42S41S2(H)(E) T*9(C,V)*C20 21.0 FC64D 1445 42.0 30.8 13.75 1 1.75 T*9(C,V)*C20 21.0 UC48C 1430 42.0 30.2 13.25 1 1.25 T*9(C,V)*C20 21.0 UC60C 1445 41.5 29.8 13.00 1 1.25 T*9(C,V)*D20 24.5 FC/MC/PC48D 1450 42.0 30.2 13.50 1 1.50 T*9(C,V)*D20 24.5 FC/MC/PC60D 1445 42.0 30.0 13.50 1 1.50 T*9( ...

  • York YCJD18 THRU 60 - page 14

    840569-YTG-A-0612 14 Johnson Controls Unitary Products YCJD42S41S2(H)(E) Y*(8,L)C*C20 21.0 UC60C 1410 42.0 30.0 13.50 1 1.50 Y*9C*C16 21.0 FC/MC/PC43C 1360 42.0 30 .0 13.25 1 1.25 Y*9C*C16 21.0 FC/MC/PC48C 1395 42.0 30 .4 13.50 1 1.50 Y*9C*C16 21.0 FC/MC/PC48D 1395 42.0 30 .4 13.50 1 1.50 Y*9C*C16 21.0 FC/MC/PC60D 1445 41.5 29 .8 13.00 1 1.00 Y*9C* ...

  • York YCJD18 THRU 60 - page 15

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 15 PSC furnaces, such as the TG8S, TG LS, and TG9S, use Coil Only Ratings. YCJD48S41S1(H)(E) Y*9C*C20 21.0 FC/MC/PC48C 1655 48.0 34.8 13.20 1 1.00 Y*9C*C20 21.0 FC/PC60C 1655 48.0 35.2 13.10 1 1.00 Y*9C*D20 24.5 FC/MC/PC48D 1645 48.0 35.2 13.20 1 1.00 Y*9C*D20 24.5 FC/MC/PC60D 1615 48.0 35.0 13.2 ...

  • York YCJD18 THRU 60 - page 16

    840569-YTG-A-0612 16 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. Off Cycle Timer Delay - Provides a 5-minute off cycle to pre- vent rapid recycling of the compressor . St art Assist Kit (S1-2SA067*) - Provides in creased starting torque for areas with low voltage. See Hard St art Kit Accessory Ins ...

  • York YCJD18 THRU 60 - page 17

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 17 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York YCJD18 THRU 60 - page 18

    840569-YTG-A-0612 18 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YCJD18 THRU 60 - page 19

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 19 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC32A 1.00 1.02 0.96 T*(8,L)V*A12 FC/MC/PC36A 1.00 1.01 0.92 T*(8,L)V*A12 FC/MC/PC37A 1.00 1.02 0.92 T*(8,L)V*A12 UC36A 0.98 0.99 0.94 T*(8,L)V*B12 FC/MC/PC35B 1.00 1.01 0.92 T*(8,L)V*B12 FC/MC/PC36B 1.00 1.02 0.92 T*(8,L)V*B12 FC/MC/PC43B 1.00 1 ...

  • York YCJD18 THRU 60 - page 20

    840569-YTG-A-0612 20 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YCJD18 THRU 60 - page 21

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 21 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC32A 1.01 1.04 1.01 T*(8,L)V*A12 FC/MC/PC37A 1.03 1.04 0.98 T*(8,L)V*B12 FC/MC/PC35B 1.02 1.02 0.98 T*(8,L)V*B12 FC/MC/PC43B 1.03 1.05 0.95 T*(8,L)V*C16 FC/MC/PC35 C 1.02 1.05 0.94 T*(8,L)V*C16 FC/MC/PC43 C 1.03 1.05 0.95 T*(8,L)V*C20 FC/MC/PC35 ...

  • York YCJD18 THRU 60 - page 22

    840569-YTG-A-0612 22 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YCJD18 THRU 60 - page 23

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 23 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC37A 0.97 0.93 0.97 T*(8,L)V*B12 FC/MC/PC43B 1.01 1.02 1.01 T*(8,L)V*C16 FC/MC/PC43C 1.02 1.02 0.97 T*(8,L)V*C16 FC/MC/PC48C 1.03 1.05 0.94 T*(8,L)V*C16 UC48C 0.99 1.00 0.95 T*(8,L)V*C20 FC/MC/PC43C 1.02 1.02 0.93 T*(8,L)V*C20 FC/MC/PC48C 1.03 1 ...

  • York YCJD18 THRU 60 - page 24

    840569-YTG-A-0612 24 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YCJD18 THRU 60 - page 25

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 25 T*(8,L)V*C20 FC/PC60C 1.01 1.01 0.95 T*(8,L)V*C20 FC64D 1.01 1.03 0.93 T*(8,L)V*C20 UC48C 1.01 1.01 0.95 T*(8,L)V*C20 UC60C 1.01 1.01 0.97 T*(8,L)X*B12 FC/MC/PC43B 1.00 0.99 0.96 T*(8,L)X*C16 FC/MC/PC43C 1.01 1.04 0.95 T*(8,L)X*C16 FC/MC/PC48C 1.01 1.01 0.93 T*(8,L)X*C16 FC/MC/PC48D 1.01 1.01 ...

  • York YCJD18 THRU 60 - page 26

    840569-YTG-A-0612 26 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YCJD18 THRU 60 - page 27

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 27 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York YCJD18 THRU 60 - page 28

    Subject to change without notice. Published in U .S.A. 840569-YTG-A-0612 Copyright © 2012 by Johnson Controls, Inc. All rights reserved. Supersedes: 561908-YTG-D-0611 Y o rk International Corp. 5005 Y ork Drive Norman, OK 73069 NOTES ...

Fabricant York Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilYork YCJD18 THRU 60 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques York
- manuels d’utilisations YCJD18 THRU 60
- fiches produit York
- dépliants
- ou étiquettes-énergie York YCJD18 THRU 60
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation York YCJD18 THRU 60.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation York YCJD18 THRU 60, manuels d’entretien, brefs manuels ou manuels de l’utilisateur York YCJD18 THRU 60. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit York YCJD18 THRU 60.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil York YCJD18 THRU 60, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser York YCJD18 THRU 60 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs York YCJD18 THRU 60.

Le manuel d’utilisation complet York, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel York YCJD18 THRU 60 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières York YCJD18 THRU 60, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lYork YCJD18 THRU 60 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil York YCJD18 THRU 60 - qui devraient nous aider dans les premières étapes lors de l'utilisation York YCJD18 THRU 60
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de York YCJD18 THRU 60
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service York YCJD18 THRU 60 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de York YCJD18 THRU 60?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec York YCJD18 THRU 60, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec York YCJD18 THRU 60 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)