    TECHNICAL GUIDE LX SERIES SPLIT -SYSTEM AIR CONDITIONERS 13 SEER – R- 410A – 1 PHASE (1.5 THRU 5 NOMINAL TONS) MODELS: YCJD18 THRU 60 Due to continuous pro duct improvement, spec ifications are subject to cha nge with ou t notice. Visit us on the web at www .upgnet.com and www .york.com Additional rating informa tion can be foun d at: www .ahri ...

  • York YCJD18 THRU 60 - page 2

    840569-YTG-A-0612 2 Johnson Controls Unitary Products All dimensions are in inche s. They are subject to ch ange with- out notice. Certified dimensions will be provi ded upon request. Physical and Electr ical Dat a MODEL YCJD18 S41S1(H)(E) YCJD24 S41S1(H)(E) YCJD30 S41S1(H)(E) YCJD36 S41S1(H)(E) YCJD42 S41S2(H)(E) YCJD48 S41S1(H)(E) YCJD60 S41S1(E) ...

  • York YCJD18 THRU 60 - page 3

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 3 System Charge for V arious Matched Sy stems Out door Unit YCJD18 S41S1(H)(E) YCJD24 S41S1(H)(E) YCJD30 S41S1(H)(E) YCJD36 S41S1(H)(E) YCJD42 S41S2(H)(E) YCJD48 S41S1(H)(E) YCJD60 S41S1(E) Required Ori fice or TXV 1 , 2 0.048/4F1 0.055/4F1 0.061/4F1 0.065/4G1 0.073/4G1 0.073/4H1 0.087/4J1 Indoor ...

  • York YCJD18 THRU 60 - page 4

    840569-YTG-A-0612 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the out door unit, the smallest matc hed indoor unit, and 15 feet of interconnect i ng lin e tubing. 2. V erify the TXV or orifice and additional charge required for specific matched indoor unit in the syst ...

  • York YCJD18 THRU 60 - page 5

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL WIDTH RA TED CFM NET MBH SEER EER TOT AL SE N S. 13 SEER AC WITH AIR HANDLERS YCJD18S41S1(H)(E) AHE18B 17.5 – 610 17.9 13.8 14.75 12.25 AHP18 17.5 – 650 17.5 12.9 13.00 1 1.00 AHR18B 17.5 – 665 17 ...

  • York YCJD18 THRU 60 - page 6

    840569-YTG-A-0612 6 Johnson Controls Unitary Products YCJD36S41S1(H)(E) AHE36C 21.0 – 1 190 35.6 25.4 14.25 12 .00 AHE42D 24.5 – 1 180 35.8 25.8 14.50 12 .25 AHP36 21.0 – 1235 35.0 24.8 13.00 1 1.00 AHP42 21.0 – 1255 35.0 24.8 13.00 1 1.00 AHR36B 17.5 – 1245 34.6 24.6 13 .00 1 1.00 AHR42C 21.0 – 1230 35.6 25.4 13 .00 1 1.25 AHX36 21.0 ? ...

  • York YCJD18 THRU 60 - page 7

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 7 — = Not applicable. MA Modular Air Handlers use Coil Only Ratings. YCJD48S41S1(H)(E) AHE48D 24.5 – 1600 47.0 34.6 13.75 1 1.50 AHP48 24.5 – 167 5 48.0 34.4 13.00 1 1.00 AHP60 24.5 – 160 0 48.0 35.0 13.50 1 1.00 AHR48D 24.5 – 1610 48.0 34.6 13.00 1 1.00 AHX48 24.5 – 166 0 48.0 35.4 1 ...

  • York YCJD18 THRU 60 - page 8

    840569-YTG-A-0612 8 Johnson Controls Unitary Products MA Modular Air Handlers use Coil Only Ratings. PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Rating s. COOLING CAP ACITY - Up flow , Downflow & Horizo nt al Furnaces and Coils (Coil Only Ratings) UNIT MODEL COIL CFM RANGE (MIN.-MAX.) COOLING MODEL WIDTH RA TED CFM NET MBH SEE ...

  • York YCJD18 THRU 60 - page 9

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 9 COOLING CAP ACITY - With High Efficiency Motor Furna ces UNIT MODEL FURNACE COIL MODEL 1 COOLING MODEL WIDTH RA TED CFM NET MBH SEER EER TOT AL SE N S. 13 SEER AC WITH HIGH EFFICIENCY MOTOR FURNACES 2 YCJD18S41S1(H)(E) T*(8,L)V*A12 14.5 FC/MC/PC18A 620 17.5 12.7 14.50 12.50 T*(8,L)V*A12 14.5 UC ...

  • York YCJD18 THRU 60 - page 10

    840569-YTG-A-0612 10 Johnson Controls Unitary Products YCJD24S41S1(H)(E) Y*(8,L)C*A12 14.5 UC36A 805 23.6 16 .6 13.80 1 1.50 Y*(8,L)C*B12 17.5 FC/MC/PC35B 760 24.0 16.8 14.00 12 .00 Y*(8,L)C*B12 17.5 FC/MC/PC36B 765 24.0 17.0 14.00 12 .00 Y*(8,L)C*B12 17.5 FC/MC/PC43B 760 24.0 16.9 14.00 12 .00 Y*(8,L)C*B12 17.5 UC36B 765 23.6 16 .7 14.00 1 1.50 Y* ...

  • York YCJD18 THRU 60 - page 11

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 11 YCJD36S41S1(H)(E) T*(8,L)V*A12 14.5 FC/MC/PC37A 980 33.8 23.0 13.50 1 1.00 T*(8,L)V*B12 17.5 FC/MC/PC43B 1210 35.2 25.2 13.50 1 1.00 T*(8,L)V*C16 21.0 FC/MC/PC43C 1205 35.6 25.4 14.00 1 1.50 T*(8,L)V*C16 21.0 FC/MC/PC48C 1210 36.0 26.0 14.00 12.00 T*(8,L)V*C16 21.0 UC48C 1210 34.6 24.8 13.50 1 ...

  • York YCJD18 THRU 60 - page 12

    840569-YTG-A-0612 12 Johnson Controls Unitary Products YCJD42S41S2(H)(E) T*(8,L)V*B12 17.5 FC/MC/PC43B 1270 41.0 28.8 13.25 1 1.25 T*(8,L)V*C16 21.0 FC/MC/PC43C 1390 42.0 30 .2 13.50 1 1.50 T*(8,L)V*C16 21.0 FC/MC/PC48C 1330 42.0 29 .8 13.50 1 1.50 T*(8,L)V*C16 21.0 FC/MC/PC48D 1330 42.0 29 .8 13.50 1 1.50 T*(8,L)V*C16 21.0 FC/MC/PC60D 1420 42.0 30 ...

  • York YCJD18 THRU 60 - page 13

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 13 YCJD42S41S2(H)(E) T*9(C,V)*C20 21.0 FC64D 1445 42.0 30.8 13.75 1 1.75 T*9(C,V)*C20 21.0 UC48C 1430 42.0 30.2 13.25 1 1.25 T*9(C,V)*C20 21.0 UC60C 1445 41.5 29.8 13.00 1 1.25 T*9(C,V)*D20 24.5 FC/MC/PC48D 1450 42.0 30.2 13.50 1 1.50 T*9(C,V)*D20 24.5 FC/MC/PC60D 1445 42.0 30.0 13.50 1 1.50 T*9( ...

  • York YCJD18 THRU 60 - page 14

    840569-YTG-A-0612 14 Johnson Controls Unitary Products YCJD42S41S2(H)(E) Y*(8,L)C*C20 21.0 UC60C 1410 42.0 30.0 13.50 1 1.50 Y*9C*C16 21.0 FC/MC/PC43C 1360 42.0 30 .0 13.25 1 1.25 Y*9C*C16 21.0 FC/MC/PC48C 1395 42.0 30 .4 13.50 1 1.50 Y*9C*C16 21.0 FC/MC/PC48D 1395 42.0 30 .4 13.50 1 1.50 Y*9C*C16 21.0 FC/MC/PC60D 1445 41.5 29 .8 13.00 1 1.00 Y*9C* ...

  • York YCJD18 THRU 60 - page 15

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 15 PSC furnaces, such as the TG8S, TG LS, and TG9S, use Coil Only Ratings. YCJD48S41S1(H)(E) Y*9C*C20 21.0 FC/MC/PC48C 1655 48.0 34.8 13.20 1 1.00 Y*9C*C20 21.0 FC/PC60C 1655 48.0 35.2 13.10 1 1.00 Y*9C*D20 24.5 FC/MC/PC48D 1645 48.0 35.2 13.20 1 1.00 Y*9C*D20 24.5 FC/MC/PC60D 1615 48.0 35.0 13.2 ...

  • York YCJD18 THRU 60 - page 16

    840569-YTG-A-0612 16 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. Off Cycle Timer Delay - Provides a 5-minute off cycle to pre- vent rapid recycling of the compressor . St art Assist Kit (S1-2SA067*) - Provides in creased starting torque for areas with low voltage. See Hard St art Kit Accessory Ins ...

  • York YCJD18 THRU 60 - page 17

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 17 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York YCJD18 THRU 60 - page 18

    840569-YTG-A-0612 18 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YCJD18 THRU 60 - page 19

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 19 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC32A 1.00 1.02 0.96 T*(8,L)V*A12 FC/MC/PC36A 1.00 1.01 0.92 T*(8,L)V*A12 FC/MC/PC37A 1.00 1.02 0.92 T*(8,L)V*A12 UC36A 0.98 0.99 0.94 T*(8,L)V*B12 FC/MC/PC35B 1.00 1.01 0.92 T*(8,L)V*B12 FC/MC/PC36B 1.00 1.02 0.92 T*(8,L)V*B12 FC/MC/PC43B 1.00 1 ...

  • York YCJD18 THRU 60 - page 20

    840569-YTG-A-0612 20 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YCJD18 THRU 60 - page 21

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 21 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC32A 1.01 1.04 1.01 T*(8,L)V*A12 FC/MC/PC37A 1.03 1.04 0.98 T*(8,L)V*B12 FC/MC/PC35B 1.02 1.02 0.98 T*(8,L)V*B12 FC/MC/PC43B 1.03 1.05 0.95 T*(8,L)V*C16 FC/MC/PC35 C 1.02 1.05 0.94 T*(8,L)V*C16 FC/MC/PC43 C 1.03 1.05 0.95 T*(8,L)V*C20 FC/MC/PC35 ...

  • York YCJD18 THRU 60 - page 22

    840569-YTG-A-0612 22 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YCJD18 THRU 60 - page 23

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 23 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC37A 0.97 0.93 0.97 T*(8,L)V*B12 FC/MC/PC43B 1.01 1.02 1.01 T*(8,L)V*C16 FC/MC/PC43C 1.02 1.02 0.97 T*(8,L)V*C16 FC/MC/PC48C 1.03 1.05 0.94 T*(8,L)V*C16 UC48C 0.99 1.00 0.95 T*(8,L)V*C20 FC/MC/PC43C 1.02 1.02 0.93 T*(8,L)V*C20 FC/MC/PC48C 1.03 1 ...

  • York YCJD18 THRU 60 - page 24

    840569-YTG-A-0612 24 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YCJD18 THRU 60 - page 25

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 25 T*(8,L)V*C20 FC/PC60C 1.01 1.01 0.95 T*(8,L)V*C20 FC64D 1.01 1.03 0.93 T*(8,L)V*C20 UC48C 1.01 1.01 0.95 T*(8,L)V*C20 UC60C 1.01 1.01 0.97 T*(8,L)X*B12 FC/MC/PC43B 1.00 0.99 0.96 T*(8,L)X*C16 FC/MC/PC43C 1.01 1.04 0.95 T*(8,L)X*C16 FC/MC/PC48C 1.01 1.01 0.93 T*(8,L)X*C16 FC/MC/PC48D 1.01 1.01 ...

  • York YCJD18 THRU 60 - page 26

    840569-YTG-A-0612 26 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73- 87 °F), sensible capacity increa ses by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM ...

  • York YCJD18 THRU 60 - page 27

    840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 27 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York YCJD18 THRU 60 - page 28

    Subject to change without notice. Published in U .S.A. 840569-YTG-A-0612 Copyright © 2012 by Johnson Controls, Inc. All rights reserved. Supersedes: 561908-YTG-D-0611 Y o rk International Corp. 5005 Y ork Drive Norman, OK 73069 NOTES ...

Manufacturer York Category Air Conditioner

Documents that we receive from a manufacturer of a York YCJD18 THRU 60 can be divided into several groups. They are, among others:
- York technical drawings
- YCJD18 THRU 60 manuals
- York product data sheets
- information booklets
- or energy labels York YCJD18 THRU 60
All of them are important, but the most important information from the point of view of use of the device are in the user manual York YCJD18 THRU 60.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York YCJD18 THRU 60, service manual, brief instructions and user manuals York YCJD18 THRU 60. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York YCJD18 THRU 60.

Similar manuals

A complete manual for the device York YCJD18 THRU 60, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York YCJD18 THRU 60 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York YCJD18 THRU 60.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York YCJD18 THRU 60 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York YCJD18 THRU 60, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York YCJD18 THRU 60, that we can find in the current document
3. Tips how to use the basic functions of the device York YCJD18 THRU 60 - which should help us in our first steps of using York YCJD18 THRU 60
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York YCJD18 THRU 60
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of York YCJD18 THRU 60 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning York YCJD18 THRU 60?

Use the form below

If you did not solve your problem by using a manual York YCJD18 THRU 60, ask a question using the form below. If a user had a similar problem with York YCJD18 THRU 60 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)