    PO WER SY STEMS, INC. ® Installation, Start-up and Adjustment Manual Air -cooled, Prepackaged Standby Generators Models: Nonsound Attenuated (Non-SA) 04077-1 (6 kW) 04109-1 (8 kW) 04079-1 (10 kW) Sound Attenuated (SA) 00789-1 (8 kW) 00844-1 (8 kW) ONL Y QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD A TTEMPT INST ALLA TION!! ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 2

    Generac ® Pow er Systems, Inc. I NTRODUCTION Thank you for purchasing a model of the Guardian product line by Generac P ower Systems Inc. These models are compact, high performance, air - cooled, engine - driven generators designed to automatically supply electrical power to operate critical loads dur- ing a utility power failure. This unit is fac ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 3

    T able of Contents Guardian Air-cooled Generators Generac® Pow er Systems, Inc. 1 Introduction ......................Inside Front Cover Read This Manual Thoroughly ......................IFC Operation and Maintenance ............................IFC How to Obtain Service ....................................IFC Authorized Dealer Location Number...... ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 4

    2 Generac ® Pow er Systems, Inc. Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Installation, Start -up and Adjustment Manual and with the unit. The generator can operate safely , efficiently and reliably only if it is properly installed, operated and maintained. Many accident ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 5

    Generac ® Pow er Systems, Inc. 3 ELE CTR ICAL HA Z AR DS • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera- tion. A void contact with bare wires, t ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 6

    1.1 I NTRODUCTION T O I NST ALL A TION NOTE: Read the entire manual before starting the installa- tion. Ensure that the model number of the unit being installed matches a model on the front cover . Generac cannot possibly know of and advise the home standby trade of all conceivable procedures and meth- ods by which installation of this equipment mi ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 7

    1.3 B EFOR E I NS T ALLA TION Before installing this equipment, check the ratings of both the generator and the transfer switch. Read “Emergency Circuit Isolation Method” and “T otal Circuit Isolation Method” in Sections 1.8 and 1.9 (P age 11) carefully . The generator's rated wattage/amperage capacity must be adequate to handle all el ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 8

    6 Generac ® Pow er Systems, Inc. W ith LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed above the liq- uid fuel in the storage tank. The engine has been fitted with a fuel carburetion sys- tem that meets the specifications of the 1997 California Air Resources Board for tamper -proof dual fuel sys- tems. The ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 9

    Generac ® Pow er Systems, Inc. 7 3. Refit the fitting and hose to the LP port and the blanking plug to the natural gas port (Figure 1.3). 4. Reverse the procedure to convert back to natural gas. NOTE: The natural gas adjustment screw is preset during installation and should not need any further adjustment. Figure 1.3 – LP Gas Setup 1.7 L OCA TIO ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 10

    8 Generac ® Pow er Systems, Inc. Figure 1.4 – Generator and Transfer Switch Mounting Dimensions (6 kW, 8 kW and 10 kW Non-SA) Section 1 — Installation Guardian Air-cooled Generators ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 11

    Generac ® Pow er Systems, Inc. 9 Figure 1.4 (Continued) Section 1 — Installation Guardian Air-cooled Generators ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 12

    10 Generac ® Pow er Systems, Inc. Figure 1.5 – Generator Mounting Dimensions (Sound Attenuated) Section 1 — Installation Guardian Air-cooled Generators ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 13

    Generac ® Pow er Systems, Inc. 11 1.8 EM ERGENCY CI RCU IT IS OL A TION METHOD One effective way of preventing the generator from being overloaded is to use the “Emergency Circuit Isolation Method” (Figure 1.6). Essential electrical loads are grouped together and wired into a separate emergency distribution panel. Load circuits fed by the emer ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 14

    12 Generac ® Pow er Systems, Inc. 1.1 0 GEN ER A T OR A C C ON N E CTION S Y S TEM Figure 1.8 represents a single-phase, three -wire gen- erator AC connection system. The stator assembly in this system consists of a pair of stationary windings with two leads brought out of each winding . Each sin- gle winding can supply a 120-volt, 60-Hertz AC out ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 15

    Generac ® Pow er Systems, Inc. 13 Section 1 — Installation Guardian Air-cooled Generators Figure 1.10 – Interconnection Diagram for Single-Phase Power System (Sound Attenuated) Figure 1.9 – Interconnection Diagram for Single-Phase Power System (6 kW, 8 kW and 10 kW Non-SA) ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 16

    14 Generac ® Pow er Systems, Inc. 1.1 2 GEN ER A T ORS AND GT S TR ANSF ER SWIT CH ES Guardian generators (this DOES NOT APPL Y to single - phase sound attenuated units) may be installed with either a prepackaged transfer switch or with a stan- dard GTS -type automatic transfer switch (Figure 1.11). Y ou can do this by connecting generator control ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 17

    Generac ® Pow er Systems, Inc. 15 1.1 4 AD APTING TH R EE-P HA SE TR ANSF ER SWIT CH The generator you are installing may include a prepackaged transfer switch configured for three - phase loads. If you want to adapt this kind of transfer switch for single -phase loads, proceed as follows: 1. Discard the three-phase power monitor (PM) found inside ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 18

    16 Generac ® Pow er Systems, Inc. 1.1 7 TH E B A TTER Y Servicing of the battery is to be performed or super- vised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized person- nel away from batteries. When replacing the battery , use the following type of battery: Group 26/26R 12-volt battery with a rating of 35 ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 19

    Generac ® Pow er Systems, Inc. 17 1.1 7 .1 BA TTERY INST ALLA TION Fill the battery with the proper electrolyte fluid if nec- essary and have the battery fully charged before installing it. Before installing and connecting the battery , complete the following steps: 1. Set the generator's A uto/Off/Manual switch to OFF . 2. T urn off utility ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 20

    18 Generac ® Pow er Systems, Inc. NOTE: Throughout the “Operation ” section, differences in procedures specific to sound attenuated units will be denoted as follows: (SA = information). 2.1 USI NG TH E AUT O/OF F/MAN UAL SWIT CH (FIGURE 2.1/2.2) 2.1.1 “ AUT O” POSITION Selecting this switch position activates fully automat- ic system opera ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 21

    Generac ® Pow er Systems, Inc. 19 2.3 SE QU ENCE OF AUT OMA TIC OP ER A TION The generator’s control panel houses a control logic circuit board. This board constantly monitors utili- ty power source voltage. Should that voltage drop below a preset level, circuit board action will signal the engine to crank and start. After the engine starts, the ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 22

    20 Generac ® Pow er Systems, Inc. 6. T o crank and start the engine, set the Auto/Off/Manual switch to MANU AL. 7. Let the engine stabilize and warm up for a few minutes. 8. Set the generator’s main circuit breaker to its ON (or closed) position. The standby power source now powers the loads. 2.4.2 TR ANSFER BA CK T O UTI LITY POWER S OURCE When ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 23

    2.5.3.1 Approximat e Crank Cycle T imes • 15 seconds ON • 15 seconds OFF • 7 seconds ON • 7 seconds OFF • Repeat for 45 seconds Approximately 90 seconds total 2.5.4 OVERSPEED This feature protects the generator from damage by shutting it down if it happens to run faster than the pre- set limit. This protection also prevents the generator ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 24

    22 Generac ® Pow er Systems, Inc. 3.1 B EFOR E I N ITIAL S T ART -U P Before starting, complete the following: 1. Set the generator's A uto/Off/Manual switch to the OFF position. 2. T urn OFF the utility power supply to the transfer switch using the means provided (such as the utility main line circuit breaker). 3. Check the engine crankcase ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 25

    Generac ® Pow er Systems, Inc. 23 Do not attempt manual transfer switch operation until all power voltage supplies to the transfer switch have been positively turned off. Failur e to turn off all power voltage supplies will result in extr emely hazardous and possibly fatal electrical shock. 4. Manually set the transfer switch to the ST ANDB Y posi ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 26

    24 Generac ® Pow er Systems, Inc. 3.7 ENGI N E G O VER NOR ADJ US TM ENT If both AC frequency and voltage are correspondingly high or low , adjust the engine governor as follows: 3.7 .1 6 KW U N IT S (NON-SA) 1. Loosen the governor clamp bolt (F igure 3.1). 2. Push the spring end of the governor lever clock- wise to the wide open throttle position ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 27

    Generac ® Pow er Systems, Inc. 25 3.7 .3 SOUN D A T TEN UA TED UN ITS 1. Carefully inspect the governor anti-lash spring (Figure 3.3). Be sure it is not broken or disengaged. 2. Loosen the governor clamp nut. Then, push the spring end of the governor lever all the way up (wide open throttle). 3. Hold the governor lever at wide open throttle and in ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 28

    26 Generac ® Pow er Systems, Inc. 3.1 0 SE T TI NG TH E EXERCISE TI M ER 3.1 0.1 6 KW , 8 KW AN D 1 0 KW UN ITS (NON-S A) Y our generator is equipped with an exercise timer . Once it is set, the generator will start and exercise once every seven days, on the day of the week and at the time of day you complete the following sequence. During this ex ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 29

    Generac ® Pow er Systems, Inc. 27 4.1 TROU B LE SHOO TI NG GU I DE P ROB LEM CAUSE C OR R E CTION The engine will not crank. 1. F use blown 1. Replace fuse. 2. Loose, corroded or defective 2. T ighten, clean or replace battery cables as necessary . 3. Defective starter contactor 3. Replace starter contactor . 4. Defective starter motor 4. Replace ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 30

    28 Generac ® Pow er Systems, Inc. Section 4 — T roubleshooting Guardian Air-cooled Generators 4.2 I NS T ALLA TION CH ECKLIS T BA TTER Y INST ALL A TION ❏ Battery is connected properly . ❏ Recommended battery is installed. ❏ Cables are clean and tight. ❏ T erminals are coated with anti- corrosion grease, and terminal covers are positione ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 31

    Generac ® Pow er Systems, Inc. 29 Section 5 — Notes Guardian Air-cooled Generators ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 32

    Part No. C4219 GENERAC ® POWER SY STEMS, INC. P .O. BOX 8 W AUKESHA, WI 53187 Revision * (12/13/99) Printed in U.S.A. ...

Fabricant Generac Catégorie Portable Generator

Les documents que nous recevons du fabricant de l'appareilGenerac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Generac
- manuels d’utilisations 04077-1, 04109-1, 04079-1, 00789-1, 00844-1
- fiches produit Generac
- dépliants
- ou étiquettes-énergie Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1.

Le manuel d’utilisation complet Generac, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lGenerac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - qui devraient nous aider dans les premières étapes lors de l'utilisation Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)