    PO WER SY STEMS, INC. ® Installation, Start-up and Adjustment Manual Air -cooled, Prepackaged Standby Generators Models: Nonsound Attenuated (Non-SA) 04077-1 (6 kW) 04109-1 (8 kW) 04079-1 (10 kW) Sound Attenuated (SA) 00789-1 (8 kW) 00844-1 (8 kW) ONL Y QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD A TTEMPT INST ALLA TION!! ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 2

    Generac ® Pow er Systems, Inc. I NTRODUCTION Thank you for purchasing a model of the Guardian product line by Generac P ower Systems Inc. These models are compact, high performance, air - cooled, engine - driven generators designed to automatically supply electrical power to operate critical loads dur- ing a utility power failure. This unit is fac ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 3

    T able of Contents Guardian Air-cooled Generators Generac® Pow er Systems, Inc. 1 Introduction ......................Inside Front Cover Read This Manual Thoroughly ......................IFC Operation and Maintenance ............................IFC How to Obtain Service ....................................IFC Authorized Dealer Location Number...... ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 4

    2 Generac ® Pow er Systems, Inc. Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Installation, Start -up and Adjustment Manual and with the unit. The generator can operate safely , efficiently and reliably only if it is properly installed, operated and maintained. Many accident ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 5

    Generac ® Pow er Systems, Inc. 3 ELE CTR ICAL HA Z AR DS • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera- tion. A void contact with bare wires, t ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 6

    1.1 I NTRODUCTION T O I NST ALL A TION NOTE: Read the entire manual before starting the installa- tion. Ensure that the model number of the unit being installed matches a model on the front cover . Generac cannot possibly know of and advise the home standby trade of all conceivable procedures and meth- ods by which installation of this equipment mi ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 7

    1.3 B EFOR E I NS T ALLA TION Before installing this equipment, check the ratings of both the generator and the transfer switch. Read “Emergency Circuit Isolation Method” and “T otal Circuit Isolation Method” in Sections 1.8 and 1.9 (P age 11) carefully . The generator's rated wattage/amperage capacity must be adequate to handle all el ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 8

    6 Generac ® Pow er Systems, Inc. W ith LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed above the liq- uid fuel in the storage tank. The engine has been fitted with a fuel carburetion sys- tem that meets the specifications of the 1997 California Air Resources Board for tamper -proof dual fuel sys- tems. The ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 9

    Generac ® Pow er Systems, Inc. 7 3. Refit the fitting and hose to the LP port and the blanking plug to the natural gas port (Figure 1.3). 4. Reverse the procedure to convert back to natural gas. NOTE: The natural gas adjustment screw is preset during installation and should not need any further adjustment. Figure 1.3 – LP Gas Setup 1.7 L OCA TIO ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 10

    8 Generac ® Pow er Systems, Inc. Figure 1.4 – Generator and Transfer Switch Mounting Dimensions (6 kW, 8 kW and 10 kW Non-SA) Section 1 — Installation Guardian Air-cooled Generators ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 11

    Generac ® Pow er Systems, Inc. 9 Figure 1.4 (Continued) Section 1 — Installation Guardian Air-cooled Generators ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 12

    10 Generac ® Pow er Systems, Inc. Figure 1.5 – Generator Mounting Dimensions (Sound Attenuated) Section 1 — Installation Guardian Air-cooled Generators ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 13

    Generac ® Pow er Systems, Inc. 11 1.8 EM ERGENCY CI RCU IT IS OL A TION METHOD One effective way of preventing the generator from being overloaded is to use the “Emergency Circuit Isolation Method” (Figure 1.6). Essential electrical loads are grouped together and wired into a separate emergency distribution panel. Load circuits fed by the emer ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 14

    12 Generac ® Pow er Systems, Inc. 1.1 0 GEN ER A T OR A C C ON N E CTION S Y S TEM Figure 1.8 represents a single-phase, three -wire gen- erator AC connection system. The stator assembly in this system consists of a pair of stationary windings with two leads brought out of each winding . Each sin- gle winding can supply a 120-volt, 60-Hertz AC out ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 15

    Generac ® Pow er Systems, Inc. 13 Section 1 — Installation Guardian Air-cooled Generators Figure 1.10 – Interconnection Diagram for Single-Phase Power System (Sound Attenuated) Figure 1.9 – Interconnection Diagram for Single-Phase Power System (6 kW, 8 kW and 10 kW Non-SA) ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 16

    14 Generac ® Pow er Systems, Inc. 1.1 2 GEN ER A T ORS AND GT S TR ANSF ER SWIT CH ES Guardian generators (this DOES NOT APPL Y to single - phase sound attenuated units) may be installed with either a prepackaged transfer switch or with a stan- dard GTS -type automatic transfer switch (Figure 1.11). Y ou can do this by connecting generator control ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 17

    Generac ® Pow er Systems, Inc. 15 1.1 4 AD APTING TH R EE-P HA SE TR ANSF ER SWIT CH The generator you are installing may include a prepackaged transfer switch configured for three - phase loads. If you want to adapt this kind of transfer switch for single -phase loads, proceed as follows: 1. Discard the three-phase power monitor (PM) found inside ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 18

    16 Generac ® Pow er Systems, Inc. 1.1 7 TH E B A TTER Y Servicing of the battery is to be performed or super- vised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized person- nel away from batteries. When replacing the battery , use the following type of battery: Group 26/26R 12-volt battery with a rating of 35 ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 19

    Generac ® Pow er Systems, Inc. 17 1.1 7 .1 BA TTERY INST ALLA TION Fill the battery with the proper electrolyte fluid if nec- essary and have the battery fully charged before installing it. Before installing and connecting the battery , complete the following steps: 1. Set the generator's A uto/Off/Manual switch to OFF . 2. T urn off utility ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 20

    18 Generac ® Pow er Systems, Inc. NOTE: Throughout the “Operation ” section, differences in procedures specific to sound attenuated units will be denoted as follows: (SA = information). 2.1 USI NG TH E AUT O/OF F/MAN UAL SWIT CH (FIGURE 2.1/2.2) 2.1.1 “ AUT O” POSITION Selecting this switch position activates fully automat- ic system opera ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 21

    Generac ® Pow er Systems, Inc. 19 2.3 SE QU ENCE OF AUT OMA TIC OP ER A TION The generator’s control panel houses a control logic circuit board. This board constantly monitors utili- ty power source voltage. Should that voltage drop below a preset level, circuit board action will signal the engine to crank and start. After the engine starts, the ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 22

    20 Generac ® Pow er Systems, Inc. 6. T o crank and start the engine, set the Auto/Off/Manual switch to MANU AL. 7. Let the engine stabilize and warm up for a few minutes. 8. Set the generator’s main circuit breaker to its ON (or closed) position. The standby power source now powers the loads. 2.4.2 TR ANSFER BA CK T O UTI LITY POWER S OURCE When ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 23

    2.5.3.1 Approximat e Crank Cycle T imes • 15 seconds ON • 15 seconds OFF • 7 seconds ON • 7 seconds OFF • Repeat for 45 seconds Approximately 90 seconds total 2.5.4 OVERSPEED This feature protects the generator from damage by shutting it down if it happens to run faster than the pre- set limit. This protection also prevents the generator ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 24

    22 Generac ® Pow er Systems, Inc. 3.1 B EFOR E I N ITIAL S T ART -U P Before starting, complete the following: 1. Set the generator's A uto/Off/Manual switch to the OFF position. 2. T urn OFF the utility power supply to the transfer switch using the means provided (such as the utility main line circuit breaker). 3. Check the engine crankcase ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 25

    Generac ® Pow er Systems, Inc. 23 Do not attempt manual transfer switch operation until all power voltage supplies to the transfer switch have been positively turned off. Failur e to turn off all power voltage supplies will result in extr emely hazardous and possibly fatal electrical shock. 4. Manually set the transfer switch to the ST ANDB Y posi ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 26

    24 Generac ® Pow er Systems, Inc. 3.7 ENGI N E G O VER NOR ADJ US TM ENT If both AC frequency and voltage are correspondingly high or low , adjust the engine governor as follows: 3.7 .1 6 KW U N IT S (NON-SA) 1. Loosen the governor clamp bolt (F igure 3.1). 2. Push the spring end of the governor lever clock- wise to the wide open throttle position ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 27

    Generac ® Pow er Systems, Inc. 25 3.7 .3 SOUN D A T TEN UA TED UN ITS 1. Carefully inspect the governor anti-lash spring (Figure 3.3). Be sure it is not broken or disengaged. 2. Loosen the governor clamp nut. Then, push the spring end of the governor lever all the way up (wide open throttle). 3. Hold the governor lever at wide open throttle and in ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 28

    26 Generac ® Pow er Systems, Inc. 3.1 0 SE T TI NG TH E EXERCISE TI M ER 3.1 0.1 6 KW , 8 KW AN D 1 0 KW UN ITS (NON-S A) Y our generator is equipped with an exercise timer . Once it is set, the generator will start and exercise once every seven days, on the day of the week and at the time of day you complete the following sequence. During this ex ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 29

    Generac ® Pow er Systems, Inc. 27 4.1 TROU B LE SHOO TI NG GU I DE P ROB LEM CAUSE C OR R E CTION The engine will not crank. 1. F use blown 1. Replace fuse. 2. Loose, corroded or defective 2. T ighten, clean or replace battery cables as necessary . 3. Defective starter contactor 3. Replace starter contactor . 4. Defective starter motor 4. Replace ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 30

    28 Generac ® Pow er Systems, Inc. Section 4 — T roubleshooting Guardian Air-cooled Generators 4.2 I NS T ALLA TION CH ECKLIS T BA TTER Y INST ALL A TION ❏ Battery is connected properly . ❏ Recommended battery is installed. ❏ Cables are clean and tight. ❏ T erminals are coated with anti- corrosion grease, and terminal covers are positione ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 31

    Generac ® Pow er Systems, Inc. 29 Section 5 — Notes Guardian Air-cooled Generators ...

  • Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - page 32

    Part No. C4219 GENERAC ® POWER SY STEMS, INC. P .O. BOX 8 W AUKESHA, WI 53187 Revision * (12/13/99) Printed in U.S.A. ...

Fabbricante Generac Categoria Portable Generator

I documenti che otteniamo dal fabbricante del dispositivoGenerac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Generac
- manuali per l’uso 04077-1, 04109-1, 04079-1, 00789-1, 00844-1
- schede prodotto Generac
- opuscoli
- o etichette energetiche Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1, manuali di manutenzione, brevi manuali o manuali utente Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1.

Manuale completo del dispositivo Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1.

Il manuale per l’uso completo Generac, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 - che ci dovrebbe aiutare nei primi passi durante l'uso Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1?

Utilizza il modulo sottostante

Se non hai risolto il problema con Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)