    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 1 36" Wood Burning Fireplaces P/N 850,005M REV. F 01/2007 COL-3629 COL-3629H MODELS RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WH Report No. J20054576-231 COLONIAL SERIES This installation manual will enable you to obtain a safe, efficient and dependable installation of your fireplace system ...

  • Linksys COL-3629 - page 2

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 2 TABLE OF CONTENTS Safety Rules .................................... page 2 Tools and Building Supplies ............ page 2 Precautions ..................................... page 3 Introduction ..................................... page 3 Clearances/Height Requirements ..... page 3 Chimney System .. ...

  • Linksys COL-3629 - page 3

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 3 Figure 1 TYPICAL INSTALLATION *Construction Materials: • framing materials • paneling • particle board • flooring • dry wall • etc. • plywood PRECAUTIONS Note: These fireplace systems are not difficult to install. However, in the interest of safety, it is recommended that the installe ...

  • Linksys COL-3629 - page 4

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 4 Figure 2 LOCATION OF FIREPLACE Carefully select the proper location for heat circulation, aesthetics, chimney obstructions and clearance to side wall(s). With proper pre- planning, a slight adjustment of a few inches can save considerable time and expense later during construction and assembly. Cha ...

  • Linksys COL-3629 - page 5

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 5 DO NOT permanently place furniture or other items such as decorative pillows within 60" of the fireplace front face. ASSEMBLY STEPS Note: The following steps represent the normal sequence of installation. Each installation is unique, however, and might require a different sequence. 1. Position ...

  • Linksys COL-3629 - page 6

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 6 Step 3. Refer to fireplace drawings and specifi- cations on pages 6 and 7 for framing dimensions and details. Frame appliance enclosure as illus- trated in Figures 12 through 15 on page 7. IMPORTANT: UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS ( SEE FIGURE 11 ) BE REMOVED OR MODIFIED, NOR ...

  • Linksys COL-3629 - page 7

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 7 Note: The framed depth, 28 ¹ ³ ⁄ ₁ ₆ " (732 mm) from a framed wall, must always be measured from a finished surface. If a wall covering such as drywall is to be attached to the rear wall, then the framed depth must be measured from the drywall sur- face. It is important that this dimen ...

  • Linksys COL-3629 - page 8

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 8 Step 5. Fireplace should be secured to side framing members using the full length nailing tabs at the top and bottom of the fireplace front face. Use 8d nails or equivalent ( Figure 18 ). Figure 18 Note: The nailing tabs and the area directly behind the nailing tabs are exempt from the clearances d ...

  • Linksys COL-3629 - page 9

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 9 Step 4. Note: Chimney sections are constructed with a unique locking tab design, which en- sures an immediate, tight assembly between sections. Plan your chimney requirements care- fully before assembly as chimney is difficult to disassemble after installation. If disassembled, the tabs might becom ...

  • Linksys COL-3629 - page 10

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 10 Locking Band Mastic Roof Ridge 120 ° Step 8. The standard Security Chimneys FTF10 roof flashing assemblies include a storm collar. Slide the storm collar over outer chimney, rest on flashing spacers and align with top surface of flashing. Insert tab in slot, pull tight and bend tab back over slot ...

  • Linksys COL-3629 - page 11

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 11 MULTIPLE TERMINATIONS If more than one termination is located in the same chase or within the same general proxim- ity, we suggest they should be separated in distance at least 24" (610 mm) horizontally from flue center to flue center and stacked or staggered vertically at least 18" (457 ...

  • Linksys COL-3629 - page 12

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 12 Figure 38 Figure 40 OFFSET CALCULATIONS Step 1. Use Offset Chart to determine amount of horizontal offset (A) and height (B) for various chimney section assemblies. Step 2. Use “Height of Chimney Only” column in The Vertical Elevation Chart to determine combinations of chimney used above retur ...

  • Linksys COL-3629 - page 13

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 13 397 ¹⁄₄ 33 1 ¹⁄₄ 20 1 1 403 ¹⁄₄ 33 7 ¹⁄₄ 11 1 1 411 34 3 0 0 12 421 ¹⁄₄ 35 1 ¹⁄₄ 10 1 2 427 ¹⁄₄ 35 7 ¹⁄₄ 01 1 2 431 ¹⁄₂ 35 11 ¹⁄₂ 20 1 2 437 ¹⁄₂ 36 5 ¹⁄₂ 11 1 2 445 ¹⁄₄ 37 1 ¹⁄₄ 00 1 3 455 ¹⁄₂ 37 11 ¹⁄₂ 10 1 3 461 ¹? ...

  • Linksys COL-3629 - page 14

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 14 Return Elbow Figure 41 Note: The return elbow assembly performs the same function as a stabilizer. Consider this when determining the need for a stabilizer. Note: Do not apply excessive pressure to any subsequent chimney section following return elbow assembly when installing. Ensure that each sub ...

  • Linksys COL-3629 - page 15

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 15 Outside combustion air ducting may be run upwards or vertically through framing and ceil- ing joists, with the hood installed through an outside wall and 3' (914 mm) below the termi- nation. Ducting may also be run downward through floor joists and under the home to a ventilated crawlspace no ...

  • Linksys COL-3629 - page 16

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 16 Fireplace Opening T ypical Installation 6 ⁹⁄₁₆ " (167mm) 12" (305mm) Min. Combustible Mantel and T rim Spacer Noncombustible Wall Covering Finished Wall 12" (305mm) Max. 1 ¹⁄₂ " (38mm) Figure 46 Hearth Extensions and Wall Shields A hearth extension must be installe ...

  • Linksys COL-3629 - page 17

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 17 Answer - The minimum required thickness of the Micore 160 is .417”, therefore round up to nearest standard thickness available which is 1/2”. ** If the hearth extension material(s) that is intended to be used is NOT listed on Table 1, the material can still be used if the material(s) is noncom ...

  • Linksys COL-3629 - page 18

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 18 Locking Band 63L60 FLB Figure 50 FINISH TO YOUR TASTE There are a wide variety of “finished looks” for these fireplaces, from formal wall decor with elaborate mantels to rustic wood paneling or warm brick facings. Only noncombustible materials like stone, tile, brick, etc., may overlap the bla ...

  • Linksys COL-3629 - page 19

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 19 63L16 FTF10-12 63L17 FTF10-18 63L18 FTF10-36 62L94 FTF10-18C Chimney Section 62L95 FTF10-36C Storm Collar 63L59 FSC 63L40 F10F6 Flashing 63L41 F10F12 Firestop Spacer (Flat) 63L36 F10FS-2 Chase Termination (Square) 63L52 FTF10-CT2RS INSTALLATION COMPONENTS Firestop Spacer (30 ° ) 63L37 F10FS30-2 R ...

  • Linksys COL-3629 - page 20

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 20 The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information. Printed in U.S.A. © 2001 by LENNOX HEARTH PRODUCTS P/N ...

Fabricant Linksys Catégorie Indoor Fireplace

Les documents que nous recevons du fabricant de l'appareilLinksys COL-3629 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Linksys
- manuels d’utilisations COL-3629
- fiches produit Linksys
- dépliants
- ou étiquettes-énergie Linksys COL-3629
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Linksys COL-3629.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Linksys COL-3629, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Linksys COL-3629. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Linksys COL-3629.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Linksys COL-3629, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Linksys COL-3629 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Linksys COL-3629.

Le manuel d’utilisation complet Linksys, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Linksys COL-3629 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Linksys COL-3629, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lLinksys COL-3629 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Linksys COL-3629 - qui devraient nous aider dans les premières étapes lors de l'utilisation Linksys COL-3629
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Linksys COL-3629
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Linksys COL-3629 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Linksys COL-3629?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Linksys COL-3629, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Linksys COL-3629 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)