    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 1 36" Wood Burning Fireplaces P/N 850,005M REV. F 01/2007 COL-3629 COL-3629H MODELS RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WH Report No. J20054576-231 COLONIAL SERIES This installation manual will enable you to obtain a safe, efficient and dependable installation of your fireplace system ...

  • Linksys COL-3629 - page 2

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 2 TABLE OF CONTENTS Safety Rules .................................... page 2 Tools and Building Supplies ............ page 2 Precautions ..................................... page 3 Introduction ..................................... page 3 Clearances/Height Requirements ..... page 3 Chimney System .. ...

  • Linksys COL-3629 - page 3

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 3 Figure 1 TYPICAL INSTALLATION *Construction Materials: • framing materials • paneling • particle board • flooring • dry wall • etc. • plywood PRECAUTIONS Note: These fireplace systems are not difficult to install. However, in the interest of safety, it is recommended that the installe ...

  • Linksys COL-3629 - page 4

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 4 Figure 2 LOCATION OF FIREPLACE Carefully select the proper location for heat circulation, aesthetics, chimney obstructions and clearance to side wall(s). With proper pre- planning, a slight adjustment of a few inches can save considerable time and expense later during construction and assembly. Cha ...

  • Linksys COL-3629 - page 5

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 5 DO NOT permanently place furniture or other items such as decorative pillows within 60" of the fireplace front face. ASSEMBLY STEPS Note: The following steps represent the normal sequence of installation. Each installation is unique, however, and might require a different sequence. 1. Position ...

  • Linksys COL-3629 - page 6

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 6 Step 3. Refer to fireplace drawings and specifi- cations on pages 6 and 7 for framing dimensions and details. Frame appliance enclosure as illus- trated in Figures 12 through 15 on page 7. IMPORTANT: UNDER NO CIRCUMSTANCES CAN THE FIREPLACE TOP SPACERS ( SEE FIGURE 11 ) BE REMOVED OR MODIFIED, NOR ...

  • Linksys COL-3629 - page 7

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 7 Note: The framed depth, 28 ¹ ³ ⁄ ₁ ₆ " (732 mm) from a framed wall, must always be measured from a finished surface. If a wall covering such as drywall is to be attached to the rear wall, then the framed depth must be measured from the drywall sur- face. It is important that this dimen ...

  • Linksys COL-3629 - page 8

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 8 Step 5. Fireplace should be secured to side framing members using the full length nailing tabs at the top and bottom of the fireplace front face. Use 8d nails or equivalent ( Figure 18 ). Figure 18 Note: The nailing tabs and the area directly behind the nailing tabs are exempt from the clearances d ...

  • Linksys COL-3629 - page 9

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 9 Step 4. Note: Chimney sections are constructed with a unique locking tab design, which en- sures an immediate, tight assembly between sections. Plan your chimney requirements care- fully before assembly as chimney is difficult to disassemble after installation. If disassembled, the tabs might becom ...

  • Linksys COL-3629 - page 10

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 10 Locking Band Mastic Roof Ridge 120 ° Step 8. The standard Security Chimneys FTF10 roof flashing assemblies include a storm collar. Slide the storm collar over outer chimney, rest on flashing spacers and align with top surface of flashing. Insert tab in slot, pull tight and bend tab back over slot ...

  • Linksys COL-3629 - page 11

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 11 MULTIPLE TERMINATIONS If more than one termination is located in the same chase or within the same general proxim- ity, we suggest they should be separated in distance at least 24" (610 mm) horizontally from flue center to flue center and stacked or staggered vertically at least 18" (457 ...

  • Linksys COL-3629 - page 12

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 12 Figure 38 Figure 40 OFFSET CALCULATIONS Step 1. Use Offset Chart to determine amount of horizontal offset (A) and height (B) for various chimney section assemblies. Step 2. Use “Height of Chimney Only” column in The Vertical Elevation Chart to determine combinations of chimney used above retur ...

  • Linksys COL-3629 - page 13

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 13 397 ¹⁄₄ 33 1 ¹⁄₄ 20 1 1 403 ¹⁄₄ 33 7 ¹⁄₄ 11 1 1 411 34 3 0 0 12 421 ¹⁄₄ 35 1 ¹⁄₄ 10 1 2 427 ¹⁄₄ 35 7 ¹⁄₄ 01 1 2 431 ¹⁄₂ 35 11 ¹⁄₂ 20 1 2 437 ¹⁄₂ 36 5 ¹⁄₂ 11 1 2 445 ¹⁄₄ 37 1 ¹⁄₄ 00 1 3 455 ¹⁄₂ 37 11 ¹⁄₂ 10 1 3 461 ¹? ...

  • Linksys COL-3629 - page 14

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 14 Return Elbow Figure 41 Note: The return elbow assembly performs the same function as a stabilizer. Consider this when determining the need for a stabilizer. Note: Do not apply excessive pressure to any subsequent chimney section following return elbow assembly when installing. Ensure that each sub ...

  • Linksys COL-3629 - page 15

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 15 Outside combustion air ducting may be run upwards or vertically through framing and ceil- ing joists, with the hood installed through an outside wall and 3' (914 mm) below the termi- nation. Ducting may also be run downward through floor joists and under the home to a ventilated crawlspace no ...

  • Linksys COL-3629 - page 16

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 16 Fireplace Opening T ypical Installation 6 ⁹⁄₁₆ " (167mm) 12" (305mm) Min. Combustible Mantel and T rim Spacer Noncombustible Wall Covering Finished Wall 12" (305mm) Max. 1 ¹⁄₂ " (38mm) Figure 46 Hearth Extensions and Wall Shields A hearth extension must be installe ...

  • Linksys COL-3629 - page 17

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 17 Answer - The minimum required thickness of the Micore 160 is .417”, therefore round up to nearest standard thickness available which is 1/2”. ** If the hearth extension material(s) that is intended to be used is NOT listed on Table 1, the material can still be used if the material(s) is noncom ...

  • Linksys COL-3629 - page 18

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 18 Locking Band 63L60 FLB Figure 50 FINISH TO YOUR TASTE There are a wide variety of “finished looks” for these fireplaces, from formal wall decor with elaborate mantels to rustic wood paneling or warm brick facings. Only noncombustible materials like stone, tile, brick, etc., may overlap the bla ...

  • Linksys COL-3629 - page 19

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 19 63L16 FTF10-12 63L17 FTF10-18 63L18 FTF10-36 62L94 FTF10-18C Chimney Section 62L95 FTF10-36C Storm Collar 63L59 FSC 63L40 F10F6 Flashing 63L41 F10F12 Firestop Spacer (Flat) 63L36 F10FS-2 Chase Termination (Square) 63L52 FTF10-CT2RS INSTALLATION COMPONENTS Firestop Spacer (30 ° ) 63L37 F10FS30-2 R ...

  • Linksys COL-3629 - page 20

    NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 20 The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information. Printed in U.S.A. © 2001 by LENNOX HEARTH PRODUCTS P/N ...

メーカー Linksys カテゴリー Indoor Fireplace

Linksys COL-3629のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- COL-3629の取扱説明書
- Linksysの製品カード
- パンフレット
- またはLinksys COL-3629の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Linksys COL-3629の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Linksys COL-3629の取り付け説明書、サービスマニュアル、簡易説明書、またはLinksys COL-3629のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Linksys COL-3629の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Linksys COL-3629デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがLinksys COL-3629を使用するのを助ける技術的文書のことです。説明書は通常、全てのLinksys COL-3629ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Linksysの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Linksys COL-3629の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははLinksys COL-3629の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Linksys COL-3629に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Linksys COL-3629デバイスの基本機能を使うにあたってのヒント。 Linksys COL-3629のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Linksys COL-3629に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるLinksys COL-3629のメーカー/サービスへの連絡先に関する情報。

Linksys COL-3629についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもLinksys COL-3629の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがLinksys COL-3629で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)