Manuale per l’uso APC MGE Galaxy 5000 40 kVA

28 pagine Non applicabile
Scarica

Vai alla pagina of 28

Summary
  • APC MGE Galaxy 5000 40 kVA - page 1

    MGE Galaxy 5000 40–130 kV A 480 V Installation ...

  • APC MGE Galaxy 5000 40 kVA - page 2

    ...

  • APC MGE Galaxy 5000 40 kVA - page 3

    T able of Contents IMPORT ANT SAFETY INSTRUCTIONS - SA VE THESE INSTRUCTIONS ............................................................................................................... 1 Symbols Used ................................................................................................................... 1 Specications ............ ...

  • APC MGE Galaxy 5000 40 kVA - page 4

    Install Panels and Labels on 48” Battery Cabinet (Stand Alone Only) ...........21 Install Panels and Labels on 48” Battery Cabinet ...............................................22 ii MGE Galaxy 5000 40–130 kV A 480 V 990–5217 ...

  • APC MGE Galaxy 5000 40 kVA - page 5

    IMPORT ANT SAFETY INSTRUCTIONS - SA VE THESE INSTRUCTIONS Symbols Used W ARNING: Indicates an electrical hazard, which, if not avoided, could r esult in injury or death. Caution: Indicates a hazard, which, if not avoided, could result in injury or death. Note: Indicates important information. See: Indicates that more information is available on the ...

  • APC MGE Galaxy 5000 40 kVA - page 6

    Specications AC Input AC input 40 kV A 50 kV A 60 kV A 80 kV A 100 kV A 130 kV A Nominal input voltage (V) 480 480 480 480 480 480 Input frequency (Hz) 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz Nominal input current (A) 1 48 59 71 94 1 17 151 Max input current (A) 2 59 70 88 1 1 1 150 182 Input current limit (A) 3 57 70 85 1 1 1 148 182 Input phase ro ...

  • APC MGE Galaxy 5000 40 kVA - page 7

    Recommended Fuses 40 kV A 50 kV A 60 kV A 80 kV A 100 kV A 130 kV A Input and output fuse rating (A) 160 160 160 160 315 315 990–5217 MGE Galaxy 5000 40–130 kV A 480 V 3 ...

  • APC MGE Galaxy 5000 40 kVA - page 8

    Connect Input and Ground Cables in Single Systems Single Utility/Mains Systems 1. Remove the protection cover in the bottom of the enclosure. 2. Connect the AC input cables to the AC input terminals and to the UPS grounding plate. 3. Connect the AC output cables to the AC output terminals and to the UPS grounding plate. 4. Connect the battery cable ...

  • APC MGE Galaxy 5000 40 kVA - page 9

    Connect AC Input and Power Cables in Parallel Systems Single Utility/Mains Note: A maximum of two UPS units can be installed for Pn. 1. Remove the protection cover in the bottom of the enclosure. 2. Connect the AC input cables to the AC input terminals and to the UPS grounding plate for both UPS units in both UPS units. 3. Connect the AC output cab ...

  • APC MGE Galaxy 5000 40 kVA - page 10

    Dual Utility/Mains Systems Caution: If the two UPS units are placed side by side, connect as indicated below . In other congurations, always make sure that the cables between the UPS units and the bypass source have the same cross-section and the same length. The same is true for the cables between the UPS units and the load. Note: The drawings ...

  • APC MGE Galaxy 5000 40 kVA - page 11

    Connect Communication Cables Overview of Communication Cables in Single Systems Caution: T o ensure suf cient isolation of control and communication cables, they must be run separately from the power cables. Reinforce the insulation of these control and communication cables if any risk of contact with the power cables exists. A. Relay communicat ...

  • APC MGE Galaxy 5000 40 kVA - page 12

    Overview of Communication Cables in Parallel Systems Caution: T o ensure suf cient isolation of control and communication cables, they must be run separately from the power cables. Reinforce the insulation of these control and communication cables if any risk of contact with the power cables exists. A. Relay communication card (SEL V) B. Optiona ...

  • APC MGE Galaxy 5000 40 kVA - page 13

    Connect Relay Communication Card Caution: Isolate and lock-out all power sources for this card before making connections. Never connect SEL V (safety extra low voltage) and non-SEL V circuits to the dif ferent outputs of the same card. Characteristics of output contacts: • Permissible voltage: 250 V AC, 30 V DC • Permissible current: 2 A • Ca ...

  • APC MGE Galaxy 5000 40 kVA - page 14

    4. Connect conductors to the output terminals. A. General alarm B. Battery fault C. Load on UPS D. Load on automatic bypass E. Load on battery power F . Low battery warning 5. Put the cover back in place and secure it with the screws. 6. T ighten the screws to lock the cables. 7. Indicate the locations of the power sources on the labels. 8. Insert ...

  • APC MGE Galaxy 5000 40 kVA - page 15

    1. Remove the wire jumper from the terminal block. 2. Connect the general shutdown NC contact to terminals 1 and 2 (SEL V). 3. Secure the cable. Connect Parallel Communication Cables in Redundant Parallel Systems Note: The supplied cables (33 ft) limit the distance between two UPS units to approximately 20 ft. 1. Connect a communication cable from ...

  • APC MGE Galaxy 5000 40 kVA - page 16

    Connect Parallel Communication Cables in Capacity Parallel Systems Note: The supplied cables (33 ft) limit the distance between the two UPS units to approximately 20 ft. 1. Use the XMS02 and XMS03 terminals to create a loop between all UPS units as shown on the illustration (all the XMS02 and XMS03 terminals must be used). 12 MGE Galaxy 5000 40–1 ...

  • APC MGE Galaxy 5000 40 kVA - page 17

    2. Daisy-chain the UPS units using the XMS06 and XMS07 terminals. Fit a blue connector on the rst UPS units and a red plug on the last UPS unit (all the XMS06 and XMS07 connectors must be used). 3. Connect terminals 7, 8, 9, and 10 on the auxiliary terminal block TB2 in the system bypass cabinet to UPS terminal blocks XMS04/XMS05 pins 1, 2, 3, a ...

  • APC MGE Galaxy 5000 40 kVA - page 18

    14 MGE Galaxy 5000 40–130 kV A 480 V 990–5217 ...

  • APC MGE Galaxy 5000 40 kVA - page 19

    Install an External Battery Cabinet Install A TIZ PCA and GND Busbar 26” and 32” Battery Cabinet 48” Battery Cabinet 1. If the A TIZ PCA option has been purchased, install the A TIZ PCA in the rst battery cabinet. 2. Install the Ground (GND) busbar . 990–5217 MGE Galaxy 5000 40–130 kV A 480 V 15 ...

  • APC MGE Galaxy 5000 40 kVA - page 20

    The Battery Circuit Breaker Note: Only one circuit breaker is necessary even if several battery cabinets are connected. 1. The battery circuit breaker is pre-installed in the battery cabinet from factory . 2. Secure the base plate to the battery cabinet to support the circuit breaker . 3. Secure the XR1 connector box to the battery cabinet frame. 4 ...

  • APC MGE Galaxy 5000 40 kVA - page 21

    Connect Power and Control Cables Power and Control Cable Connections for 26” and 32” Battery Cabinets 990–5217 MGE Galaxy 5000 40–130 kV A 480 V 17 ...

  • APC MGE Galaxy 5000 40 kVA - page 22

    Power and Control Cable Connections for 48” Battery Cabinets 1. Route the power and control cables as shown. For multiple adjacent cabinets, cables interconnect through the middle of cabinet. 18 MGE Galaxy 5000 40–130 kV A 480 V 990–5217 ...

  • APC MGE Galaxy 5000 40 kVA - page 23

    Mount the Battery Cells Caution: The battery cabinet must only be assembled by trained personnel. Caution: A minimum clearance of 150 mm is required between the top of the battery cells and the next shelf. 1. Place the battery cells on each shelves and interconnect them. 2. Interconnect all the battery shelves and connect the complete battery assem ...

  • APC MGE Galaxy 5000 40 kVA - page 24

    Install Panels and Labels on 26” Battery Cabinet (Stand Alone Only) 1. V erify proper lock operation in door . 20 MGE Galaxy 5000 40–130 kV A 480 V 990–5217 ...

  • APC MGE Galaxy 5000 40 kVA - page 25

    Install Panels, Labels and Pallet on 26” Battery Cabinet 1. Place kickplates on top of unit. 2. Place interconnect brackets kit on top of unit. 3. Use corner board and damage label. Install Panels and Labels on 48” Battery Cabinet (Stand Alone Only) 1. V erify proper lock operation in door . 990–5217 MGE Galaxy 5000 40–130 kV A 480 V 21 ...

  • APC MGE Galaxy 5000 40 kVA - page 26

    Install Panels and Labels on 48” Battery Cabinet 1. Place kickplates on top of unit. 2. Place interconnect bracket kit on top of unit. 3. Use corner board and damage label. 22 MGE Galaxy 5000 40–130 kV A 480 V 990–5217 ...

  • APC MGE Galaxy 5000 40 kVA - page 27

    990–5217 MGE Galaxy 5000 40–130 kV A 480 V 23 ...

  • APC MGE Galaxy 5000 40 kVA - page 28

    Worldwide Customer Support Customer support for this or any other product is available at no char ge: • Contact the Customer Support Center by telephone or e-mail. For local, country-specic centers: go to www .apc.com/support/contact for contact information. © APC by Schneider Electric. APC and the APC logo are owned by Schneider Electric Ind ...

Fabbricante APC Categoria Uninterruptible power supply (

I documenti che otteniamo dal fabbricante del dispositivoAPC MGE Galaxy 5000 40 kVA possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici APC
- manuali per l’uso MGE Galaxy 5000 40 kVA
- schede prodotto APC
- opuscoli
- o etichette energetiche APC MGE Galaxy 5000 40 kVA
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso APC MGE Galaxy 5000 40 kVA.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione APC MGE Galaxy 5000 40 kVA, manuali di manutenzione, brevi manuali o manuali utente APC MGE Galaxy 5000 40 kVA. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto APC MGE Galaxy 5000 40 kVA.

Manuale completo del dispositivo APC MGE Galaxy 5000 40 kVA, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare APC MGE Galaxy 5000 40 kVA dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti APC MGE Galaxy 5000 40 kVA.

Il manuale per l’uso completo APC, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale APC MGE Galaxy 5000 40 kVA - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice APC MGE Galaxy 5000 40 kVA, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per APC MGE Galaxy 5000 40 kVA che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo APC MGE Galaxy 5000 40 kVA - che ci dovrebbe aiutare nei primi passi durante l'uso APC MGE Galaxy 5000 40 kVA
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del APC MGE Galaxy 5000 40 kVA
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio APC MGE Galaxy 5000 40 kVA in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su APC MGE Galaxy 5000 40 kVA?

Utilizza il modulo sottostante

Se non hai risolto il problema con APC MGE Galaxy 5000 40 kVA con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con APC MGE Galaxy 5000 40 kVA è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)