    T able of Contents IMPORT ANT SAFETY INSTRUCTIONS - SA VE THESE INSTRUCTIONS ............................................................................................................... 1 Symbols Used ................................................................................................................... 1 Specications ............ ...

  • APC MGE Galaxy 5000 40 kVA - page 4

    Install Panels and Labels on 48” Battery Cabinet (Stand Alone Only) ...........21 Install Panels and Labels on 48” Battery Cabinet ...............................................22 ii MGE Galaxy 5000 40–130 kV A 480 V 990–5217 ...

  • APC MGE Galaxy 5000 40 kVA - page 5

    IMPORT ANT SAFETY INSTRUCTIONS - SA VE THESE INSTRUCTIONS Symbols Used W ARNING: Indicates an electrical hazard, which, if not avoided, could r esult in injury or death. Caution: Indicates a hazard, which, if not avoided, could result in injury or death. Note: Indicates important information. See: Indicates that more information is available on the ...

  • APC MGE Galaxy 5000 40 kVA - page 6

    Specications AC Input AC input 40 kV A 50 kV A 60 kV A 80 kV A 100 kV A 130 kV A Nominal input voltage (V) 480 480 480 480 480 480 Input frequency (Hz) 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz 60 Hz Nominal input current (A) 1 48 59 71 94 1 17 151 Max input current (A) 2 59 70 88 1 1 1 150 182 Input current limit (A) 3 57 70 85 1 1 1 148 182 Input phase ro ...

  • APC MGE Galaxy 5000 40 kVA - page 7

    Recommended Fuses 40 kV A 50 kV A 60 kV A 80 kV A 100 kV A 130 kV A Input and output fuse rating (A) 160 160 160 160 315 315 990–5217 MGE Galaxy 5000 40–130 kV A 480 V 3 ...

  • APC MGE Galaxy 5000 40 kVA - page 8

    Connect Input and Ground Cables in Single Systems Single Utility/Mains Systems 1. Remove the protection cover in the bottom of the enclosure. 2. Connect the AC input cables to the AC input terminals and to the UPS grounding plate. 3. Connect the AC output cables to the AC output terminals and to the UPS grounding plate. 4. Connect the battery cable ...

  • APC MGE Galaxy 5000 40 kVA - page 9

    Connect AC Input and Power Cables in Parallel Systems Single Utility/Mains Note: A maximum of two UPS units can be installed for Pn. 1. Remove the protection cover in the bottom of the enclosure. 2. Connect the AC input cables to the AC input terminals and to the UPS grounding plate for both UPS units in both UPS units. 3. Connect the AC output cab ...

  • APC MGE Galaxy 5000 40 kVA - page 10

    Dual Utility/Mains Systems Caution: If the two UPS units are placed side by side, connect as indicated below . In other congurations, always make sure that the cables between the UPS units and the bypass source have the same cross-section and the same length. The same is true for the cables between the UPS units and the load. Note: The drawings ...

  • APC MGE Galaxy 5000 40 kVA - page 11

    Connect Communication Cables Overview of Communication Cables in Single Systems Caution: T o ensure suf cient isolation of control and communication cables, they must be run separately from the power cables. Reinforce the insulation of these control and communication cables if any risk of contact with the power cables exists. A. Relay communicat ...

  • APC MGE Galaxy 5000 40 kVA - page 12

    Overview of Communication Cables in Parallel Systems Caution: T o ensure suf cient isolation of control and communication cables, they must be run separately from the power cables. Reinforce the insulation of these control and communication cables if any risk of contact with the power cables exists. A. Relay communication card (SEL V) B. Optiona ...

  • APC MGE Galaxy 5000 40 kVA - page 13

    Connect Relay Communication Card Caution: Isolate and lock-out all power sources for this card before making connections. Never connect SEL V (safety extra low voltage) and non-SEL V circuits to the dif ferent outputs of the same card. Characteristics of output contacts: • Permissible voltage: 250 V AC, 30 V DC • Permissible current: 2 A • Ca ...

  • APC MGE Galaxy 5000 40 kVA - page 14

    4. Connect conductors to the output terminals. A. General alarm B. Battery fault C. Load on UPS D. Load on automatic bypass E. Load on battery power F . Low battery warning 5. Put the cover back in place and secure it with the screws. 6. T ighten the screws to lock the cables. 7. Indicate the locations of the power sources on the labels. 8. Insert ...

  • APC MGE Galaxy 5000 40 kVA - page 15

    1. Remove the wire jumper from the terminal block. 2. Connect the general shutdown NC contact to terminals 1 and 2 (SEL V). 3. Secure the cable. Connect Parallel Communication Cables in Redundant Parallel Systems Note: The supplied cables (33 ft) limit the distance between two UPS units to approximately 20 ft. 1. Connect a communication cable from ...

  • APC MGE Galaxy 5000 40 kVA - page 16

    Connect Parallel Communication Cables in Capacity Parallel Systems Note: The supplied cables (33 ft) limit the distance between the two UPS units to approximately 20 ft. 1. Use the XMS02 and XMS03 terminals to create a loop between all UPS units as shown on the illustration (all the XMS02 and XMS03 terminals must be used). 12 MGE Galaxy 5000 40–1 ...

  • APC MGE Galaxy 5000 40 kVA - page 17

    2. Daisy-chain the UPS units using the XMS06 and XMS07 terminals. Fit a blue connector on the rst UPS units and a red plug on the last UPS unit (all the XMS06 and XMS07 connectors must be used). 3. Connect terminals 7, 8, 9, and 10 on the auxiliary terminal block TB2 in the system bypass cabinet to UPS terminal blocks XMS04/XMS05 pins 1, 2, 3, a ...

  • APC MGE Galaxy 5000 40 kVA - page 18

    14 MGE Galaxy 5000 40–130 kV A 480 V 990–5217 ...

  • APC MGE Galaxy 5000 40 kVA - page 19

    Install an External Battery Cabinet Install A TIZ PCA and GND Busbar 26” and 32” Battery Cabinet 48” Battery Cabinet 1. If the A TIZ PCA option has been purchased, install the A TIZ PCA in the rst battery cabinet. 2. Install the Ground (GND) busbar . 990–5217 MGE Galaxy 5000 40–130 kV A 480 V 15 ...

  • APC MGE Galaxy 5000 40 kVA - page 20

    The Battery Circuit Breaker Note: Only one circuit breaker is necessary even if several battery cabinets are connected. 1. The battery circuit breaker is pre-installed in the battery cabinet from factory . 2. Secure the base plate to the battery cabinet to support the circuit breaker . 3. Secure the XR1 connector box to the battery cabinet frame. 4 ...

  • APC MGE Galaxy 5000 40 kVA - page 21

    Connect Power and Control Cables Power and Control Cable Connections for 26” and 32” Battery Cabinets 990–5217 MGE Galaxy 5000 40–130 kV A 480 V 17 ...

  • APC MGE Galaxy 5000 40 kVA - page 22

    Power and Control Cable Connections for 48” Battery Cabinets 1. Route the power and control cables as shown. For multiple adjacent cabinets, cables interconnect through the middle of cabinet. 18 MGE Galaxy 5000 40–130 kV A 480 V 990–5217 ...

  • APC MGE Galaxy 5000 40 kVA - page 23

    Mount the Battery Cells Caution: The battery cabinet must only be assembled by trained personnel. Caution: A minimum clearance of 150 mm is required between the top of the battery cells and the next shelf. 1. Place the battery cells on each shelves and interconnect them. 2. Interconnect all the battery shelves and connect the complete battery assem ...

  • APC MGE Galaxy 5000 40 kVA - page 24

    Install Panels and Labels on 26” Battery Cabinet (Stand Alone Only) 1. V erify proper lock operation in door . 20 MGE Galaxy 5000 40–130 kV A 480 V 990–5217 ...

  • APC MGE Galaxy 5000 40 kVA - page 25

    Install Panels, Labels and Pallet on 26” Battery Cabinet 1. Place kickplates on top of unit. 2. Place interconnect brackets kit on top of unit. 3. Use corner board and damage label. Install Panels and Labels on 48” Battery Cabinet (Stand Alone Only) 1. V erify proper lock operation in door . 990–5217 MGE Galaxy 5000 40–130 kV A 480 V 21 ...

  • APC MGE Galaxy 5000 40 kVA - page 26

    Install Panels and Labels on 48” Battery Cabinet 1. Place kickplates on top of unit. 2. Place interconnect bracket kit on top of unit. 3. Use corner board and damage label. 22 MGE Galaxy 5000 40–130 kV A 480 V 990–5217 ...

  • APC MGE Galaxy 5000 40 kVA - page 27

    990–5217 MGE Galaxy 5000 40–130 kV A 480 V 23 ...

  • APC MGE Galaxy 5000 40 kVA - page 28

    Worldwide Customer Support Customer support for this or any other product is available at no char ge: • Contact the Customer Support Center by telephone or e-mail. For local, country-specic centers: go to www .apc.com/support/contact for contact information. © APC by Schneider Electric. APC and the APC logo are owned by Schneider Electric Ind ...

Производитель APC Категория Uninterruptible power supply (

Документы, которые мы получаем от производителя устройства APC MGE Galaxy 5000 40 kVA мы можем разделить на несколько групп. Это в частности:
- технические чертежи APC
- инструкции обслуживания MGE Galaxy 5000 40 kVA
- паспорта изделия APC
- информационные брошюры
- энергетические этикетки APC MGE Galaxy 5000 40 kVA
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания APC MGE Galaxy 5000 40 kVA.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа APC MGE Galaxy 5000 40 kVA, инструкции обслуживания, короткие инструкции или инструкции пользователя APC MGE Galaxy 5000 40 kVA. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия APC MGE Galaxy 5000 40 kVA.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства APC MGE Galaxy 5000 40 kVA, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании APC MGE Galaxy 5000 40 kVA пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей APC MGE Galaxy 5000 40 kVA.

Полная инструкция обслуживания APC, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией APC MGE Galaxy 5000 40 kVA - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания APC MGE Galaxy 5000 40 kVA, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся APC MGE Galaxy 5000 40 kVA, которое найдем в данном документе
3. Советы по использованию основных функций устройства APC MGE Galaxy 5000 40 kVA - которые должны облегчить нам первые шаги во время использования APC MGE Galaxy 5000 40 kVA
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем APC MGE Galaxy 5000 40 kVA
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра APC MGE Galaxy 5000 40 kVA в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся APC MGE Galaxy 5000 40 kVA?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с APC MGE Galaxy 5000 40 kVA, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с APC MGE Galaxy 5000 40 kVA со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)