    © Copyright 2003 Manual No.: 2100-416C Supersedes: 2100416B File: V ol II T ab 14 Date: 12-22-03 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. QC SERIES CHILLED W A TER UNIT INST ALLA TION INSTRUCTIONS Model: QC501 MIS-1554 ...

  • Bard QC501 - page 2

    CONTENTS i Getting Other Information and Publications For more information, contact these publishers: ..... 1 QC General Information QC Model Nomenclature ......................................... 2 Shipping Damage .................................................... 5 Unit Removal From Skid .......................................... 5 Handling Uni ...

  • Bard QC501 - page 3

    Manual 2100-416 Page 1 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code ...................... ANSI/NFPA 70 ...

  • Bard QC501 - page 4

    Manual 2100-416 Page 2 QC SERIES WA TER SOURCE GENERAL INFORMA TION QC MODEL NOMENCLATURE QC 50 1 – A 10 X X X X X X TABLE 1 FACTORY BUILT-IN ELECTRIC HEAT TABLE s l e d o MA - 1 0 5 C Q 1 - V 0 4 21 - V 8 0 2 W KH U T BH U T B 0 . 50 8 3 , 6 10 9 2 , 2 1 0 . 0 10 7 6 , 2 30 7 5 , 4 2 0 . 5 10 5 1 , 9 40 6 8 , 6 3 Q R S Maximum size of the time d ...

  • Bard QC501 - page 5

    Manual 2100-416 Page 3 TABLE 2A COOLING PERFORMANCE CHART M P GT W EM F C ) 0 0 0 1 ( y t i c a p a C H U T B) 0 0 0 1 ( y t i c a p a C H U T B l i o C r e t a W p o r D e r u s s e r P 1 e g a t S2 d n a 1 e g a t S l a t o Te l b i s n e St n e t a Ll a t o Te l b i s n e St n e t a LG I S P. d H . t F 6 2 40 0 0 1 1 . 5 15 . 0 16 . 45 . 8 33 . ...

  • Bard QC501 - page 6

    Manual 2100-416 Page 4 FIGURE 1 UNIT DIMENSIONS ...

  • Bard QC501 - page 7

    Manual 2100-416 Page 5 SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. The skid must remain attached to the unit until the unit is ready for installation. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by t ...

  • Bard QC501 - page 8

    Manual 2100-416 Page 6 REMOVAL OF WALL BRACKET FROM SHIPPING LOCATION The wall brackets are attached to the back of the unit. Remove and retain the wall brackets for use when attaching the unit to the wall. In those installations where a wall sleeve is required these two wall brackets are to be discarded. A different style bracket is supplied with ...

  • Bard QC501 - page 9

    Manual 2100-416 Page 7 FIGURE 4 INSTALLATION OF UNIT THRU WALL WITH WALL SLEEVE MIS-1564 ...

  • Bard QC501 - page 10

    Manual 2100-416 Page 8 FIGURE 6 DUCTED APPLICATION MIS-1558 FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM CEILING FLOOR DUCT FLANGE DUCT FIXED CEILING SUSPENDED CEILING FLOOR MIS-1559 20 IN. MINIMUM ...

  • Bard QC501 - page 11

    Manual 2100-416 Page 9 DUCT WORK Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit. All duct work must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work ...

  • Bard QC501 - page 12

    Manual 2100-416 Page 10 CONDENSATE DRAIN The condensate drain hose is routed down from the evaporator drain pan on the right side of the unit into the compressor compartment. There are three locations that the drain can exit the cabinet. For a stand pipe type of drain, the drain hose can exit the rear of the cabinet. There is adequate hose length t ...

  • Bard QC501 - page 13

    Manual 2100-416 Page 11 BAROMETRIC FRESH AIR DAMPER (Optional) Before start to remove make sure the power has been turned off. The hinged return air grille panel must be opened. The fresh air damper assembly can be seen on the back of the unit. Refer to Figure 10. 1. The fresh air damper is attached to the back of the unit with one screw on either ...

  • Bard QC501 - page 14

    Manual 2100-416 Page 12 FIGURE 10 FRESH AIR DAMPER REMOVAL MOUNTING SCREW MIS-1627 ...

  • Bard QC501 - page 15

    Manual 2100-416 Page 13 QTEC ENERGY RECOVERY VENTILATOR OPTION Before starting the removal make sure that the power has been turned off. The hinged return air grille panel must be opened. The energy recovery ventilator (QERV) can be seen after the panel is opened. To gain access to the mist eliminator, the QERV must be removed. Refer to Figure 11 1 ...

  • Bard QC501 - page 16

    Manual 2100-416 Page 14 INST ALLA TION INSTRUCTIONS MOUNTING THE UNIT When installing a QC unit near an interior wall on the left side, a minimum of 8 inches is required; 12 inches is preferred. When installing a QC unit near an interior wall on the right side, a minimum of 12 inches is required as additional space is required to connect the drain. ...

  • Bard QC501 - page 17

    Manual 2100-416 Page 15 FIGURE 13 UNIT MOUNTING WITHOUT VENTILATION WALL SLEEVE (REFER TO MOUNTING INSTRUCTIONS ON PAGE 13) SIDE TRIM (2 PIECES) SIDE TRIM (2 PIECES) WALL MOUNTING BRACKET BOTTOM TRIM EXTENSION BOTTOM TRIM PIECE MIS-1557 ...

  • Bard QC501 - page 18

    Manual 2100-416 Page 16 FIGURE 14 COMPONENT LOCATION SIDE FIELD WIRE ENTRANCE REMOTE THERMOST A T TERMINAL BLOCK INDOOR BLOWER CONTROL BOX/ CIRCUIT BREAKER P ANEL MIS-1736 WIRING – MAIN POWER Refer to the unit rating plate and/or Table 2 for wire sizing information and maximum fuse or “HACR Type” circuit breaker size. Each unit is marked with ...

  • Bard QC501 - page 19

    Manual 2100-416 Page 17 The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR Type” circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection, and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor ...

  • Bard QC501 - page 20

    Manual 2100-416 Page 18 LOW VOLTAGE CONNECTIONS These units use a grounded 24 volt AC low voltage circuit. The “R” terminal is the hot terminal and the “C” terminal is grounded. “G” terminal or pins 6 and 1 of P2 are the fan inputs . Both must be energized for proper fan operation. This is done automatically in the factory installed cli ...

  • Bard QC501 - page 21

    Manual 2100-416 Page 19 FIGURE 16 REMOTE THERMOSTAT WIRING DIAGRAM “X” OPTION MIS-1734 IF93-380 ...

  • Bard QC501 - page 22

    Manual 2100-416 Page 20 4102-028 IF93-380 FIGURE 17 REMOTE THERMOSTAT WIRING DIAGRAM “D” THERMOSTAT OPTION ...

  • Bard QC501 - page 23

    Manual 2100-416 Page 21 j Maximum ESP (inches WC) shown is with 1 ” thick disposable filter (reduced by .2 for 2 ” filter). k Rated CFM for ducted applications – required for maximum performance rating. T o obtain full CFM locate low voltage terminal strip in the circuit breaker box.There is a pink jumper wire with both ends attached to termi ...

  • Bard QC501 - page 24

    Manual 2100-416 Page 22 M O T P M Y S E R U D E C O R P / E S U A C . g n i t r a t s n e h w y l t h g i l s s k c o r r o t o M % M C I r o f p u - t r a t s l a m r o n s i s i h T t r a t s t ' n o w r o t o M % t n e m e v o m o N % r o t o m t a r e w o p k c e h C % r o t o m t a ) C o t R C A V 4 2 ( e g a t l o v w o l k c e h C % r o ...

  • Bard QC501 - page 25

    Manual 2100-416 Page 23 M O T P M Y S E R U D E C O R P / E S U A C y l l a c i t a r r e s n u r t u b s t r a t s r o t o M % t n e t t i m r e t n i r o n w o d d n a p u s e i r a V % " g a s " r o n o i t a i r a v r o f e g a t l o v e n i l k c e h C % ; r o t o m t a ) C , R , W , Y , G ( s n o i t c e n n o c e g a t l o v w o l ...

  • Bard QC501 - page 26

    Manual 2100-416 Page 24 FIGURE 18 INTERNAL 2-WAY VALVE PIPING Water Valves Valve Location "NC" side of valve "NO" side of valve "COM" side of valve Valve Detail MIS-1899 ...

  • Bard QC501 - page 27

    Manual 2100-416 Page 25 FIGURE 19 INTERNAL 3-WAY VALVE PIPING Water Valves Valve Location "NC" side of valve "COM" side of valve "NO" side of valve Valve Detail MIS-1900 ...

Fabbricante Bard Categoria Water Dispenser

I documenti che otteniamo dal fabbricante del dispositivoBard QC501 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bard
- manuali per l’uso QC501
- schede prodotto Bard
- opuscoli
- o etichette energetiche Bard QC501
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bard QC501.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bard QC501, manuali di manutenzione, brevi manuali o manuali utente Bard QC501. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bard QC501.

Manuali per l’uso simili

Manuale completo del dispositivo Bard QC501, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bard QC501 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bard QC501.

Il manuale per l’uso completo Bard, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bard QC501 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bard QC501, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bard QC501 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bard QC501 - che ci dovrebbe aiutare nei primi passi durante l'uso Bard QC501
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bard QC501
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bard QC501 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bard QC501?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bard QC501 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bard QC501 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)