    © Copyright 2003 Manual No.: 2100-416C Supersedes: 2100416B File: V ol II T ab 14 Date: 12-22-03 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. QC SERIES CHILLED W A TER UNIT INST ALLA TION INSTRUCTIONS Model: QC501 MIS-1554 ...

  • Bard QC501 - page 2

    CONTENTS i Getting Other Information and Publications For more information, contact these publishers: ..... 1 QC General Information QC Model Nomenclature ......................................... 2 Shipping Damage .................................................... 5 Unit Removal From Skid .......................................... 5 Handling Uni ...

  • Bard QC501 - page 3

    Manual 2100-416 Page 1 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code ...................... ANSI/NFPA 70 ...

  • Bard QC501 - page 4

    Manual 2100-416 Page 2 QC SERIES WA TER SOURCE GENERAL INFORMA TION QC MODEL NOMENCLATURE QC 50 1 – A 10 X X X X X X TABLE 1 FACTORY BUILT-IN ELECTRIC HEAT TABLE s l e d o MA - 1 0 5 C Q 1 - V 0 4 21 - V 8 0 2 W KH U T BH U T B 0 . 50 8 3 , 6 10 9 2 , 2 1 0 . 0 10 7 6 , 2 30 7 5 , 4 2 0 . 5 10 5 1 , 9 40 6 8 , 6 3 Q R S Maximum size of the time d ...

  • Bard QC501 - page 5

    Manual 2100-416 Page 3 TABLE 2A COOLING PERFORMANCE CHART M P GT W EM F C ) 0 0 0 1 ( y t i c a p a C H U T B) 0 0 0 1 ( y t i c a p a C H U T B l i o C r e t a W p o r D e r u s s e r P 1 e g a t S2 d n a 1 e g a t S l a t o Te l b i s n e St n e t a Ll a t o Te l b i s n e St n e t a LG I S P. d H . t F 6 2 40 0 0 1 1 . 5 15 . 0 16 . 45 . 8 33 . ...

  • Bard QC501 - page 6

    Manual 2100-416 Page 4 FIGURE 1 UNIT DIMENSIONS ...

  • Bard QC501 - page 7

    Manual 2100-416 Page 5 SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. The skid must remain attached to the unit until the unit is ready for installation. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by t ...

  • Bard QC501 - page 8

    Manual 2100-416 Page 6 REMOVAL OF WALL BRACKET FROM SHIPPING LOCATION The wall brackets are attached to the back of the unit. Remove and retain the wall brackets for use when attaching the unit to the wall. In those installations where a wall sleeve is required these two wall brackets are to be discarded. A different style bracket is supplied with ...

  • Bard QC501 - page 9

    Manual 2100-416 Page 7 FIGURE 4 INSTALLATION OF UNIT THRU WALL WITH WALL SLEEVE MIS-1564 ...

  • Bard QC501 - page 10

    Manual 2100-416 Page 8 FIGURE 6 DUCTED APPLICATION MIS-1558 FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM CEILING FLOOR DUCT FLANGE DUCT FIXED CEILING SUSPENDED CEILING FLOOR MIS-1559 20 IN. MINIMUM ...

  • Bard QC501 - page 11

    Manual 2100-416 Page 9 DUCT WORK Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit. All duct work must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work ...

  • Bard QC501 - page 12

    Manual 2100-416 Page 10 CONDENSATE DRAIN The condensate drain hose is routed down from the evaporator drain pan on the right side of the unit into the compressor compartment. There are three locations that the drain can exit the cabinet. For a stand pipe type of drain, the drain hose can exit the rear of the cabinet. There is adequate hose length t ...

  • Bard QC501 - page 13

    Manual 2100-416 Page 11 BAROMETRIC FRESH AIR DAMPER (Optional) Before start to remove make sure the power has been turned off. The hinged return air grille panel must be opened. The fresh air damper assembly can be seen on the back of the unit. Refer to Figure 10. 1. The fresh air damper is attached to the back of the unit with one screw on either ...

  • Bard QC501 - page 14

    Manual 2100-416 Page 12 FIGURE 10 FRESH AIR DAMPER REMOVAL MOUNTING SCREW MIS-1627 ...

  • Bard QC501 - page 15

    Manual 2100-416 Page 13 QTEC ENERGY RECOVERY VENTILATOR OPTION Before starting the removal make sure that the power has been turned off. The hinged return air grille panel must be opened. The energy recovery ventilator (QERV) can be seen after the panel is opened. To gain access to the mist eliminator, the QERV must be removed. Refer to Figure 11 1 ...

  • Bard QC501 - page 16

    Manual 2100-416 Page 14 INST ALLA TION INSTRUCTIONS MOUNTING THE UNIT When installing a QC unit near an interior wall on the left side, a minimum of 8 inches is required; 12 inches is preferred. When installing a QC unit near an interior wall on the right side, a minimum of 12 inches is required as additional space is required to connect the drain. ...

  • Bard QC501 - page 17

    Manual 2100-416 Page 15 FIGURE 13 UNIT MOUNTING WITHOUT VENTILATION WALL SLEEVE (REFER TO MOUNTING INSTRUCTIONS ON PAGE 13) SIDE TRIM (2 PIECES) SIDE TRIM (2 PIECES) WALL MOUNTING BRACKET BOTTOM TRIM EXTENSION BOTTOM TRIM PIECE MIS-1557 ...

  • Bard QC501 - page 18

    Manual 2100-416 Page 16 FIGURE 14 COMPONENT LOCATION SIDE FIELD WIRE ENTRANCE REMOTE THERMOST A T TERMINAL BLOCK INDOOR BLOWER CONTROL BOX/ CIRCUIT BREAKER P ANEL MIS-1736 WIRING – MAIN POWER Refer to the unit rating plate and/or Table 2 for wire sizing information and maximum fuse or “HACR Type” circuit breaker size. Each unit is marked with ...

  • Bard QC501 - page 19

    Manual 2100-416 Page 17 The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR Type” circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection, and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor ...

  • Bard QC501 - page 20

    Manual 2100-416 Page 18 LOW VOLTAGE CONNECTIONS These units use a grounded 24 volt AC low voltage circuit. The “R” terminal is the hot terminal and the “C” terminal is grounded. “G” terminal or pins 6 and 1 of P2 are the fan inputs . Both must be energized for proper fan operation. This is done automatically in the factory installed cli ...

  • Bard QC501 - page 21

    Manual 2100-416 Page 19 FIGURE 16 REMOTE THERMOSTAT WIRING DIAGRAM “X” OPTION MIS-1734 IF93-380 ...

  • Bard QC501 - page 22

    Manual 2100-416 Page 20 4102-028 IF93-380 FIGURE 17 REMOTE THERMOSTAT WIRING DIAGRAM “D” THERMOSTAT OPTION ...

  • Bard QC501 - page 23

    Manual 2100-416 Page 21 j Maximum ESP (inches WC) shown is with 1 ” thick disposable filter (reduced by .2 for 2 ” filter). k Rated CFM for ducted applications – required for maximum performance rating. T o obtain full CFM locate low voltage terminal strip in the circuit breaker box.There is a pink jumper wire with both ends attached to termi ...

  • Bard QC501 - page 24

    Manual 2100-416 Page 22 M O T P M Y S E R U D E C O R P / E S U A C . g n i t r a t s n e h w y l t h g i l s s k c o r r o t o M % M C I r o f p u - t r a t s l a m r o n s i s i h T t r a t s t ' n o w r o t o M % t n e m e v o m o N % r o t o m t a r e w o p k c e h C % r o t o m t a ) C o t R C A V 4 2 ( e g a t l o v w o l k c e h C % r o ...

  • Bard QC501 - page 25

    Manual 2100-416 Page 23 M O T P M Y S E R U D E C O R P / E S U A C y l l a c i t a r r e s n u r t u b s t r a t s r o t o M % t n e t t i m r e t n i r o n w o d d n a p u s e i r a V % " g a s " r o n o i t a i r a v r o f e g a t l o v e n i l k c e h C % ; r o t o m t a ) C , R , W , Y , G ( s n o i t c e n n o c e g a t l o v w o l ...

  • Bard QC501 - page 26

    Manual 2100-416 Page 24 FIGURE 18 INTERNAL 2-WAY VALVE PIPING Water Valves Valve Location "NC" side of valve "NO" side of valve "COM" side of valve Valve Detail MIS-1899 ...

  • Bard QC501 - page 27

    Manual 2100-416 Page 25 FIGURE 19 INTERNAL 3-WAY VALVE PIPING Water Valves Valve Location "NC" side of valve "COM" side of valve "NO" side of valve Valve Detail MIS-1900 ...

メーカー Bard カテゴリー Water Dispenser

Bard QC501のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- QC501の取扱説明書
- Bardの製品カード
- パンフレット
- またはBard QC501の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Bard QC501の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Bard QC501の取り付け説明書、サービスマニュアル、簡易説明書、またはBard QC501のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Bard QC501の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Bard QC501デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがBard QC501を使用するのを助ける技術的文書のことです。説明書は通常、全てのBard QC501ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Bardの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Bard QC501の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははBard QC501の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Bard QC501に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Bard QC501デバイスの基本機能を使うにあたってのヒント。 Bard QC501のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Bard QC501に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問