    1 of 18 3015-4568 Revision 0 9/11/03 Installation Guide Bacharach HGM300 to LonWorks FT-10 Communications Adapter Introduction The Bacharach HGM300 to LonWorks Comm unications Adapter enables an HGM300 Refrigerant Monitor to communicate with a LonWorks FT-10 Free Topology network. Zone PPM readings, flow status, refrigerant selections, and HGM inte ...

  • Bacharach LonWorks FT-10 - page 2

    2 of 18 front side of the door. Position the adap ter board over the s tandoffs mounted on the HGM door. Install the five remaining 6- 32 screws through the board and into the standoffs and tighten. Connect power wiring from the HGM300’s 120V Auxiliary Power term inal block to the adapter board’s POWER terminal block. Use UL approved wire. W ir ...

  • Bacharach LonWorks FT-10 - page 3

    3 of 18 If an RDM800 remote display IS to be used w ith the adapter, refer to Figure 3 for wiring details. Note that when the RDM800 is used, TWO RS-485 cables must be run betw een the HGM300 and RDM800, so plan accordingly. In either case, be sure to set the HGM300’s in ternal “Terminator” s lide switch next to the RS-485 terminal block to t ...

  • Bacharach LonWorks FT-10 - page 4

    4 of 18 ...

  • Bacharach LonWorks FT-10 - page 5

    5 of 18 Setting HGM Communication Address On Adapter See Figure 4 for the location of adapter dipswitch ‘A’. Switches 5-8 on the adapter’s ‘A ’ dipswitch are used to matc h the node address set on the HGM’s address dipswitch (on HGM main boa rd). Values from 0-15 are possible: HGM address A5 A6 A7 A8 ----------------- ------------------ ...

  • Bacharach LonWorks FT-10 - page 6

    6 of 18 ...

  • Bacharach LonWorks FT-10 - page 7

    7 of 18 Configuring the HGM300 with RDM800 or Laptop PC The only HGM parameters that are cha ngeable through LonWorks are the alarm thresholds. Configuring the HGM for refriger ant type and length of tubing for each zone (zero length to disable a zone ) must be done with the RDM800 remote display or a laptop PC. Refer to the appropriate Bacharach i ...

  • Bacharach LonWorks FT-10 - page 8

    8 of 18 HGM Alarm Acknowledge Options Two alarm acknowledge options are s upported—Auto Acknowledge and Network Acknowledge. In the Auto Acknowledge mode, the HGM will clear its alarm outputs the next tim e the alarmed zone is sampled and its PP M has dropped below the alarm thresholds. No intervention from the LonW or ks network is necessary. In ...

  • Bacharach LonWorks FT-10 - page 9

    9 of 18 LonWorks Objects and Network Variables The adapter contains one Node Object, sixteen Zone Objects, one Ge neral Status Object, and one Alarm Control Object. There is one Zone Object fo r each refrigerant sampling zone. Object 0 – The Node Object Network input variable nviRequest allows the user to requ est information from different objec ...

  • Bacharach LonWorks FT-10 - page 10

    10 of 18 Network output variable nvoStatus returns the information requested by nviRequest. The status response will indicate the status of the object that received the request. The status bits supported are list ed above under RQ_REPORT_MASK. One nvoStatus response will be returned for each nviRequest. The configuration variable nciMaxStsSendT can ...

  • Bacharach LonWorks FT-10 - page 11

    11 of 18 Objects 1-16 – Zone Objects There is one Zone Object for each sampling zone in the HGM300 (16 total): Network output variable nvoHgmZonePPM shows the m easured gas concentration for a particular zone. The value will range from 0-65535 PPM. Network output variable nvoHgmZoneStatus is a text string that displays inform ation about the zone ...

  • Bacharach LonWorks FT-10 - page 12

    12 of 18 CRITICAL FAULT Some critical fault pr events normal zone PPM m easurement. (View nvoHgmFaults for details on fault type) HGM BUSY Occurs with RDM800 insta lled when certain scr eens are displayed. COMM FAULT 1 Comm failure between HGM and adapter. COMM FAULT 2 Comm failure between adapter internal processors. HGM WARMING UP HGM must go thr ...

  • Bacharach LonWorks FT-10 - page 13

    13 of 18 Object 17 – General Status Objec t The General Status Object provides info rmation about any HGM300 internal faults present and shows which zone is currently being sampled: Network output variable nvoHgmFaultAlert reports whenever ANY fault is detected within the HGM or adapter. It is of type S NVT_switch. It is useful for binding to a F ...

  • Bacharach LonWorks FT-10 - page 14

    14 of 18 HGM Busy (if RDM800 attached a nd showing certain screens)(bit 4) Comm Fault 1 (communications fail ed between HGM and adapter)(bit 3) Comm Fault 2 (internal communicati ons failed within adapter)(bit 2) Unused (bit 1) Unused (bit 0)(least significant b it) Network output variable nvoZ oneSampling shows which zone is currently being sample ...

  • Bacharach LonWorks FT-10 - page 15

    15 of 18 Object 18 – Alarm Control Object The Alarm Control Object provides information about any alarm s which are present in the HGM. It also provides mechanisms fo r acknowledging alarm s, and for viewing and setting the Leak, Spill, and Evacuate alarm thresholds for each zone: Network input variable nviHgmAlarmAck has a single parameter (unsi ...

  • Bacharach LonWorks FT-10 - page 16

    16 of 18 Network input variable nviSetZoneThresh allows Leak, Spill, and Eva cuate alarm thresholds (in PPM) to be set for each m onitoring zone. nviSetZoneThresh has four parameters to be set by the user: Zone Specifier: a number 1-16 specifies which zone is having its thresholds changed Leak Alarm Threshold: a number 0–65535 PPM Spill Alarm Thr ...

  • Bacharach LonWorks FT-10 - page 17

    17 of 18 Network output variable nvoHgmZoneThresh displays the following in formation for the zone specified by nviGetZoneThresh: 1. Zone (1-16) whose alarm th resholds are being displayed 2. Leak Alarm Threshold in PPM (0-65535) 3. Spill Alarm Threshold in PPM (0-65535) 4. Evacuate Alarm Threshold in PPM (0-65535) To change the Leak, Spill, or Eva ...

  • Bacharach LonWorks FT-10 - page 18

    18 of 18 LED 1 and LED 2 will normally show activ ity about every 15 seconds. Since the refrigerant monitoring process is fairly slow and new data is only available every 15 seconds or so, the adapter po lls the HGM at a slow rate to reduce the com munications burden on the HGM main processor. Agai n, commands com ing in from LonWorks might occasio ...

Fabbricante Bacharach Categoria Network Card

I documenti che otteniamo dal fabbricante del dispositivoBacharach LonWorks FT-10 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bacharach
- manuali per l’uso LonWorks FT-10
- schede prodotto Bacharach
- opuscoli
- o etichette energetiche Bacharach LonWorks FT-10
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bacharach LonWorks FT-10.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bacharach LonWorks FT-10, manuali di manutenzione, brevi manuali o manuali utente Bacharach LonWorks FT-10. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bacharach LonWorks FT-10.

Manuali per l’uso simili

Manuale completo del dispositivo Bacharach LonWorks FT-10, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bacharach LonWorks FT-10 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bacharach LonWorks FT-10.

Il manuale per l’uso completo Bacharach, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bacharach LonWorks FT-10 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bacharach LonWorks FT-10, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bacharach LonWorks FT-10 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bacharach LonWorks FT-10 - che ci dovrebbe aiutare nei primi passi durante l'uso Bacharach LonWorks FT-10
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bacharach LonWorks FT-10
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bacharach LonWorks FT-10 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bacharach LonWorks FT-10?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bacharach LonWorks FT-10 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bacharach LonWorks FT-10 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)