Summary
  • Bacharach LonWorks FT-10 - page 1

    1 of 18 3015-4568 Revision 0 9/11/03 Installation Guide Bacharach HGM300 to LonWorks FT-10 Communications Adapter Introduction The Bacharach HGM300 to LonWorks Comm unications Adapter enables an HGM300 Refrigerant Monitor to communicate with a LonWorks FT-10 Free Topology network. Zone PPM readings, flow status, refrigerant selections, and HGM inte ...

  • Bacharach LonWorks FT-10 - page 2

    2 of 18 front side of the door. Position the adap ter board over the s tandoffs mounted on the HGM door. Install the five remaining 6- 32 screws through the board and into the standoffs and tighten. Connect power wiring from the HGM300’s 120V Auxiliary Power term inal block to the adapter board’s POWER terminal block. Use UL approved wire. W ir ...

  • Bacharach LonWorks FT-10 - page 3

    3 of 18 If an RDM800 remote display IS to be used w ith the adapter, refer to Figure 3 for wiring details. Note that when the RDM800 is used, TWO RS-485 cables must be run betw een the HGM300 and RDM800, so plan accordingly. In either case, be sure to set the HGM300’s in ternal “Terminator” s lide switch next to the RS-485 terminal block to t ...

  • Bacharach LonWorks FT-10 - page 4

    4 of 18 ...

  • Bacharach LonWorks FT-10 - page 5

    5 of 18 Setting HGM Communication Address On Adapter See Figure 4 for the location of adapter dipswitch ‘A’. Switches 5-8 on the adapter’s ‘A ’ dipswitch are used to matc h the node address set on the HGM’s address dipswitch (on HGM main boa rd). Values from 0-15 are possible: HGM address A5 A6 A7 A8 ----------------- ------------------ ...

  • Bacharach LonWorks FT-10 - page 6

    6 of 18 ...

  • Bacharach LonWorks FT-10 - page 7

    7 of 18 Configuring the HGM300 with RDM800 or Laptop PC The only HGM parameters that are cha ngeable through LonWorks are the alarm thresholds. Configuring the HGM for refriger ant type and length of tubing for each zone (zero length to disable a zone ) must be done with the RDM800 remote display or a laptop PC. Refer to the appropriate Bacharach i ...

  • Bacharach LonWorks FT-10 - page 8

    8 of 18 HGM Alarm Acknowledge Options Two alarm acknowledge options are s upported—Auto Acknowledge and Network Acknowledge. In the Auto Acknowledge mode, the HGM will clear its alarm outputs the next tim e the alarmed zone is sampled and its PP M has dropped below the alarm thresholds. No intervention from the LonW or ks network is necessary. In ...

  • Bacharach LonWorks FT-10 - page 9

    9 of 18 LonWorks Objects and Network Variables The adapter contains one Node Object, sixteen Zone Objects, one Ge neral Status Object, and one Alarm Control Object. There is one Zone Object fo r each refrigerant sampling zone. Object 0 – The Node Object Network input variable nviRequest allows the user to requ est information from different objec ...

  • Bacharach LonWorks FT-10 - page 10

    10 of 18 Network output variable nvoStatus returns the information requested by nviRequest. The status response will indicate the status of the object that received the request. The status bits supported are list ed above under RQ_REPORT_MASK. One nvoStatus response will be returned for each nviRequest. The configuration variable nciMaxStsSendT can ...

  • Bacharach LonWorks FT-10 - page 11

    11 of 18 Objects 1-16 – Zone Objects There is one Zone Object for each sampling zone in the HGM300 (16 total): Network output variable nvoHgmZonePPM shows the m easured gas concentration for a particular zone. The value will range from 0-65535 PPM. Network output variable nvoHgmZoneStatus is a text string that displays inform ation about the zone ...

  • Bacharach LonWorks FT-10 - page 12

    12 of 18 CRITICAL FAULT Some critical fault pr events normal zone PPM m easurement. (View nvoHgmFaults for details on fault type) HGM BUSY Occurs with RDM800 insta lled when certain scr eens are displayed. COMM FAULT 1 Comm failure between HGM and adapter. COMM FAULT 2 Comm failure between adapter internal processors. HGM WARMING UP HGM must go thr ...

  • Bacharach LonWorks FT-10 - page 13

    13 of 18 Object 17 – General Status Objec t The General Status Object provides info rmation about any HGM300 internal faults present and shows which zone is currently being sampled: Network output variable nvoHgmFaultAlert reports whenever ANY fault is detected within the HGM or adapter. It is of type S NVT_switch. It is useful for binding to a F ...

  • Bacharach LonWorks FT-10 - page 14

    14 of 18 HGM Busy (if RDM800 attached a nd showing certain screens)(bit 4) Comm Fault 1 (communications fail ed between HGM and adapter)(bit 3) Comm Fault 2 (internal communicati ons failed within adapter)(bit 2) Unused (bit 1) Unused (bit 0)(least significant b it) Network output variable nvoZ oneSampling shows which zone is currently being sample ...

  • Bacharach LonWorks FT-10 - page 15

    15 of 18 Object 18 – Alarm Control Object The Alarm Control Object provides information about any alarm s which are present in the HGM. It also provides mechanisms fo r acknowledging alarm s, and for viewing and setting the Leak, Spill, and Evacuate alarm thresholds for each zone: Network input variable nviHgmAlarmAck has a single parameter (unsi ...

  • Bacharach LonWorks FT-10 - page 16

    16 of 18 Network input variable nviSetZoneThresh allows Leak, Spill, and Eva cuate alarm thresholds (in PPM) to be set for each m onitoring zone. nviSetZoneThresh has four parameters to be set by the user: Zone Specifier: a number 1-16 specifies which zone is having its thresholds changed Leak Alarm Threshold: a number 0–65535 PPM Spill Alarm Thr ...

  • Bacharach LonWorks FT-10 - page 17

    17 of 18 Network output variable nvoHgmZoneThresh displays the following in formation for the zone specified by nviGetZoneThresh: 1. Zone (1-16) whose alarm th resholds are being displayed 2. Leak Alarm Threshold in PPM (0-65535) 3. Spill Alarm Threshold in PPM (0-65535) 4. Evacuate Alarm Threshold in PPM (0-65535) To change the Leak, Spill, or Eva ...

  • Bacharach LonWorks FT-10 - page 18

    18 of 18 LED 1 and LED 2 will normally show activ ity about every 15 seconds. Since the refrigerant monitoring process is fairly slow and new data is only available every 15 seconds or so, the adapter po lls the HGM at a slow rate to reduce the com munications burden on the HGM main processor. Agai n, commands com ing in from LonWorks might occasio ...

Manufacturer Bacharach Category Network Card

Documents that we receive from a manufacturer of a Bacharach LonWorks FT-10 can be divided into several groups. They are, among others:
- Bacharach technical drawings
- LonWorks FT-10 manuals
- Bacharach product data sheets
- information booklets
- or energy labels Bacharach LonWorks FT-10
All of them are important, but the most important information from the point of view of use of the device are in the user manual Bacharach LonWorks FT-10.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Bacharach LonWorks FT-10, service manual, brief instructions and user manuals Bacharach LonWorks FT-10. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Bacharach LonWorks FT-10.

A complete manual for the device Bacharach LonWorks FT-10, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Bacharach LonWorks FT-10 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Bacharach LonWorks FT-10.

A complete Bacharach manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Bacharach LonWorks FT-10 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Bacharach LonWorks FT-10, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Bacharach LonWorks FT-10, that we can find in the current document
3. Tips how to use the basic functions of the device Bacharach LonWorks FT-10 - which should help us in our first steps of using Bacharach LonWorks FT-10
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Bacharach LonWorks FT-10
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Bacharach LonWorks FT-10 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Bacharach LonWorks FT-10?

Use the form below

If you did not solve your problem by using a manual Bacharach LonWorks FT-10, ask a question using the form below. If a user had a similar problem with Bacharach LonWorks FT-10 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)