Manuale per l’uso APC SmartSlot Series

17 pagine 1.39 mb
Scarica

Vai alla pagina of 17

Summary
  • APC SmartSlot Series - page 1

    Thank Y ou! Thank y ou for selectin g the American Power Conversion SmartSlot Series Measure-UPS II . It has been desi g ned for man y y ears of reliable, mainte- nance-free service. Please read this manual! It provides installation and operatin g instructions that will help y ou g et the most from y our accessor y . Save this manual! It includes i ...

  • APC SmartSlot Series - page 2

    Contents 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 Operation Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 4 Sensor Zone Connections . . . . . . . . . . ...

  • APC SmartSlot Series - page 3

    1. Introduction The SmartSlot Measure-UPS II performs temperature and humidit y sensin g , as well as contact monitorin g . Measure-UPS II supports up to four zones of contact monitorin g , each of which supports both normall y open and normall y closed contacts. Measure-UPS II reports temperatures from 0 to 60 °C (32 to 140 °F) and relative humi ...

  • APC SmartSlot Series - page 4

    Safety Notice The SmartSlot Measure-UPS II UPS accessor y is intended solel y for use in supplementar y surveillance of equipment. APC does not recom- mend this product for life or propert y protection. APC will not know- in g l y sell Measure-UPS II for use in such applications. APC disclaims all liabilit y arisin g out of improper use of Measure- ...

  • APC SmartSlot Series - page 5

    2. Installation Use the followin g procedure to install SmartSlot Measure-UPS II : 1. Install and configure an y software or hardware that will be used with Measure-UPS II for data reporting (see software and hard- ware compatibility abov e). 2. Using figure 2 as a guide, install Measure-UPS II in the host SmartSlot. Use a #2 Phillips head screwdri ...

  • APC SmartSlot Series - page 6

    Do not: • Cov er any of the ventilation holes on the probe • Immerse the probe or place it where de w can be expected to form • Use the probe in an en vironment with chlorine gas or insecti- cides. 5. The contact monitoring connection is a two piece design. Connect contact closure-type sensors to the remov able scre w terminal block using the ...

  • APC SmartSlot Series - page 7

    3. Operation Check 1. Confirm the basic operation of Measure-UPS II . Use the data reporting system (see hardware and software compatibility in sec- tion 1) to confirm that Measure-UPS II is w orking. W ith the probe (temperature or temperature and humidity) connected to probe connector 1, Measure-UPS II should transmit temperature or tem- perature ...

  • APC SmartSlot Series - page 8

    4. Sensor Zone Connections Connection Information Measure-UPS II supports normall y open and normall y closed loop s y stems, and allows mixin g of normall y open and normall y closed sensors on an y zone. See the fi g ures below for more information on usin g multiple sensors in one zone and for s y stem hookup. Note: Do not cross connect sensors ...

  • APC SmartSlot Series - page 9

    In order to avoid receivin g alarm indications on unused zones, install a j umper wire between the COM and NC connectors for each unused zone. T o use more than one sensor on a zone, follow the dia g ram below . Connect normall y open sensors in parallel and normall y open sensors in series. ...

  • APC SmartSlot Series - page 10

    See below for a t y pical hookup. Note that in this example s y stem zone 1 is a normall y closed motion zone with power for the passive infrared detector supplied b y Measure-UPS II . Zone 2 is a normall y open zone. Zone 3 is a combination normall y open and normall y closed zone. Zone 4 is not used. ...

  • APC SmartSlot Series - page 11

    5. Sensor Selection Measure-UPS II ma y be used with an y dr y contact closure t y pe sen- sors. The Measure-UPS II sensor inputs are desi g ned to monitor cir- cuits that have no volta g e potential of their own. Connection of Measure-UPS II sensor inputs to an y circuit other than a dr y closure t y pe will void the warrant y and ma y r e su l t ...

  • APC SmartSlot Series - page 12

    6. Maintenance Measure-UPS II requires periodic maintenance. Confirm contact sens- in g usin g the sensor manufacturers recommended intervals and meth- ods. Use the data reportin g s y stem to verif y that each sensor operates as planned. Clean the temperature (or temperature and humidit y ) probe whenever there is a visible buildup of dust. Gentl ...

  • APC SmartSlot Series - page 13

    7. T roubleshooting Problem Possible Cause Solution Constant Alarm on one or more unused zones. Unused zones not jumpered. Connect a wire between the COM and NC terminals of all unused zones (see section 4). Constant low tem- perature and humid- ity readings. 12 Vdc supply (pin 1) shorted to ground or overloaded. Correct short circuit — examine a ...

  • APC SmartSlot Series - page 14

    8. Service If the SmartSlot Measure-UPS II requires service: 1. Check Measure-UPS II using the troubleshooting chart in section 7 before calling for service. 2. Note the model number of the Measure-UPS II , the serial number , and the date purchased. See the back cov er of this manual for the correct telephone number and call customer service. A te ...

  • APC SmartSlot Series - page 15

    9. Specifications Electrical SmartSlot specification compatible Operatin g volta g e: 16 - 27 Vdc Operatin g current draw: 30 mAdc (exclusive of an y attached sensors) T emperature accurac y : ±2° C (± 3.6° F), from 0 to 40° C (32 to 104° F) Humidit y accurac y : ±8% RH, 10 to 90% RH, at 25° C (77° F); ±8% RH, 30 to 80% RH, from 15 to 30? ...

  • APC SmartSlot Series - page 16

    10. Declaration of Conformity Application of Council Directives: 89/336/EEC Standards to Which Conformit y is Declared: EN55022, EN50082-1 Manufacturers Name: American Power Conversion 132 Fair g rounds Road We s t K i n g ston, RI 02892 USA Importer ’ s Name and Address: T y pe of Equipment: Measure-UPS II Model Number: AP9612T , AP9612TH Serial ...

  • APC SmartSlot Series - page 17

    Limited W arranty American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obli- gation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. T o obtain service under warranty you must o ...

Fabbricante APC Categoria Power Supply

I documenti che otteniamo dal fabbricante del dispositivoAPC SmartSlot Series possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici APC
- manuali per l’uso SmartSlot Series
- schede prodotto APC
- opuscoli
- o etichette energetiche APC SmartSlot Series
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso APC SmartSlot Series.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione APC SmartSlot Series, manuali di manutenzione, brevi manuali o manuali utente APC SmartSlot Series. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto APC SmartSlot Series.

Manuali per l’uso simili

Manuale completo del dispositivo APC SmartSlot Series, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare APC SmartSlot Series dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti APC SmartSlot Series.

Il manuale per l’uso completo APC, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale APC SmartSlot Series - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice APC SmartSlot Series, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per APC SmartSlot Series che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo APC SmartSlot Series - che ci dovrebbe aiutare nei primi passi durante l'uso APC SmartSlot Series
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del APC SmartSlot Series
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio APC SmartSlot Series in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su APC SmartSlot Series?

Utilizza il modulo sottostante

Se non hai risolto il problema con APC SmartSlot Series con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con APC SmartSlot Series è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)