    Form No. PDS 698B.24.1 TWO-SPEED PURON® PLUS™ ELECTRIC HEAT PUMP 698B (60 HZ) Sizes 024, 036, 048, and 060 • T W O - S P E E D • ™ Model 698B Heat Pumps incor porate innov ativ e 2-speed com- pressor technology with Puron ® , the refrigerant of the future, to provide quiet, ef fi cient cooling perf ormance. Built into these units are f e ...

  • Bryant 698B - page 2

    — 2 — DIMENSIONS A01063 DIMENSIONS (IN.) SOUND PO WER (dBA) *Sound lev els are equivalent at high and low speeds. UNIT SIZE SERIES A B C D E F G H K L M N MINIMUM MOUNTING P AD DIMENSIONS 024 A 33-13/16 22-1/2 26-3/16 4-1/8 7-1/8 21-15/16 28-3/8 5/8 12 13-3/4 12 2-3/8 20 x 27 036 A 27-13/16 30 33 5-1/16 9-11/16 15-15/16 22-3/8 3/4 16-1/4 14 13- ...

  • Bryant 698B - page 3

    — 3 — RECOMMENDED TUBE DIAMETERS NO TE: Maximum long-line tube length of 50 ft liquid and v apor line sets indicated abov e must be f ollowed on all applications . Over 50 ft or 20 ft vertical differential, refer to Application Guideline and Service Manual — Air Conditioners and Heat Pumps Using Puron ® Refrigerant. UNIT SIZE TUBE LENGTH (Ft ...

  • Bryant 698B - page 4

    — 4 — SPECIFICA TIONS * P ermissible limits of the voltage r ange at which the unit will operate satisf actorily . Oper ation outside these limits ma y result in unit failure . † If wire is applied at ambient greater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70). The ampacity of nonmetallic-sheathed cab le (NM), tra ...

  • Bryant 698B - page 5

    — 5 — OPTIONAL EQUIPMENT DESCRIPTION AND USA GE (Listed Alphabetically) 1. Coastal Filter A mesh screen inser ted under the top cov er and inside the base pan to protect the condenser coil from salt damage without restricting air fl ow . SUGGESTED USE:In geographic areas where salt damage could occur . 2. Snow Stand Coated wire rac k which sup ...

  • Bryant 698B - page 6

    — 6 — COMBINA TION RA TINGS UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Lo w High Low High Lo w High Low High Low High Low 024-A FV4ANF002* 735 440 24,000 12,000 14.0 11.0 21,000 10,600 3.38 3.40 12,400 4400 2.34 1.52 7.8 CC5A/CD5AA024 750 450 22,000 11,800 11.5 9.5 20,400 1 ...

  • Bryant 698B - page 7

    — 7 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 036-A FK4CNF001 1100 660 33,600 17,200 14.0 10.7 32,600 15,400 3.12 3.50 18,500 7300 2.32 1.78 8.1 FK4CNF002 1100 660 34,000 17,400 14.5 10.8 33,400 15,600 3.26 3.56 18,800 730 ...

  • Bryant 698B - page 8

    — 8 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 036-A CK5A/CK5BA048 1100 700 34,800 17,600 15.0 11.6 32,400 15,800 3.32 3.66 18,400 7300 2.46 1.82 8.7 CK5A/CK5BT042 1100 700 34,400 17,600 15.0 11.5 32,000 15,600 3.26 3.62 18 ...

  • Bryant 698B - page 9

    — 9 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 036-A CC5A/CD5AB042 1200 800 34,600 17,600 14.5 11.2 32,800 15,800 3.20 3.58 18,700 7500 2.38 1.80 8.3 CC5A/CD5A C048 1200 800 34,200 17,400 14.5 11.1 32,000 15,600 3.08 3.52 1 ...

  • Bryant 698B - page 10

    — 10 — UNIT SIZE SERIES INDOOR UNIT Cooling ‡ Heating HPSF High-T emp Low-T emp CFM** TC* SEER EER TC* Cop TC* Cop High Low High Low High Low High Low High Low High Low 048-A CK5A/CK5BN060 1470 910 45,500 24,000 14.5 11.0 42,500 24,000 3.06 3.62 27,800 14,000 2.58 2.22 9.0 CK5A/CK5BT048 1470 910 44,000 24,000 14.0 10.6 42,000 24,000 3.02 3.52 ...

  • Bryant 698B - page 11

    — 11 — * Ratings are net values re fl ecting the eff ects of circulating fan heat. Supplemental electric heat is not included. Ratings are based on: Cooling Standard: 80 ° F (27 ° C) db 67 ° F (19 ° C) wb indoor entering air temperature and 95 ° F (35 ° C) db air entering outdoor unit. High-T emp Heating Standard: 70 ° F (21 ° C) db in ...

  • Bryant 698B - page 12

    — 12 — 698BNX BALANCE POINT WORKSHEET BUILDING H EAT LO SS, 1000 BTU / HR UN I T I NTEGRATED HEATING C APACITY, 1000 BTU/HR P rinte d in U .S.A . OUTDOOR TEMPERATURE, ° F -10 0 10 20 30 40 50 60 70 80 2.9 5.9 8.8 11.7 14.7 17.6 20.5 70 60 50 40 30 20 10 KW BASED ON INDOOR ENT. AIR AT 70 ∞ F AND AT RATED CFM 23. 4 80 A - 698BNX024 / FV4ANF002 ...

  • Bryant 698B - page 13

    — 13 — DET AILED COOLING CAP A CITIES* See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacit ...

  • Bryant 698B - page 14

    — 14 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 15

    — 15 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 16

    — 16 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 17

    — 17 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 18

    — 18 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 19

    — 19 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 20

    — 20 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 21

    — 21 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 22

    — 22 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 23

    — 23 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 24

    — 24 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 25

    — 25 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 26

    — 26 — DET AILED COOLING CAP A CITIES* continued See notes on page 27. EV APORA TOR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 75 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW** Capacity MBtuh † T otal System KW ...

  • Bryant 698B - page 27

    — 27 — DET AILED COOLING CAP A CITIES* continued * Detailed cooling capacities are based on indoor and outdoor unit at the same ele vation per ARI standard 210/240-94. If additional tubing length is used and/or indoor unit is located abov e outdoor unit, a slight v ariation in capacity may occur . † T otal and sensible capacities are net capa ...

  • Bryant 698B - page 28

    — 28 — HEA T PUMP HEA TING PERFORMANCE See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh ...

  • Bryant 698B - page 29

    — 29 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K ...

  • Bryant 698B - page 30

    — 30 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac ...

  • Bryant 698B - page 31

    — 31 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac ...

  • Bryant 698B - page 32

    — 32 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac ...

  • Bryant 698B - page 33

    — 33 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K ...

  • Bryant 698B - page 34

    — 34 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K ...

  • Bryant 698B - page 35

    — 35 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K ...

  • Bryant 698B - page 36

    — 36 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac ...

  • Bryant 698B - page 37

    — 37 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac ...

  • Bryant 698B - page 38

    — 38 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K ...

  • Bryant 698B - page 39

    — 39 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr T otal Int* K ...

  • Bryant 698B - page 40

    — 40 — HEA T PUMP HEA TING PERFORMANCE continued See notes on page 41. INDOOR AIR OUTDOOR COIL ENTERING AIR TEMPERA TURES ° F – 3 7 17 27 37 47 57 67 EDB CFM Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capacity MBtuh † T otal Pwr Capac ...

  • Bryant 698B - page 41

    — 41 — HEA T PUMP HEA TING PERFORMANCE continued * The Btuh heating capacity values sho wn are net “ integrated ” values from which the defrost eff ect has been subtracted. The Btuh heating from supplement heaters should be added to those v alues to obtain total system capacity . † The kW values include the compressor , outdoor f an motor ...

  • Bryant 698B - page 42

    — 42 — ...

  • Bryant 698B - page 43

    — 43 — ...

  • Bryant 698B - page 44

    — 44 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: New © 2001 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls., IN 46231 PRINTED IN U.S.A. Catalog No. 5269-803 4-01 ...

Fabbricante Bryant Categoria Heat Pump

I documenti che otteniamo dal fabbricante del dispositivoBryant 698B possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Bryant
- manuali per l’uso 698B
- schede prodotto Bryant
- opuscoli
- o etichette energetiche Bryant 698B
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Bryant 698B.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Bryant 698B, manuali di manutenzione, brevi manuali o manuali utente Bryant 698B. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Bryant 698B.

Manuali per l’uso simili

Manuale completo del dispositivo Bryant 698B, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Bryant 698B dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Bryant 698B.

Il manuale per l’uso completo Bryant, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Bryant 698B - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Bryant 698B, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Bryant 698B che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Bryant 698B - che ci dovrebbe aiutare nei primi passi durante l'uso Bryant 698B
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Bryant 698B
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Bryant 698B in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Bryant 698B?

Utilizza il modulo sottostante

Se non hai risolto il problema con Bryant 698B con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Bryant 698B è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)