    5/17/2007 1 100 Serie s Media Conve rter & Industri al Ethernet Switche s User Manual & Install ation Guide ...

  • N-Tron 100 Series - page 2

    5/17/2007 2 Industrial Medi a Converter Installation Guide 102MC-XX 102MCE-XX-YY 104TX 105TX 108TX Where: XX = ST or SC a nd YY = -15, -40, or -80 ...

  • N-Tron 100 Series - page 3

    5/17/2007 3 Copyright, © N-TRON Corp., 2 007 820 S. Universit y Blvd., Suite 4E Mobile, AL USA 36609 All rights reserved. Repr oduction, adaptation, or translation without prior written permission from N-TRON Corp. is prohibited, ex cept as allowed under cop yright laws. Ethernet is a registered trademark of Xerox Corporation. All other product na ...

  • N-Tron 100 Series - page 4

    5/17/2007 4 GENERAL SAFETY WARNIN GS WARNING: Do not operate the equipment i n the presen ce o f flamm able gasses or fumes. Operating electrical equipment in such an environment constit utes a definite safety hazard. WARNING: If the equi pment is used in the manner not specified b y N-TRON Corp., t he protection provided by the equipment ma y be i ...

  • N-Tron 100 Series - page 5

    5/17/2007 5 HAZARDOUS LOCAT ION INSTAL LATION REQUIREMENTS 1. This equipment is suitable for use in Class I, Di v 2, Groups A, B, C, and D, or uncl assified or non- hazardous locations. 2. WARNING: Explos ion Hazard - Substitut ion of components may impair suitabilit y for Class I, Division 2. 3. WARNING: Explosion hazard, do not disconnect while t ...

  • N-Tron 100 Series - page 6

    5/17/2007 6 100 Series Indus trial Ethernet Switches The 100 Series Unmana ged Industrial Ethernet Swit ches support high speed la yer 2 switching between ports. This series of swit ches are housed in a ru ggedized aluminum enclosure, and provid e Categor y-5 compliant 10/100-BaseT connections for high perform ance network design, and hub/repe ater ...

  • N-Tron 100 Series - page 7

    5/17/2007 7 PACKAGE CONTENT S Please make sure the Serial ov er Ethernet package contains the foll owing items: 1. 100 Series Media Converter or Ethern et Switch 2. Instruction Sheet Contact your carrier if an y items are damaged. UNPACKING Remove all the equipment from the packaging, and s tore the packaging in a safe place. File an y damage claim ...

  • N-Tron 100 Series - page 8

    5/17/2007 8 DIN-Rail Mounting Install the unit in a standard D IN rail. Recess the uni t to allow at least 2” of horizont al clearance for CAT5e cable bend radius. To inst all the unit to 35mm ind ustrial D I N rail, place the top ed ge of the includ ed mounting bracket on the back of the unit against the D IN rail at a 15° angle as sho wn. Rota ...

  • N-Tron 100 Series - page 9

    5/17/2007 9 FRONT PANEL 102MC/MCE From Top to Bottom: SPD Speed LED LNK/ACT Link/Activity LED RJ45 Ports Auto sensing 10/100 BaseT Connection Green LED lights when Power is connected NOTE: The RJ 45 data port has two LED’s located at the left side of t he connector. The top LED indi cates Activity (ACT), and the l ower LED indicates Link (LNK) st ...

  • N-Tron 100 Series - page 10

    5/17/2007 10 APPLYING POWER (To p View) Unscrew & Remove the DC Voltage Input Plug fr om the top header. Install the DC Power Ca bles into the Plug (observing polarit y on unit). Plug the Voltage Input Pl ug back into the top header. Tightening torque for the termin al block power plug is 0.22 N m/0.162 Pound Foot . All LED’s will flash ON Mo ...

  • N-Tron 100 Series - page 11

    5/17/2007 11 N-TRON SWITCH GR OUNDING TECHNIQ UES FOR 100 SERIE S The grounding phil osophy of an y control s ystem is an integral part of the design. N-Tron s witches are designed to be grounded, but the user has been given the flexibilit y to float the switch when required. The best noise immunit y and emissi ons (i.e. CE) are obtained when the N ...

  • N-Tron 100 Series - page 12

    5/17/2007 12 CONNECTING THE UNIT For th e 100 BaseFX Fiber Optic port, remove th e dust cap(s) fr om the fiber optic connector and connect the fiber optic cables. The T X port on the l ocal unit should be connected to the RX port of the far end device, and the RX port should be co nnected to the TX port of the far end device. For 10Base-T ports, pl ...

  • N-Tron 100 Series - page 13

    5/17/2007 13 FCC STATEMENT This product complies with P art 15 of the FCC-A Rules. Operation is subject to the following condi tions: (1) This device ma y not cause harmful Interference (2) This device m ust accept an y interference r eceived, including inter ference that may cause undesired operation. NOTE: This equipment has been tested and found ...

  • N-Tron 100 Series - page 14

    5/17/2007 14 Regulatory Approvals: Safety: UL Listed per ANS I/ISA-12.12.01-2000 (US and C anada) This apparatus is suitable for use in Class I, Div 2, Groups A, B, C, an d D UL Temperature Ratings: 102MC/MC E - T5 104TX, 105TX, and 108TX - T4A EMI: EN61000-6-4, EN55011 - Class A FCC Title 47, Part 15, S ubpart B - Class A ICES-003 – Class A EMS: ...

  • N-Tron 100 Series - page 15

    5/17/2007 15 102MC/MCE - KEY SPECI FICATIONS Physical Height: 2.90” (max.) Width: 1.50” (max. ) Depth Including Din-Rail Clip: 4.82” (max.) Weight: 0.60 lbs. Electrical Input Voltage: 10-30 VDC (Regulated ) Input Current: 1 40mA max. @ 24VDC (Steady State) Inrush Current: 8.5Amp/0.7 ms max . @ 24VDC Input Ripple: Less than 100 mV Input Wire S ...

  • N-Tron 100 Series - page 16

    5/17/2007 16 104TX/105TX - KEY SPECI FICATIONS Physical Height: 2.9” (max.) Width: 1.50” (max. ) Depth: 4.25” (max.) Weight: 0.60 lbs. Electrical Input Voltage: 10-30 VDC (Regulated ) Input Current: 215 mA max. @ 2 4VDC (Steady State) Inrush Current: 7.8 Amp/0.7ms m ax. @ 24VDC Input Ripple: Less than 100 mV Input Wire Size: 16-28 AW G Enviro ...

  • N-Tron 100 Series - page 17

    5/17/2007 17 108TX - KEY SPECI FICATIONS Physical Height: 3.5” (8.89 cm) Width: 1.50” (3.81 cm) Depth Including DIN Rail Cli p: 4.22” (10.7 cm) Weight: 0.64 lbs. (0.29 kg) DIN Rail 35 mm Electrical Input Voltage: 10-30 VDC (Regulated) Input Current: 250 mA max. @ 2 4VDC (Steady State) Inrush Current: 8.1 Amp/0.7ms max . @ 24VDC Input Ripple: ...

  • N-Tron 100 Series - page 18

    5/17/2007 18 N-TRON Limited Warrant y N-TRON, Co rp. warrants to the end u ser t hat this hardware pro duct will b e free from defects in workmanship and materials, und er nor mal use and service, for the ap plicable warranty perio d from th e date of purchase from N- TRON o r it s autho rized r eseller. If a produ ct does not o perate as warranted ...

Fabbricante N-Tron Categoria Switch

I documenti che otteniamo dal fabbricante del dispositivoN-Tron 100 Series possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici N-Tron
- manuali per l’uso 100 Series
- schede prodotto N-Tron
- opuscoli
- o etichette energetiche N-Tron 100 Series
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso N-Tron 100 Series.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione N-Tron 100 Series, manuali di manutenzione, brevi manuali o manuali utente N-Tron 100 Series. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto N-Tron 100 Series.

Manuali per l’uso simili

Manuale completo del dispositivo N-Tron 100 Series, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare N-Tron 100 Series dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti N-Tron 100 Series.

Il manuale per l’uso completo N-Tron, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale N-Tron 100 Series - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice N-Tron 100 Series, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per N-Tron 100 Series che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo N-Tron 100 Series - che ci dovrebbe aiutare nei primi passi durante l'uso N-Tron 100 Series
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del N-Tron 100 Series
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio N-Tron 100 Series in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su N-Tron 100 Series?

Utilizza il modulo sottostante

Se non hai risolto il problema con N-Tron 100 Series con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con N-Tron 100 Series è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)