    D N A G N I T A R E P O , N O I T A L L A T S N I R O F S N O I T C U R T S N I E C I V R E S ™ M O D E E R F Y C N E I C I F F E H G I H G N I S N E D N O C T N E V T C E R I D R E L I O B R E T A W T O H D E R I F - S A G W ARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury , or loss ...

  • Burnham 101008-01R1-2/07 - page 2

    2 T able of Contents I. Product Description ............................................................................ 2 II. Speci fi cations ..................................................................................... 2 III. Before Installing .................................................................................. 3 IV . Loca ...

  • Burnham 101008-01R1-2/07 - page 3

    3 I Pr oduct Description The FCM070, FCM090 and FCM120 are aluminum gas fi red condensing boilers designed for use in forced hot water heating systems requiring supply water temperatures of 180°F or less. These boilers are designed for installation on a wall, however they may be fl oor mounted using an optional pedestal kit available from U.S. B ...

  • Burnham 101008-01R1-2/07 - page 4

    4 III Befor e Installing 1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance with this manual and the authority having jurisdiction. • In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the National Fuel Gas Code, AN ...

  • Burnham 101008-01R1-2/07 - page 5

    5 6) The combustion air piping must terminate where outdoor air is available for combustion and away from areas that will contaminate combustion air . A void areas near chemical products containing chlorine, chloride based salts, chloro/ fl uorocarbons, paint removers, cleaning solvents and detergents. Figure 4.1: Clearances T o Combustible Or Non ...

  • Burnham 101008-01R1-2/07 - page 6

    6 T ABLE 4.2: CLEARANCES FROM VENT PIPING T O COMBUSTIBLE CONSTRUCTION TYPE OF VENT PIPE PIPE DIRECTION ENCLOSURE MINIMUM CLEARANCE TO COMBUSTIBLE MA TERIAL 60/100mm CONCENTRIC VENTING VERTICAL OR HORIZONT AL ENCLOSED ON ALL FOUR SIDES 0” HEA T F AB SAF-T VENT PROTECH F ASNSEAL Z-FLEX Z-VENT III FLEX-L ST AR-34 VERTICAL OR HORIZONT AL A T LEAST O ...

  • Burnham 101008-01R1-2/07 - page 7

    7 V Mounting The Boiler CAUTIO N T his boiler wei g hs approximatel y 1 10 pounds : • T wo people are required to safel y lift this boiler onto the wall mountin g hook . • Make sure that wall mountin g hook is anchored to a structure capable of supportin g the wei g ht of the boiler and attached pipin g when fi lled with water . Jurisdictions ...

  • Burnham 101008-01R1-2/07 - page 8

    8 Fi g ure 5.1 W all Mountin g Hole Locations ...

  • Burnham 101008-01R1-2/07 - page 9

    9 Fi g ure 5.2 Boiler Mountin g/ Hardwar e ...

  • Burnham 101008-01R1-2/07 - page 10

    10 VI Air for V entilation W ARNING OUTDOOR COMBUSTION AIR MUST BE PIPED TO THE AIR INT AKE. NEVER PIPE COMBUSTION AIR FROM AREAS CONT AINING CONT AMINA TES SUCH AS SWIMMING POOLS AND LAUNDR Y ROOM EXHAUST VENTS. CONT AMINA TED COMBUSTION AIR WILL DAMAGE THE BOILER AND MA Y CAUSE PROPERTY DAMAGE, PERSONAL INJUR Y OR LOSS OF LIFE. Air for combustion ...

  • Burnham 101008-01R1-2/07 - page 11

    11 Figure 6.1: Boiler Installed In A Con fi ned Space, V entilation Air From Inside ...

  • Burnham 101008-01R1-2/07 - page 12

    12 A. V ent System Design There are three basic ways to vent this boiler: • Horizontal (“Side W all”) Concentric V enting - V ent system exits the building through an outside wall. Concentric venting consists of a “pipe within a pipe”. Flue gas exits the building through the inner pipe and combustion air is drawn into the boiler through t ...

  • Burnham 101008-01R1-2/07 - page 13

    13 shown in T able 7.1 are in addition to the fi rst elbow on top of the boiler . For vertical vent systems, the maximum vertical vent lengths shown in T able 7.8 are in addition to two elbows. If more elbows are desired, the maximum allowable vent length must be reduced by the amount shown in T able 7.7 for each additional elbow used. T erminatio ...

  • Burnham 101008-01R1-2/07 - page 14

    14 T ABLE 7.1: SUMMAR Y OF HORIZONT AL VENTING OPTIONS VENT OPTION # 1 2 3 4 CLASSIFICA TION USED IN THIS MANUAL HORIZONT AL CONCENTRIC HORIZONT AL TWIN PIPE (RESER VED FOR FUTURE USE) (RESER VED FOR FUTURE USE) ILLUSTRA TED IN FIGURE 7.2 7.3 VENT PIPE STRUCTURE PENETRA TION W ALL W ALL AIR INT AKE PIPE STRUCTURE PENETRA TION W ALL W ALL VENT PIPE ...

  • Burnham 101008-01R1-2/07 - page 15

    15 Figure 7.2: Horizontal Concentric V enting (V ent Option 1) Figure 7.3: Horizontal T win Pipe V enting (V ent Option 2) ...

  • Burnham 101008-01R1-2/07 - page 16

    16 T ABLE 7.4: U.S. BOILER CONCENTRIC VENT COMPONENTS (VENT OPTION 1) P AR T NO. DESCRIPTION SIZE USED ON VENT OPTION # COMMENTS 101005-01 80/125 x 60/100mm REDUCING ELBOW 80/125 x 60/100mm 1 INCLUDED WITH ST ANDARD BOILER 101006-01 TERMINAL SECTION 60/100mm 1 INCLUDED WITH ST ANDARD BOILER 101007-01 W ALL GROMMET 60/100mm 1 INCLUDED WITH ST ANDARD ...

  • Burnham 101008-01R1-2/07 - page 17

    17 Figure 7.6a: Location of V ent T erminal Relative to Windows, Doors, Grade Figure 7.6b: Location of V ent T erminal Relative to Meters and Forced Air Inlets Figure 7.6c: Positioning V ent T erminal Under Overhangs ...

  • Burnham 101008-01R1-2/07 - page 18

    18 T ABLE 7.7: VENT/ AIR INT AKE FITTING EQUIV ALENT LENGTH VENT FITTING EQUIV ALENT LENGTH (ft) 60/100mm 90 CONCENTRIC ELBOW 4.5 60/100mm 45 CONCENTRIC ELBOW 4.0 3” 90 ELBOW 5.5 3” 45 ELBOW 4.0 6) Permitted T erminals for V ertical V enting (V ent Option 5) - A straight termination is installed in the end of the vent pipe. V ent manufacturer p ...

  • Burnham 101008-01R1-2/07 - page 19

    19 T ABLE 7.8: SUMMARY OF VERTICAL VENTING OPTIONS VENT OPTION # 5 6 CLASSIFICA TION USED IN THIS MANUAL VER TICAL TWIN PIPE (RESER VED FOR FUTURE USE) ILLUSTRA TED IN FIGURE 7.9 VENT PIPE STRUCTURE ROOF AIR INT AKE PIPE STRUCTURE ROOF VENT PIPE SIZE 3” AIR INT AKE PIPE SIZE 3” MAXIMUM LENGTH VENT FCM070 49.5ft FCM090 49.5ft FCM120 49.5ft INLET ...

  • Burnham 101008-01R1-2/07 - page 20

    20 B. Removing an Existing Boiler Fr om a Common Chimney Read this only if the FCM boiler is replacing an existing boiler that is being removed from a common chimney . This section does not apply to the installation of a FCM boiler . In some cases, when an existing boiler is removed from a common chimney , the common venting system may be too large ...

  • Burnham 101008-01R1-2/07 - page 21

    21 C. Assembly of U.S. Boiler 60/100mm Concentric V enting 1) Concentric vent components supplied with the boiler are packed inside the boiler carton and include the following: a) 80/125 x 60/100mm reducing elbow (P/N 101005-01). b) 60/100mm terminal section (straight section with a terminal and overall length of 27 3/4” (P/N 101006-01). c) (2) R ...

  • Burnham 101008-01R1-2/07 - page 22

    22 Figure 7.10: Installation of Reducing Elbow on Concentric Boiler Collar Figure 7.1 1: Dimension “L” ...

  • Burnham 101008-01R1-2/07 - page 23

    23 6) Use locking bands provided to join adjacent sections of non-cuttable pipe as well as fi ttings. The male end of the terminal section and other cuttable sections must be held to the female end of the adjoining pipe with at least three #10 x 1/2” sheet metal screws. Drill a 1/8" hole through both outer pipes to start this screw . Use a ...

  • Burnham 101008-01R1-2/07 - page 24

    24 Figure 7.14: Preparing T erminal Section for Installation in the W all Figure 7.15: Attaching T erminal Section ...

  • Burnham 101008-01R1-2/07 - page 25

    25 D. Assembly of Stainless Steel V enting CAUTION V ent systems made by Heat Fab, Protech, and Z-Flex rely on gaskets for proper sealing. When these vent systems are used, take the following precautions: • Make sure that gasket is in position and undamaged in the female end of the pipe. • Make sure that both the male and female pipes are free ...

  • Burnham 101008-01R1-2/07 - page 26

    26 3) Assembly of Flex-L-Intl. Star-34 V ent System: a) Star-34 General Notes: • Do not cut Star-34 vent components. • Support horizontal piping sections at intervals of 48” or less. • V ertical venting systems must be supported by at least one Star-34 Fire stop. An additional vertical support is required after any offset. • Orient Star-3 ...

  • Burnham 101008-01R1-2/07 - page 27

    27 4) Assembly of Z-Flex Z-V ent III: a) General Notes: • Non-expanded ends of SVE Series III piping sections may be cut using aviation snips or a 24 thread per inch hacksaw . File or sand the cut end smooth before assembling. Expanded ends may be cut to adapt the SVE series III to the vent collar . See the following instructions. • Support hor ...

  • Burnham 101008-01R1-2/07 - page 28

    28 5) Assembly of Heat Fab Saf-T V ent EZ Seal: a) Saf-T V ent General Notes: • These instructions cover the installation of Saf-T V ent EZ Seal. Saf-T V ent EZ Seal piping has integral gaskets installed in the female ends of the pipe which seal the joints. • In general, Saf-T V ent pipe sections may not be cut. Exceptions to this are the Saf-T ...

  • Burnham 101008-01R1-2/07 - page 29

    29 6) Assembly of Protech FasNSeal a) FasNSeal General Notes: • Do not cut 4” FasNSeal pipe. Consult FasNSeal instructions for method of cutting other 3” pipe. • Orient FasNSeal vent components so that the arrows on the piping labels are in the direction of fl ue gas fl ow . • Support horizontal piping sections at intervals of 6 feet or ...

  • Burnham 101008-01R1-2/07 - page 30

    30 8) Installation of V ertical Exhaust T erminal - Use the terminal supplied by the vent system manufacturer shown in T able 7.5. Attach to the vent system, following the assembly instructions in this manual for the stainless vent system being used. 9) Assembly of the Air Intake System and Air Intake T erminals: a) Assemble the air intake system u ...

  • Burnham 101008-01R1-2/07 - page 31

    31 Figure 7.21: Condensate Piping Arrangement ...

  • Burnham 101008-01R1-2/07 - page 32

    32 VIII Gas Piping Gas piping to the boiler must be sized to deliver adequate gas for the boiler to fi re at the nameplate input at an inlet pressure between the minimum and maximum values shown on the rating plate. For more information on gas line sizing, consult the utility or the National Fuel Gas Code. Figure 8.1 shows typical gas piping conne ...

  • Burnham 101008-01R1-2/07 - page 33

    33 IX System Piping A. General System Piping Precautions W ARNING INST ALL BOILER SO THA T THE GAS IGNITION SYSTEM COMPONENTS ARE PROTECTED FROM W A TER (DRIPPING, SPRA YING, RAIN, ETC) DURING APPLIANCE OPERA TION AND SERVICE (CIRCULA TOR REPLACEMENT , ETC). CAUTION THE HEA T EXCHANGER USED IN THE FCM IS MADE FROM A SPECIAL ALUMINUM ALLOY . F AILUR ...

  • Burnham 101008-01R1-2/07 - page 34

    34 Method 1: Primary/Secondary Piping This method can be used in heat-only applications as shown in Figure 9.2 or with an indirect water heater as shown in Figure 9.3. This method relies on primary/secondary pumping to ensure that the required fl ow is always maintained through the boiler . In this system, the fl ow rate through the boiler is com ...

  • Burnham 101008-01R1-2/07 - page 35

    35 Figure 9.2: Piping Method #1 - Heat Only Example (contd.) T otal fi ttings in Indirect W ater Heater Loop: 5 90 Elbows 2 T urns in T ees 1 Swing Check 2 Isolation V alves Calculate total equivalent length fr om T able 9.7: 20 Straight Pipe + 5 Elbows x 2.75 + 2 T urns in T ees x 5.5 + 1 Swing Check x 7 + 2 valves x 0.6 = 52.95 Equivalent Feet S ...

  • Burnham 101008-01R1-2/07 - page 36

    36 Figure 9.3: Piping Method #1 - Heat + Indirect W ater Heater Figure 9.4a: Piping Method #1 - Secondary Loop Piping (Shaded) ...

  • Burnham 101008-01R1-2/07 - page 37

    37 Figure 9.4c: Modular Boiler Piping Figure 9.4b: Piping Method #1 - Indirect W ater Heater Loop Piping (Shaded) ...

  • Burnham 101008-01R1-2/07 - page 38

    38 T ABLE 9.6: PIPE AND CIRCULA TOR SIZING FOR INDIRECT W A TER HEA TER LOOP BOILER MODEL (a) (b) (c) (d) (e) (f) PIPE SIZE FLOW MAX. I.W .H. PRESSURE DROP ALLIANCE™ INDIRECT W A TER HEA TERS CIRCULA TOR MODEL I.W .H. LOOP MAX EQUIV ALENT LENGTH (in NPT) (GPM) (ft HEAD) (ft) FCM070 1 6.0 1.7 AL27SL (*) AL35SL (*) AL70SL (*) AL1 19SL (*) T aco 008 ...

  • Burnham 101008-01R1-2/07 - page 39

    39 Method 2: Direct Connection to Heating System (Generally NOT Recommended) The FCM can be connected directly to the heating system as is done with conventional boilers (Figure 9.8). If this is done, the fl ow rate through the boiler will equal the fl ow rate through the system. The fl ow rate through the system must therefore always remain wit ...

  • Burnham 101008-01R1-2/07 - page 40

    40 C: Standard Piping Installation Requirements Observe the following guidelines when making the actual installation of the boiler piping: 1) The relief valve is packaged loose with the boiler and must be installed in the location shown in Figure 2.1. The relief valve is set to open at 30 psi. If the valve is replaced, the replacement must have a r ...

  • Burnham 101008-01R1-2/07 - page 41

    41 2) Circulator (Required) - Usually at least two circulators will be required to properly install a FCM Series boiler . See the previous section for information on sizing the circulators. 3) Expansion T ank (Required) - If this boiler is replacing an existing boiler with no other changes in the system, the old expansion tank can generally be reus ...

  • Burnham 101008-01R1-2/07 - page 42

    42 Figure 9.1 1: Chiller Piping Figure 9.10: Isolation of the Boiler From Oxygenated W ater with A Plate Heat Exchanger ...

  • Burnham 101008-01R1-2/07 - page 43

    43 1) Line V oltage (120 V AC) Connections (Fig 10.1) – The line voltage connections are located in the junction box on the right side of the vestibule: • Black – Line voltage “hot” • White – “Neutral” for boiler and circulators • Red – “Heating” circulator “hot” • Blue – “Indirect W ater Heater “ circulator ? ...

  • Burnham 101008-01R1-2/07 - page 44

    44 Figure 10.1: Wiring Connections Diagram ...

  • Burnham 101008-01R1-2/07 - page 45

    45 Figure 10.2: Ladder Diagram ...

  • Burnham 101008-01R1-2/07 - page 46

    46 Figure 10.3: Wiring of Isolation Relay for Control of T wo Heating Circulators ...

  • Burnham 101008-01R1-2/07 - page 47

    47 XI Start-up and Checkout Use the following procedure for initial start-up of the boiler: 1) If not already done, fl ush the system to remove sediment, fl ux, and traces of boiler additives. This should be done with the boiler isolated from the system. 2) Fill the boiler and hydronic system with water meeting the following requirements below (a ...

  • Burnham 101008-01R1-2/07 - page 48

    48 W A TER QUALITY AND BOILER W A TER ADDITIVE S I MP O RT A N T N O T E This boiler is equipped with an aluminum heat exchan g er that can be seriousl y dama g ed b y failure to follow t he following guidelines : 1 ) Flush the system before connecting the boiler yg - In a replacement installation, fl ushing the system will remove r s ediment, sol ...

  • Burnham 101008-01R1-2/07 - page 49

    49 FCM Series Lighting and Operating Instructions ...

  • Burnham 101008-01R1-2/07 - page 50

    50 10) Check the inlet pressure and adjust if necessary . V erify that the inlet pressure is between the upper and lower limits shown on the rating plate with all gas appliances on and off. W ARNING THE OUTLET PRESSURE FOR THE GAS V AL VE HAS BEEN F ACTOR Y SET AND REQUIRES NO FIELD ADJUSTMENT . THIS SETTING IS SA TISF ACTOR Y FOR BOTH NA TURAL GAS ...

  • Burnham 101008-01R1-2/07 - page 51

    51 1 1) Perform a combustion test. Boilers equipped with a concentric vent system have a fl ue gas sample tap located in the boiler vent collar (under the screw cap). For other vent systems, the sample probe may be inserted into the terminal. If this is not possible, remove the fl ue temperature sensor and insert the analyzer probe in the sensor ...

  • Burnham 101008-01R1-2/07 - page 52

    52 W ARNING Each FCM series boiler is tested at the factory and adjustments to the air- fuel mixture are normally not necessary . Consult a U.S. Boiler representative before attempting to make any such adjustments. Improper gas valve or mixture adjustments could result in property damage, personal injury , or loss of life. 12) T est any external li ...

  • Burnham 101008-01R1-2/07 - page 53

    53 XII Operation 1) The FCM boiler uses a microprocessor based control, known as a “MCBA”, to manage all boiler functions including fl ame supervision and modulation. T wo set point or “target” boiler supply temperatures are stored in the MCBA ’ s memory; one for space heating and one for domestic water production. If an outdoor temperat ...

  • Burnham 101008-01R1-2/07 - page 54

    54 CAUTION PUSHING AND HOLDING THE “+” WHILE IN ST ANDBY MODE WILL PREVENT THE BOILER FROM RESPONDING TO A CALL FOR HEA T . PUSHING AND HOLDING THE “-” WHILE IN ST ANDBY MODE WILL PREVENT THE BOILER FROM RESPONDING TO A CALL FOR DOMESTIC W A TER. IF THIS HAPPENS, “cOFF” or “dOFF” WILL APPEAR ON THE DISPLA Y . TO TURN BACK ON THE HEA ...

  • Burnham 101008-01R1-2/07 - page 55

    55 FIGURE 12.2 BASIC MENU TREE ...

  • Burnham 101008-01R1-2/07 - page 56

    56 3) T wo basic types of errors codes are shown on the display: • Soft Lockout Codes – When a soft lockout occurs, the boiler will shut down and the display will alternate between the number “9” and the letter “b” followed by a two digit service code. A list of these codes, and their meanings, is shown in T able 14.3. The boiler will a ...

  • Burnham 101008-01R1-2/07 - page 57

    57 d) After the prepurge, the control module ener gizes the gas control valve and the spark for 4.5 seconds. If a fl ame is established and proved, the control allows the fl ame to stabilize for 5 seconds at the combustion fan ignition speed setting. If the fl ame fails to prove, the control module will attempt to light the burner 4 more times. ...

  • Burnham 101008-01R1-2/07 - page 58

    58 XIII. Service and Maintenance IMPORT ANT W ARRANTY DOES NOT COVER BOILER DAMAGE OR MALFUNCTION IF THE FOLLOWING STEPS ARE NOT PERFORMED A T THE INTERV ALS SPECIFIED 1) Continuously: a. Keep the area around the boiler free from combustible materials, gasoline and other fl ammable vapors and liquids. b. Keep the area around the combustion air inl ...

  • Burnham 101008-01R1-2/07 - page 59

    59 d. Remove the ignition electrode and inspect it for oxides. Clean the oxides off the electrode with sandpaper . Inspect the ceramic insulator for cracks and replace the ignitor assembly if necessary . e. Remove the fan/gas valve assembly from the burner hood. Inspect for lint and dust. If signi fi cant lint and dust are found, disassemble the f ...

  • Burnham 101008-01R1-2/07 - page 60

    60 XIV . T roubleshooting A. T roubleshooting problems where no error code is displayed: T ABLE 14.1: NO ERROR CODE DISPLA YED CONDITION POSSIBLE CAUSES Display Blank, Fan off, L WCO lights off • No 120V AC Power at boiler . Check breaker and wiring between breaker panel and boiler Display Panel Blank, Fan running • Loose 120V AC connection wir ...

  • Burnham 101008-01R1-2/07 - page 61

    61 T ABLE 14.3: SOFT LOCKOUT CODES DISPLA YED CODE CONDITION POSSIBLE CAUSES b 08 Pressure switch circuit open • Blockage in intake or vent system. • V ent and/or intake system not constructed in accordance with Part VI. • Blocked or leaking pressure switch tubing • Heat exchanger or burner blockage • T erminals exposed to high winds • ...

  • Burnham 101008-01R1-2/07 - page 62

    62 T ABLE 14.4: HARD LOCKOUT CODES DISPLA YED CODE CONDITION POSSIBLE CAUSES E 00 A fl ame signal was present when there should be no fl ame. • Defective gas valve - make sure inlet pressure is below maximum on rating plate before replacing valve. E 02 Flame failure after 5 tries to restart • No gas pressure • Gas pressure under minimum val ...

  • Burnham 101008-01R1-2/07 - page 63

    63 XV Parts All FCM Series Repair Parts may be obtained through your local Burnham Wholesale distributor . Should you require assistance in locating a Burnham distributor in your area, or have questions regarding the availability of Burnham products or repair parts, please contact Burnham Customer Service at (717) 481-8400 or Fax (717) 481-8408. ...

  • Burnham 101008-01R1-2/07 - page 64

    64 ...

  • Burnham 101008-01R1-2/07 - page 65

    65 KEY DESCRIPTION (Quantity) Part Number (Quantity) Part Number (Quantity) Part Number FCM070 FCM090 FCM120 * T aco 007 (1) 8056170 ----- ----- * T aco 0014 ----- (1) 100362-01 (1)100362-01 * Gas Cock (1) 100487-01 (1) 100487-01 (1) 100487-01 * M4 x 30mm Machine Screw (for gas valve harness) (1) 100364-01 (1) 100364-01 (1) 100364-01 * Outdoor Sens ...

  • Burnham 101008-01R1-2/07 - page 66

    66 ...

  • Burnham 101008-01R1-2/07 - page 67

    67 KEY DESCRIPTION (Quantity) Part Number FCM070 FCM090 FCM120 46 ½" x 1 1" Y ellow Coated CSST , Nut by Nut (1) 100396-01 (1) 100396-01 (1) 100396-01 47 5/8" OD x 1/2" MPT CSST Adaptor (2) 100397-01 (2) 100397-01 (2) 100397-01 48 1/2" Blk Elbow (1) 100539-01 (1) 100539-01 (1) 100539-01 49 Flanged Nipple Assy . (1) 100398- ...

  • Burnham 101008-01R1-2/07 - page 68

    68 ...

  • Burnham 101008-01R1-2/07 - page 69

    69 ...

  • Burnham 101008-01R1-2/07 - page 70

    70 ...

  • Burnham 101008-01R1-2/07 - page 71

    71 KEY DESCRIPTION (Quantity) Part Number FCM070 FCM090 FCM120 102 DISP4D (1) 100450-01 (1) 100450-01 (1) 100450-01 103 Graphic Overlay Mounting Plate (1)100452-01 (1)100452-01 (1)100452-01 104 8-32 Lock Nut (4) 100449-01 (4) 100449-01 (4) 100449-01 105 Zinc Plated Brass Spacer (4) 101031-01 (4) 101031-01 (4) 101031-01 106 8-32 x ¾" Round Hea ...

  • Burnham 101008-01R1-2/07 - page 72

    72 150 151 152 153 154 155 ...

  • Burnham 101008-01R1-2/07 - page 73

    73 156 157 158 159 160 161 ...

  • Burnham 101008-01R1-2/07 - page 74

    74 162 ...

  • Burnham 101008-01R1-2/07 - page 75

    75 NOTES ...

  • Burnham 101008-01R1-2/07 - page 76

    76 Appendix A: Special Requir ements For Side-W all V ented Appliances In The Commonwealth of Massachusetts IMPOR T ANT The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for installation of side-wall vented gas appliances as follows: (a) For all side wall horizontally vented gas fueled equipment installed i ...

  • Burnham 101008-01R1-2/07 - page 77

    77 (d) MANUF ACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the fl ue gases, but identi fi es “special venting systems”, the following requirements shall be satis fi ed by the manufacturer: ...

  • Burnham 101008-01R1-2/07 - page 78

    78 NOTES ...

  • Burnham 101008-01R1-2/07 - page 79

    79 NOTES ...

  • Burnham 101008-01R1-2/07 - page 80

    e. Boilers installed outside the 48 contiguous United States, the State of Alaska, and Canada. f. Damage to the boiler and /or proper ty due to installation or operation of the boiler that is not in accordance with the boiler installation and operating instr uction manual. g. Any damage of failure of the boiler resulting from hard water or scale bu ...

Fabbricante Burnham Categoria Ventilation Hood

I documenti che otteniamo dal fabbricante del dispositivoBurnham 101008-01R1-2/07 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Burnham
- manuali per l’uso 101008-01R1-2/07
- schede prodotto Burnham
- opuscoli
- o etichette energetiche Burnham 101008-01R1-2/07
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Burnham 101008-01R1-2/07.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Burnham 101008-01R1-2/07, manuali di manutenzione, brevi manuali o manuali utente Burnham 101008-01R1-2/07. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Burnham 101008-01R1-2/07.

Manuali per l’uso simili

Manuale completo del dispositivo Burnham 101008-01R1-2/07, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Burnham 101008-01R1-2/07 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Burnham 101008-01R1-2/07.

Il manuale per l’uso completo Burnham, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Burnham 101008-01R1-2/07 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Burnham 101008-01R1-2/07, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Burnham 101008-01R1-2/07 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Burnham 101008-01R1-2/07 - che ci dovrebbe aiutare nei primi passi durante l'uso Burnham 101008-01R1-2/07
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Burnham 101008-01R1-2/07
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Burnham 101008-01R1-2/07 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Burnham 101008-01R1-2/07?

Utilizza il modulo sottostante

Se non hai risolto il problema con Burnham 101008-01R1-2/07 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Burnham 101008-01R1-2/07 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)