Manuale per l’uso Burnham IN10

92 pagine 9.31 mb
Scarica

Vai alla pagina of 92

Summary
  • Burnham IN10 - page 1

    8141049R26-10/08 Price - $5.00 , r e l i o b n o n o i t a m r o f n i g n i k e e s n e h W . r o t c a r t n o c g n i t a e h r u o y l l a c , r e l i o b o t s r i a p e r r o e c i v r e s r o F . l e b a L g n i t a R n o n w o h s s a r e b m u N l a i r e S d n a r e b m u N l e d o M r e l i o B e d i v o r p r e b m u N l e d o M r e l i ...

  • Burnham IN10 - page 2

    2 The New Y ork City Department of Buildings has approved the Independence® Series boiler: Approval No. MEA 154-93-E V ol. III. The City of New Y ork requires a Licensed Master Plumber supervise the installation of this product. The Massachusetts Board of Plumbers and Gas Fitters has approved the Independence® Series boiler . See the Massachusett ...

  • Burnham IN10 - page 3

    3 CAUTION Probe type low water cutoff devices require annual inspection and maintenance! Although these devices are solid state in their operation, the probe is exposed to possible contamination in the boiler water and subject to fouling. Refer to Low W ater Cutoff Service Instructions for complete, step-by-step inspection and cleaning instructions ...

  • Burnham IN10 - page 4

    4 Figure 1: Dimensional Drawing ...

  • Burnham IN10 - page 5

    5 Dimensional Data Heating Surface: 4.35 sq. ft. per ueway (steam); 5.72 sq. ft. per ueway (water) T able of Contents I. P re-I nstallation ..................................... 7 II. Knockdown Boiler Assembly ................ 9 III. Semi-P ak Boiler Assembly .................. 13 IV . P ackaged Boiler A ssembly .................. 15 V . Pipi ...

  • Burnham IN10 - page 6

    6 Figure 2: Section T appings T able 1: T rim and Control Installation in Section T appings T apping Size (NPT) Steam Boiler with Probe L.W .C.O. Steam Boiler with Float L.W .C.O. W ater Boiler W ater Boiler with T ankless Heater A 2 Supply Supply Supply Supply B ½ Bush to ¼ Pressure Gauge Plug Plug Plug C ½ Gauge Glass Nipple & ½ Union Gau ...

  • Burnham IN10 - page 7

    7 I. Pre-Installation A. Inspect shipment carefully for any signs of damage. All equipment is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of boiler to carrier in good condition. Any claim for damage or shortage in shipment must be led immediately against carrier by consignee. No claims for variances or s ...

  • Burnham IN10 - page 8

    8 Figure 3: Clearance to Combustible Materials 5. For boiler located in an unconned space in a building of other than unusually tight construction , adequate combustion and ventilation air is normally provided by fresh air inltration through cracks around windows and doors. 6. For boiler located within unconned space in building of unusual ...

  • Burnham IN10 - page 9

    9 Figure 4: Base Gasket Installation II. Knocked-Down Boiler Assembly W ARNING Installation of this boiler should be undertaken only by trained and skilled personnel from a qualied service agency . A. Install Base-Burner -Manifold Assembly 1. Base-Burner-Manifold is shipped assembled from factory (Gas V alve and Pilot/Burner Assembly is shipped ...

  • Burnham IN10 - page 10

    10 Figure 9: Jacket Assembly Figure 7: Canopy Gasket Installation Figure 8: Canopy Installation D. Install Canopy . 1. Install ½" thick x 1" wide ceramic ber gasket. See Figure 7. 2. Position canopy on ceramic ber gasket. See Figure 8. 3. Attach canopy using ¼" carriage bolts, nuts, and washers provided. E. Inspect joints bet ...

  • Burnham IN10 - page 11

    1 1 Figure 1 1: Pilot and Gas Piping, Continuous Ignition (Standing Pilot) (IN3 through IN9 Only) Figure 13: Pilot and Gas Piping, Intermittent Ignition (EI) (IN3 through IN1 1 Only) Figure 12: Pilot and Gas Piping, Continuous Ignition (Standing Pilot) (IN10 through IN12 Only) Figure 14: Pilot and Gas Piping, Intermittent Ignition (EI) (IN12 Only) ...

  • Burnham IN10 - page 12

    12 Figure 16: Blocked V ent Switch Installation, IN10 through IN12 Figure 15: Blocked V ent Switch Installation, IN3 through IN9 I. Install Blocked V ent Switch with sheet metal screws. 1. Models IN3 - IN9. Install on rear ange of canopy . See Figure 15. 2. Models IN10 - IN12. Install on right side of draft hood. See Figure 16. Reset switch must ...

  • Burnham IN10 - page 13

    13 III. Semi-Pak Boiler Assembly W ARNING Installation of this boiler should be undertaken only by trained and skilled personnel from a qualied service agency . A. Remove Crate 1. Remove all hold down screws and brackets. 2. Slide boiler to rear of skid and carefully remove from crate skid onto 2 inch thick piece of wood and then onto oor . D ...

  • Burnham IN10 - page 14

    14 Figure 20: Thermostat Isolation Relay Attachment 3. All Steam Boilers and W ater Boilers except "EZW" and "WC" Controls Cartons a. Install Junction Box. See Figure 19A. i . Remove center knockout in rear of Junction Box and insert black plastic snap bushing in hole. ii . Install mounting bracket to rear of Junction Box with t ...

  • Burnham IN10 - page 15

    15 Figure 22: Securing Draft Hood to Canopy A. Remove crate and move boiler to permanent position as detailed in Section III: Semi-Pak Boiler Assembly . B. Remove Jacket Front Panel. See Figure 45. C. Remove poly bag from vestibule area. D. On Steam Boilers with probe low water cutoff the L404 pressure limit/control has been packed in the vestibule ...

  • Burnham IN10 - page 16

    16 V . Piping and T rim A. Design and install boiler and system piping to prevent oxygen contamination of boiler water . Sources of oxygen contamination are system leaks requiring addition of makeup water , ttings, and oxygen permeable materials in distribution system. Eliminate oxygen contamination by repairing system leaks, repairing ttings ...

  • Burnham IN10 - page 17

    17 Figure 24: Steam Boiler Piping (Minimum) NOTICE Failure to pipe boiler as specied in this manual may result in excessive system noise, water line uctuations and water carry over . ...

  • Burnham IN10 - page 18

    18 Figure 25: Recommended W ater Piping for Circulator Zoned Heating System ...

  • Burnham IN10 - page 19

    19 Figure 25A: Recommended W ater Piping for Zone V alve Zoned Heating System ...

  • Burnham IN10 - page 20

    20 Figure 27: Recommended Piping for Indirect W ater Heater Figure 28: T ankless Heater Piping Figure 26: Recommended Piping for Combination Heating and Cooling (Refrigeration) Systems E. Alliance Indirect W ater Heater (if used). Refer to Alliance Installation, Operating and Service Instructions for additional information. 1. Steam. See Figure 27 ...

  • Burnham IN10 - page 21

    21 G. If a long term pressure test of the hydronic system is required, the boiler should rst be isolated to avoid a pressure loss due to the escape of air trapped in the boiler . T o perform a long term pressure test including the boiler , ALL trapped air must rst be removed from the boiler . A loss of pressure during such a test, with no vis ...

  • Burnham IN10 - page 22

    22 VI. Gas Piping W ARNING Failure to properly pipe gas supply to boiler may result in improper operation and damage to the boiler or structure. Always assure gas piping is absolutely leak free and of the proper size and type for the connected load. An additional gas pressure regulator may be needed. Consult gas supplier . A. Size gas Piping. Desig ...

  • Burnham IN10 - page 23

    23 T able 4: Fitting Equivalent Lengths T able 5: Specic Gravity Correction Factors for Natural Gas 4. All above ground gas piping upstream from manual gas valve must be electrically continuous and bonded to a grounding electrode. Do not use gas piping as a grounding electrode. Refer to the National Electrical Code , ANSI/NFP A 70 and/or CSA C22 ...

  • Burnham IN10 - page 24

    24 VII. V enting A. Install vent system in accordance with local building codes; or local authority having jurisdiction; or National Fuel Gas Code , ANSI Z223.1/NFP A 54, Part 7, V enting of Equipment and/or CAN/CSA B149.1 Installation Codes. Install any of the following for this Independence Series Category I, draft hood equipped appliance: 1. T y ...

  • Burnham IN10 - page 25

    25 3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. T urn on clothes dryers and any appliance not connected to the common venting system. T urn on any exhaust fans, such as range-hood ...

  • Burnham IN10 - page 26

    26 A. General. Install wiring and ground boiler in accordance with requirements of authority having jurisdiction, or in absence of such requirements the National Electrical Code , ANSI/NFP A 70 and/or CSA C22.1 Electrical Code. B. Wir e V ent Damper (if used). 1. Steam or W ater with gravity circulation or tankless heater . a. Remove one (1) 7/8&qu ...

  • Burnham IN10 - page 27

    27 T able 6: Thermostat Heat Anticipator Settings Set heat anticipator to match system requirements. See T able 6. In general, setting heat anticipator too low will cause boiler to short cycle without bringing heated space up to temperature. Setting heat anticipator too high will allow boiler to operate longer than necessary and overheat space. D. ...

  • Burnham IN10 - page 28

    28 Figure 34: V ent Damper Schematic Wiring Diagram Figure 33: V ent Damper Harness to Limit ...

  • Burnham IN10 - page 29

    29 THIS P AGE LEFT INTENTIONALL Y BLANK ...

  • Burnham IN10 - page 30

    30 Figure 35: Wiring Diagrams, Steam, Continuous Ignition (Standing Pilot), Probe Low W ater Cutoff ...

  • Burnham IN10 - page 31

    31 b . Low W ater Cutoff (L WCO): Automatically interrupts main burner operation when surface of boiler water falls to lowest permissible operating level. Normal operation resumes when water returns to normal level. c . Blocked V ent Switch. Automatically interrupts main burner operation when excessive vent system blockage occurs. Control is a mult ...

  • Burnham IN10 - page 32

    32 Figure 36: Wiring Diagrams, Steam, Intermittent Ignition (EI), Probe Low W ater Cutoff ...

  • Burnham IN10 - page 33

    33 level. Normal operation resumes when water returns to normal level. c . Blocked V ent Switch. Automatically interrupts main burner operation when excessive vent system blockage occurs. Control is a multiple use device. If blocked vent switch is activated do not attempt to place boiler in operation. Correct source of blockage and reset blocked ve ...

  • Burnham IN10 - page 34

    34 Figure 37: Wiring Diagrams, Steam, Continuous Ignition (Standing Pilot), Float Low W ater Cutoff ...

  • Burnham IN10 - page 35

    35 J. Steam Boiler with Continuous Ignition (Standing Pilot) and Float Low W ater Cutoff. See Figure 37. 1. Normal Operation a. Thermostat calls for heat. Thermostat Isolation Relay is energized, closing contacts. b. V ent Damper (if used) opens as stated in V ent Damper Sequence of Operation. c . Gas V alve(s) is energized allowing main gas ow ...

  • Burnham IN10 - page 36

    36 Figure 38: Wiring Diagrams, Steam, Intermittent Ignition (EI), Float Low W ater Cutoff ...

  • Burnham IN10 - page 37

    37 K. Steam Boiler with Intermittent Ignition (EI) and Float Low W ater Cutoff. See Figure 38. 1. Normal Operation a. Thermostat calls for heat. Thermostat Isolation Relay is energized, closing contacts. b. V ent Damper (if used) opens as stated in V ent Damper Sequence of Operation. c . Ignition Module is energized. Pilot V alve opens and Igniter ...

  • Burnham IN10 - page 38

    38 Figure 39: Wiring Diagrams, W ater , Continuous Ignition (Standing Pilot), Intermittent Circulation ...

  • Burnham IN10 - page 39

    39 L. W ater Boiler with Continuous Ignition (Standing Pilot) and Intermittent Circulation. See Figure 39. 1. Normal Operation a. Thermostat calls for heat. b. V ent Damper (if used) opens as stated in V ent Damper Sequence of Operation. c . Gas V alve(s) is energized allowing main gas ow and ignition of Main Burners. d . After Thermostat is sat ...

  • Burnham IN10 - page 40

    40 Figure 40: Wiring Diagrams, W ater , Intermittent Ignition (EI), Intermittent Circulation ...

  • Burnham IN10 - page 41

    41 M. W ater Boiler with Intermittent Ignition (EI) and Intermittent Circulation. See Figure 40. 1. Normal Operation a. Thermostat calls for heat. b. V ent Damper (if used) opens as stated in V ent Damper Sequence of Operation. c . Ignition Module is energized. Pilot V alve opens and Igniter is energized to ignite Pilot Burner . d. Sensor proves pr ...

  • Burnham IN10 - page 42

    42 Figure 41: Wiring Diagrams, W ater , Continuous Ignition (Standing Pilot), Gravity Circulation ...

  • Burnham IN10 - page 43

    43 N. W ater Boiler with Continuous Ignition (Standing Pilot) and Gravity Circulation. See Figure 41. 1. Normal Operation a. Thermostat calls for heat. Thermostat Isolation Relay is energized, closing contacts. b. V ent Damper (if used) opens as stated in V ent Damper Sequence of Operation. c . Gas V alve(s) is energized allowing main gas ow and ...

  • Burnham IN10 - page 44

    44 Figure 42: Wiring Diagrams, W ater , Intermittent Ignition (EI), Gravity Circulation ...

  • Burnham IN10 - page 45

    45 O. W ater Boiler with Intermittent Ignition (EI) and Gravity Circulation. See Figure 42. 1. Normal Operation a. Thermostat calls for heat. Thermostat Isolation Relay is energized, closing contacts. b. V ent Damper (if used) opens as stated in V ent Damper Sequence of Operation. c . Ignition Module is energized. Pilot V alve opens and Igniter is ...

  • Burnham IN10 - page 46

    46 Figure 43: Wiring Diagrams, W ater , Continuous Ignition (Standing Pilot), T ankless Heater ...

  • Burnham IN10 - page 47

    47 P . W ater Boiler with Continuous Ignition (Standing Pilot) and T ankless Heater . See Figure 43. 1. Normal Operation a. Thermostat calls for heat or low limit senses water temperature below set point. b. V ent Damper (if used) opens as stated in V ent Damper Sequence of Operation. c . Gas V alve(s) is energized allowing main gas ow and ignit ...

  • Burnham IN10 - page 48

    48 Figure 44: Wiring Diagrams, W ater , Intermittent Ignition (EI), T ankless Heater ...

  • Burnham IN10 - page 49

    49 Q. W ater Boiler with Intermittent Ignition (EI) and T ankless Heater . See Figure 44. 1. Normal Operation a. Thermostat calls for heat or low limit senses water temperature below set point. b. V ent Damper (if used) opens as stated in V ent Damper Sequence of Operation. c . Ignition Module is energized. Pilot V alve opens and Igniter is energiz ...

  • Burnham IN10 - page 50

    50 IX. System Start-up Figure 47: Gas V alve Pressure T ap, Robertshaw Gas V alve Figure 46: Gas V alve Pressure T ap, Honeywell Gas V alves Figure 45: Front Door Removal W ARNING Completely read, understand and follow all instructions in this manual before attempting start up. A. Safe lighting and other performance criteria were met with the gas m ...

  • Burnham IN10 - page 51

    51 Figure 48: Lighting Instructions, Continuous Ignition System, VR8200 and VR8300 Gas V alves ...

  • Burnham IN10 - page 52

    52 Figure 49: Lighting Instructions, Continuous Ignition System, 7000 ERHC Gas V alve ...

  • Burnham IN10 - page 53

    53 Figure 50: Operating Instruction, Intermittent Ignition System, VR8204 and VR8304 (except IN12) Gas V alves ...

  • Burnham IN10 - page 54

    54 Figure 51: Operating Instructions, Intermittent Ignition System (EI), VR8304 (IN12 only) Gas V alves ...

  • Burnham IN10 - page 55

    55 T able 7: Ignition Module T erminal Cross-Reference Ignition Module T erminal Designation Wiring Ladder Diagram T erminal Number MV 1 MV/PV 2 PV 3 GND 4 24V (GND) 5 24V 6 SP ARK 9 Figure 52: LED Locations Y ellow LED Flash Code a Indicates Recommended Service Action Heartbeat Normal Flame Signal N/A 2 Weak Flame Signal - System will operate reli ...

  • Burnham IN10 - page 56

    56 Green LED Flash Code (X + Y) a Indicates Next System Action Recommended Service Action OFF No “Call for Heat” N/A None Flash Fast Startup - Flame sense calibration N/A None Heartbeat Normal operation N/A None 2 5 minute Retry Delay- Pilot ame not detected during trial for ignition Initiate new trial for ignition after retry delay complete ...

  • Burnham IN10 - page 57

    57 Figure 57: 1" Main Burner Flame Figure 53: Pilot Burner Flame, Honeywell Q350 Figure 55: Pilot Burner Flame, Honeywell Q348 Figure 54: Pilot Burner Flame, Honeywell Q327 Figure 56: 40mm Main Burner Flame F .  Checkpilotburnerameandmainburnerames through observation port. 1. Check pilot ame. a. Continuous Ign ...

  • Burnham IN10 - page 58

    58 2. Adjust thermostat to highest setting. 3. Check main burner ames. See Figure 56 or 57. Flame should have clearly dened inner cones with no yellow tipping. Orange-yellow streaks caused by dust should not be confused with true yellow tipping. 4. Adjust thermostat to normal setting. G. Check thermostat operation. Raise and lower temperature ...

  • Burnham IN10 - page 59

    59 T able 10: Input Rate L. Adjust gas input rate to boiler . LP/Propane. 1. Set thermostat to highest setting. 2. Adjust tank regulator for gas valve inlet pressure of 13.5 inches w .c. or less. 3. Gas valve has step opening regulator which initially opens to 1.4 or 2.5 inch w .c. and steps to full pressure after approximately 30 seconds. Check ma ...

  • Burnham IN10 - page 60

    60 h. Follow instructions T O TURN OFF GAS TO APPLIANCE. See Figure 48, 49, 50, or 51. Drain boiler and system piping. i. Remove drain valve. Thoroughly wash boiler water passages with high pressure spray through drain valve tapping. j. Fill boiler to normal waterline. If water in gauge glass is not clear , repeat procedure starting at step b. k. R ...

  • Burnham IN10 - page 61

    61 1. Boiling Out of Boiler and System. Oil and grease which accumulate in a new hot water boiler can be washed out in the following manner . a . Remove Safety Relief V alve using extreme care to avoid damaging it. b . Partially ll boiler . Pour recommended compound into boiler through safety relief valve opening. c . Replace Safety Relief V alv ...

  • Burnham IN10 - page 62

    62 X. Service Instructions A. General. Inspection and service should be conducted annually , except as noted. T urn off electrical power and gas supply while conducting service or maintenance. Follow instructions T O TURN OFF GAS TO APPLIANCE. See Figures 48, 49, 50 or 51. B. Maintenance of Low W ater Cutoff 1. McDonnell & Miller PS-802 or Hydr ...

  • Burnham IN10 - page 63

    63 5. tightness of joints. Remove all accumulations of soot with wire brush and vacuum Remove all obstructions. Replace all deteriorated parts and support properly . Seal all joints. E. Clean Boiler Flueways. 1. Shut down gas boiler in accordance with lighting/ operating instructions attached to inside of Front Removable Door . See Figure 45. 2. Re ...

  • Burnham IN10 - page 64

    64 CAUTION When necessary to remove burners, be sure to reinstall them in the original manner by engaging the orice and locating hole in the rear of the burner tray . Burners must be aligned with the burner manifold. F . Remove Burners for cleaning, changing orice plugs, or repairs. 1. T urn off electric service to boiler . 2. T urn off gas s ...

  • Burnham IN10 - page 65

    65 M. Excessive Make-Up W ater CAUTION IF , DURING NORMAL OPERA TION, IT IS NECESSAR Y TO ADD MORE W A TER THAN INDICA TED BELOW , CONSUL T A QUALIFIED SERVICE TECHNICIAN TO CHECK YOUR SYSTEM FOR LEAKS. Model No. Gallons Per Month Gallons Per Y ear IN3 0.1 1 IN4 0.1 1 IN5 0.2 2 IN6 0.2 2 IN7 0.2 3 IN8 0.2 3 IN9 0.3 3 IN10 0.3 4 IN1 1 0.3 4 IN12 0.4 ...

  • Burnham IN10 - page 66

    66 Honeywell Electronic Ignition T rouble Shooting Guide ...

  • Burnham IN10 - page 67

    67 Honeywell Hot Surface to Pilot T rouble Shooting Guide ...

  • Burnham IN10 - page 68

    68 Important Produc t Safety Information Refractory Ceram ic Fiber Product Warning : The Repair Parts list designates parts t hat contain refracto ry ceramic fibers (RCF). RCF has been classified as a possible human carcinogen. When exposed to temperatures about 1805°F, su ch as during direct flame contact, RCF changes into crystalline silica, a k ...

  • Burnham IN10 - page 69

    69 XI. Repair Parts All Independence® Repair Parts may be obtained through your local Burnham Wholesale distributor . Should you require assis- tance in locating a Burnham Distributor in your area, or have questions regarding the availability of Burnham products or repair parts, please contact Burnham Customer Service at (717) 481-8400 or Fax (717 ...

  • Burnham IN10 - page 70

    70 Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 I N10 IN1 1 IN12 1. Section Assembly 1A Left End Section (less tankless heater) 7 1710002 2 1 1 1 1 1 1 1 1 1 1 Left End Section (with tankless heater) 7 1710004 2 1 1 1 1 1 1 1 1 1 1 1B Center Section 71710 0031 1 2 3456 7 8 9 10 1C Right End Section 71710001 1 1 1 1 1 1 1 1 1 1 ...

  • Burnham IN10 - page 71

    71 Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 I N10 IN1 1 IN12 2. Canopy and Draft Hood Canopy/Draft Hood Parts 2A Canopy Assembly 61 1 1003 1 --- --- --- --- --- --- --- --- --- 61 1 1004 --- 1 --- --- --- --- --- --- --- --- 61 1 1005 --- --- 1 --- --- --- --- --- --- --- 61 1 1006 --- --- --- 1 --- --- --- --- --- --- 61 1 ...

  • Burnham IN10 - page 72

    72 Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 I N10 IN1 1 IN12 3. Base Assembly 3A Base T ray 71860 0391 1 --- --- --- --- --- --- --- --- --- 71860 0491 --- 1 --- --- --- --- --- --- --- --- 71860 0591 --- --- 1 --- --- --- --- --- --- --- 71860 0691 --- --- --- 1 --- --- --- --- --- --- 71860 0791 --- --- --- --- 1 --- --- ...

  • Burnham IN10 - page 73

    73 Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 I N10 IN1 1 IN12 3. Base Assembly (Continued) 3B2 Base Rear Insulation 72060035 1 --- --- --- --- --- --- --- --- --- 72060045 --- 1 --- --- --- --- --- --- --- --- 72060055 --- --- 1 --- --- --- --- --- --- --- 72060065 --- --- --- 1 --- --- --- --- --- --- 72060075 --- --- --- - ...

  • Burnham IN10 - page 74

    74 Manifold and 1" Main Burners Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 I N10 IN1 1 IN12 3. Base Assembly (Continued) 3F Burner Access Panel 71860 0361 1 --- --- --- --- --- --- --- --- --- 71860 0461 --- 1 --- --- --- --- --- --- --- --- 71860 0561 --- --- 1 --- --- --- --- --- --- --- 71860 0661 --- --- --- 1 --- -- ...

  • Burnham IN10 - page 75

    75 Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN1 0 IN1 1 I N12 4. Manifold and Main Burners (1 Inch Main Burners Only) 4A Main Burner 8236099 2 4 6 8 1 1 13 15 17 20 22 4B Main Burner with Pilot Bracket (Continuous Ignition) (Q350 Pilot) 8236097 1 1 1 1 1 --- --- --- --- --- Main Burner with Pilot Bracket (Continuous Ignitio ...

  • Burnham IN10 - page 76

    76 Manifold and 40mm Main Burners Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 4. Manifold and Main Burners (40MM MAIN BURNERS ONL Y) 4A Main Burner 8236135 1 2 3456 7 Intermittent Ignition Only 4B Main Burner with 41° Pilot Bracket 8236136 1 1 1 1 1 1 1 24-V olt Continuous Ignition (Standing Pilot) Natural Gas 4B Main Burner ...

  • Burnham IN10 - page 77

    77 Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 4. Manifold and Main Burners (40MM MAIN BURNERS ONL Y) Continued Natural Gas, High Altitude (2000-5000 Ft.) USA Only 4D Main Burner Orice #39 822727 2 3 --- --- --- --- --- Main Burner Orice #38 822720 --- --- 456 7 8 LP Gas, High Altitude (2000-5000 Ft.) USA Only 4D Main Bu ...

  • Burnham IN10 - page 78

    78 Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 I N10 IN1 1 IN12 5. Pilot Burner and Gas V alve, Continuous Ignition (Standing Pilot), Natural Gas 5A Pilot Burner , Honeywell Q350A1321 8236065 1 1 1 1 1 --- --- --- --- --- Pilot Burner , Honeywell Q327A1006 8236022 --- --- --- --- 1** 1 1 1 1 1 5B Pilot Orice, Honeywell 3906 ...

  • Burnham IN10 - page 79

    79 Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 I N10 IN1 1 IN12 5. Pilot Burner and Gas V alve, Intermittent Ignition (EI), Natural Gas 5A Pilot Burner , Honeywell Q348A1002 8236072 1 1 1 1 1 1 1 1 1 1 5B Pilot Orice, Honeywell 388146NE Included with 5A 1 1 1 1 1 1 1 1 1 1 5C Compression Nut/Fitting, 1/4" OD x 1/4 C.C. ...

  • Burnham IN10 - page 80

    80 ...

  • Burnham IN10 - page 81

    81 Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 I N10 IN1 1 IN12 Jacket Assembly 1 Left Side Panel 60410013 1 1 1 1 1 1 1 --- --- --- 60410023 --- --- --- --- --- --- --- 1 1 1 2 Right Side Panel 60410012 1 1 1 1 1 1 1 --- --- --- 60410022 --- --- --- --- --- --- --- 1 1 1 3 Front Removable Panel 60410033 1 --- --- --- --- --- ...

  • Burnham IN10 - page 82

    82 Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 I N10 IN1 1 IN12 Jacket Assembly (Continued) - Refer to Figure on Page 80 5A Upper Left Rear Panel (not shown) 604101 051 --- --- --- --- --- --- --- 1 1 1 5B Upper Right Rear Panel (not shown) 6041010 52 --- --- --- --- --- --- --- 1 1 1 6A Front T op Panel 60410036 1 --- --- --- ...

  • Burnham IN10 - page 83

    83 Key No. Description Part No. Quantity Steam T rim 7A Safety V alve, 3/4 NPT , 15 psi, Conbraco 13-51 1-08 81660530 1 7B Elbow , 3/4 NPT 806601502 2 7C Nipple, 3/4 NPT x 3" 806600002 2 8A Low W ater Cutoff, McDonnell & Miller PS-802-24 (Probe Included) 80160720 1 Low W ater Cutoff, Hydrolevel CG400-2090 (Less Probe - See Key No. 8B) 8016 ...

  • Burnham IN10 - page 84

    84 ...

  • Burnham IN10 - page 85

    85 Key No. Description Part No. IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN10 IN 1 1 IN12 W ater T rim 7A Safety Relief V alve, 3/4 NPT , 30 psi, Conbraco 10-407-05 81660363 1 1 1 1 1 1 1 1 1 1 7B Elbow , 3/4 NPT 806601520 1 1 1 1 1 1 1 1 1 1 7C Nipple, 3/4 NPT x 3" 806600002 2 2 2 2 2 2 2 2 2 2 8A Circulator , Bell & Gossett NRF-22 with Gaskets 805617 ...

  • Burnham IN10 - page 86

    86 Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN10 IN1 1 IN12 T ransformer/J-Box Adapter Plate 1 Junction Box, 4-1 1/16" x 4-1 1/16" x 2-1/8" 81361761 1 1 1 1 1 1 1 1 1 1 2 T ransformer/J-Box Adapter Plate 701 1001 1 1 1 1 1 1 1 1 1 1 3 Sheet Metal Screw , #8 x 1/2, T ype B, Phillips Head, Blunt 80860019 2 2 2 ...

  • Burnham IN10 - page 87

    87 THIS P AGE LEFT BLANK INTENTIONALL Y ...

  • Burnham IN10 - page 88

    88 ...

  • Burnham IN10 - page 89

    89 Key No. Description Part No. Quantity IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN10 IN1 1 IN12 12. T ransformer (Steam and Gravity Water Only) 12A Junction Box, 4-1 1/16" x 4-1 1/16" x 2-1/8" Refer to T able on Page 86 12B T ransformer , 50 V A, Honeywell A T150D1019 80160186 1 1 1 1 1 1 1 1 1 1 12C Relay , SPST , Honeywell R8222K1000 80160127 ...

  • Burnham IN10 - page 90

    90 A 24 V AC L WCO is used primarily for gas red boilers where a 24 volt control circuit exists within the boiler . However , a 24 V AC L WCO can only be used if the boiler manufacturer has provided piping and wiring connections and instructions to allow for this application. How to T est Shut off fuel supply . Lower water level until water leve ...

  • Burnham IN10 - page 91

    91 if the residential grade water boiler is used or operated over its rated capacity, is subjected to unauthorized modification, or is damaged as a result of being otherwise improperly operated or serviced including, but not limited to, damage from any of the following: operation with insufficient water, allowing the boiler to freeze, subjecting th ...

  • Burnham IN10 - page 92

    92 By this Warranty Statement the U.S. Boiler ™ Company, Inc. of Lancaster, Pennsylvania issues limited warranties subject to the terms and conditions stated below. These limited warranties apply to residential cast iron boilers labeled Independence ® , Independence ® PV, V8H ™ and MegaSteam ™ Series, these warranties are issued only to the ...

Fabbricante Burnham Categoria Boiler

I documenti che otteniamo dal fabbricante del dispositivoBurnham IN10 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Burnham
- manuali per l’uso IN10
- schede prodotto Burnham
- opuscoli
- o etichette energetiche Burnham IN10
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Burnham IN10.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Burnham IN10, manuali di manutenzione, brevi manuali o manuali utente Burnham IN10. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Burnham IN10.

Manuali per l’uso simili

Manuale completo del dispositivo Burnham IN10, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Burnham IN10 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Burnham IN10.

Il manuale per l’uso completo Burnham, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Burnham IN10 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Burnham IN10, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Burnham IN10 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Burnham IN10 - che ci dovrebbe aiutare nei primi passi durante l'uso Burnham IN10
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Burnham IN10
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Burnham IN10 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Burnham IN10?

Utilizza il modulo sottostante

Se non hai risolto il problema con Burnham IN10 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Burnham IN10 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)